GEM-P816 Installation Instructions
NAPCO Security Systems
WI994A 10/99
Page 34
Fire; Keypad Fire
Any zone may be programmed for Fire. Connect normally-open devices across a Fire Zone. (The EOL2.2K end-of-line resistor must
be installed.) A short across the zone will cause a fire alarm, which will be indicated at the keypad by a “
” LCD display and
pulsing sounder. An open circuit on the Fire Zone will identify a trouble and cause flashing “
#
” LCD
display and pulsing sounder after a 10-second delay. The sounder may be silenced by pressing the
button. The LED will go
off within 30 seconds after reset if the alarm or trouble is cleared. For Smoke-Detector Reset, see Alarm Outputs. Fire or Keypad Fire
can be made to trip an alarm or report to Central Station. If Keypad Fire is programmed, pressing both the
and
buttons
at the same time will sound a fire panic alarm and display “
” at the keypad. The Keypad Fire function is supplementary to
the hardwired zones. Note: This feature shall not be considered a substitute for listed manual initiating devices. A fire condition that
has not been restored will cause the zone number and description to scroll. To reset (acknowledge) the condition, enter a valid code,
then press the
button.
Fire Verification (Not for use in California.)
An alarm on any Fire Zone programmed for “Fire Verification” and connected to the fire power terminal will cause all fire zones to be
powered down for 12 seconds. (All devices must be wired with + power on Terminal 25.) After this time, power is restored and a
4-second power-up time is started. Thereafter, the zone will be active again. This represents a total processing delay of 16 seconds
from the time the alarm is first detected. If an alarm condition still exists at this time or reoccurs within 2 minutes, an alarm will be
initiated, otherwise the zone will return to its original state. NOTE: A zone programmed for “Fire Verification” must be programmed as
a “Fire Zone” as well.
Include Selective Bypass In Conditional Closing/Status See Closing Report; Interior Zones
Removal of a programmed group of interior zones from the system will permit freedom of movement throughout the premises but still
allow protection from intrusion through armed perimeter zones. Pressing the
button prior to arming will select the Interior
Zones, then arm to bypass. The next time the control panel is disarmed, all bypassed zones will automatically revert to non-bypassed
(disarmed) zones. When the
button is pressed, the “
” reminder will come on. The bypassed zones may be displayed
on the keypad (see GEM-RP1CAe2 FUNCTION MODE).
Jumpers (Refer to Wiring Diagram for UL configuration)
JP1: Keypad Configuration Jumper (top center, above micro shield) is installed across top and center pins for normal operation. When
configuring GEM-RP1CAe2 keypads, move jumper across center and lower pins.
JP3: 2-Wire Fire jumpers. Select Zones 7 and/or 8 for use as either 2-Wire Fire Zones or Burglary Zones. Note: If customizing a
single-area default program, Zone 8 is configured as a 2-Wire Fire Zone. In a two-area default program, Zones 7 and 8 are configured
as 2-Wire Fire Zones common to both areas; be sure to move JP3 Zone-7 jumper to the 2-WF position (see Wiring Diagram).
Gem-Print
A printer can be made to print all operations directly from the panel, when programmed for “Enable GEM-PRINT Module” and a
separate Gem-Print Module is added to the panel.
GEM-RP1CAe2 Keypad Jumpers
Refer to label LA1374 on the circuit board fishpaper for jumper locations and a summary of settings.
JP1: Cut to enable Keypad Tamper.
W1 & W3: Cut both to disable touch pad backlighting.
W2: Cut to disable LCD backlighting.
GEM-RP2ASe2 Keypad Jumpers
Refer to label LA1390 on the circuit board fishpaper for jumper locations and a summary of settings. See Section 3: Configuring the
GEM-RP2ASe2 Keypad for jumper selection.
Glossary
: Fire to GEM
-RP2A
Se2 Key
p
ad Jumpers