3.3 MAIN MENU continued
Analog Output Configuration
-
The Airflow G5 transmitter is equipped with dual analog outputs.
The Analog Output Configuration menu configures the analog
output type, parameter and filter.
Output Type:
4 - 20 mA DC, 0 - 5 VDC or 0 - 10 VDC
Output 1 and 2:
Flow, Velocity or Temperature
Optional True Dual Channel Version
Output 1:
Flow, Temperature or SYS1 Flow Add
Output 2:
Flow, Temperature or SYS2 Flow Subt
Airflow:
Available on connector J1, terminals AO1+ and AO1-
or AO2+ and AO2-. The full scale output is equal to Max Flow as
programmed into the ELECTRA-flo G5 transmitter on the Flow
Configuration menu.
Temperature:
Available on connector J1, terminals AO1+ and
AO1- or AO2+ and AO2-. The temperature analog output has a
fixed scale of -40°F to 140°F (-40°C to 60°C).
The filter has a minimum setting of 0 to a maximum setting of
10. To disable the filter, select Off.
IMPORTANT NOTE: Optional True Dual Channel Version
• Sys1 and Sys2 full scale flow values are set in the Sys1
and Sys2 flow configuration menus
• Sys1 Flow Add full scale = Sys1 max flow + Sys2 max flow
• Sys2 Flow Subt full scale = Sys1 flow max
ANALOG OUTPUT CONFIGURATION
OUTPUT TYPE:
OUTPUT 1:
OUTPUT 2:
FILTER:
ENT - ACCEPT ESC - LEAVE UP/DN - CHANGE
4-20 mA
TEMPERATURE
4
FLOW