background image

2

 

NOTE:

    Smoke  detectors  are  not  to  be  used  with 

detector  guards  unless  the  combination  has  been 

evaluated and found suitable for that purpose.

 

Pick  smoke

-

detector  location.   

Referring to the 

NFPA standard on page 3, select a suitable loca-

tion to mount the detector.  

Note:

  

Mounting the detector 

on  foil

-

backed  wallpaper  is  NOT  recommended  be-

cause the radio range will be reduced.

 

Install  mounting  plate.   

Use  the  two  screws 

and  anchors  provided  to  attach  the  mounting 

plate to the wall or ceiling.  

NOTE:   

Do not install on 

removable surfaces such as ceiling tiles.

 

Map the Transmitter.  

Referring to the instructions 

for the control  panel  and keypad  in  use, enter  the 

following:

 

 

• 

the zone to which the transmitter will be mapped;

 

• 

the  6

-

digit  RF  identification  number/1

-

digit  check-

sum  number  printed  on  the  transmitter  (include  all 

numbers  and/or  letters  and  leading  zeros,  if  any); 

and

 

• 

the transmitter point number ("1").

 

 

NOTE:

    In  fire  alarm  installations,  the  control  panel 

must be programmed to activate the fire alarm bells or 

horns upon detection of a fire.

 

Low Battery Chirp Silence

 

Allows  temporary  disabling  of  the  Low  Battery  Chirp 

("sleep")  for  12  hours.    Press 

TEST 

button  during  low 

battery condition to enter mode.

 

Smoke Alarm

 

Sounder and red LED both turn on continuously.

 

Silencing the Unit

 

To silence the unit during a smoke alarm, press and hold 

the 

TEST 

button  for  10  seconds  to  temporarily  silence 

the unit for 5 minutes.

 

Maintenance Warning

 

The  smoke  detector  will  warn  that  it  must  be  cleaned 

when the unit flashes the red LED every 5 seconds and 

the unit does not pass the weekly test by the user (see 

#8  at  left).    To  clean  the  smoke  detector,  vacuum  the 

outside of the unit at least once a year (preferably every 

six  months)  using  a  soft  brush  attachment.   

Do  not  at-

tempt to clean the unit in any other way.  

If this mainte-

nance procedure fails to clean the unit sufficiently, call for 

service  and/or  replace  the  unit.   

Note:

    A  Gemini  C

-

Series  (GEMC)  control  panel  indicates  an  E66 

"CleanSMK"  system  trouble  when  a  maintenance 

warning is detected.

 

Test  system  weekly  with  unit  mounted.   

If the 

system  is  monitored,  notify  central  station  of  im-

pending test.  Press and hold 

TEST 

button (using a 

non

-

conductive  pointed object such  as a  toothpick) for 5 

seconds  after  the  local  alarm  sounds.    The  sounder  will 
turn on while the button is pressed; if the unit is operating 
within its proper sensitivity limits and is not in a low battery 
condition, the green LED turns off and the red LED turns 
on continuously.  Verify that the detector triggers the cor-
rect zone in the control panel and that the correct report is 
sent to the central station.

 

Attach  the  detector  to  mounting  plate.  

Match up alignment tabs on detector and plate.  

Turn detector clockwise until it locks into place.

 

TWIST  

DETECTOR 

CLOCKWISE 

TO LOCK TO 

MOUNTING 

PLATE 

 

 

 

 

 

 

DINING 

ROOM

 

KITCHEN

 

SMOKE 

DETECTOR

 

BEDROOM

 

BEDROOM

 

LIVING 

ROOM

 

BEDROOM

 

 

4

 

 

5

 

 

6

 

 

7

 

 

8

 

MATCH UP 

ALIGNMENT 

TABS 

HOLD BUTTON FOR AT LEAST 5 SECONDS 
AFTER LOCAL ALARM SOUNDS TO SEND 

AN ALARM TRANSMISSION 

PRESS AND HOLD 

TEST 

BUTTON BY 

INSERTING NON-CONDUCTIVE 

POINTED OBJECT 

SCREW ANCHORS FOR 

WALLBOARD 

THIS SIDE TO 

CEILING 

Note:

    Use  System  Sensor  model  SENS

-

RDR  to  verify 

smoke  detector  sensitivity  as  required  by  the  NFPA  in 

Commercial  installations.    For  Go/No  Go  test,  use  UL 

Listed SDi SOLOA4 and SDi SMOKESABRE canned aer-

osol products to verify smoke detector trips into alarm.

 

Отзывы: