Page 9
3/21 IOM-ELECTRA-FLO-INST
Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.
2.3.1 G5 Power/Signal Connections
1. Input power requirements:
• 24 VAC (20 - 28 VAC), 16 - 90 VA, varies based on number of
sensors.
• 24 VDC (20 - 28 VDC), 16 - 50 W, varies based on number of
sensors.
2. Alarm can be set for either flow or temperature with upper and
lower limits. Refer to page 16 for more information.
2.3.2 G5 Analog Outputs and Serial Communication
IMPORTANT NOTE
Two (2) analog outputs (4 - 20 mA, 0 - 10 VDC or 0 - 5 VDC) are
available based on configuration. Refer to page 15 for more
information.
BACnet
D+ D- G SH
NO C NC
L
N
24 V INPUT PWR
J2
J1
J3
J4
G
ALARM
AO1 / AO2
+ COM / + COM
S1
TERM
BIAS
TB - J4
INPUT POWER
GROUND (G)
(-) COMMON (N)
(+) 24 V AC/DC (L)
NORMALLY CLOSED CONTACT (NC)
COMMON (C)
NORMALLY OPEN CONTACT (NO)
TB - J3
ALARM
CONNECTION
1
2
BACnet
D+ D- G SH
NO C NC
L
N
24 V INPUT PWR
J2
J1
J3
J4
G
ALARM
AO1 / AO2
+ COM / + COM
S1
TERM
BIAS
TB - J2
SERIAL
COMMUNICATION
SHIELD (SH)
RS485 COMMON (G)
(-) RS485 (D)
(-) AO2 COMMON
(+) AO2
(-) AO1 COMMON
(+) RS485 (D)
(+) AO1
TB - J1
AO OUT 1 & 2