5 General concepts
Ready to switch on
Transition to the Ready to switch on state (shutdown option):
In this case, the action stored in object 605B
is executed (see following table).
Value in object 605B
h
Description
-32768 … -1
Reserved
0
Immediate stop
1
Braking with slow down ramp (braking deceleration depending on
operating mode) and subsequent state change to Switch on disabled
2 … 32767
Reserved
Switched on
Transition to the Switched on state (disable operation option):
In this case, the action stored in object 605C
is executed (see following table).
Value in object 605C
h
Description
-32768 … -1
Reserved
0
Immediate stop
1
Braking with slow down ramp (braking deceleration depending on
operating mode) and subsequent state change to Switch on disabled
2 … 32767
Reserved
Halt
The bit is valid in the following modes:
•
•
•
•
•
When setting bit 8 in object 6040
h
(controlword), the reaction stored in 605D
is executed (see
following table):
Value in object 605D
h
Description
-32768 … 0
Reserved
1
Braking with slow down ramp (braking deceleration depending on
operating mode)
2
Braking with quick stop ramp (braking deceleration depending on
operating mode)
3 … 32767
Reserved
Fault
Case of an error (fault):
If an error occurs, the motor will brake according to the value stored in object 605E
h
.