![Nailor ELECTRA-FLO G5 Скачать руководство пользователя страница 27](http://html1.mh-extra.com/html/nailor/electra-flo-g5/electra-flo-g5_operation-and-maintenance-manual_703949027.webp)
Page 27
3/21 IOM-ELECTRA-FLO-INST
Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.
INPUT REGISTERS FOR SYSTEM VARIABLES
DESCRIPTION
ADDRESS
DATA TYPE
DESCRIPTION
System Velocity Units
30400
uint16_t
1 = FPM, 2 = FPS, 3 = MPM, 4 = MPS
System Flow Units
30401
uint16_t
1 = CFM, 2 = CFH, 3 = L/S, 4 = L/M, 5 = M3H
Version
30402
uint16_t
MSB = Major, LSB = Minor
30403
uint16_t
MSB = Patch, LSB = Build Number
System Status 1
30404
uint16_t
1 = ALL_OK, 2 = IN ALARM, 3 = IN FAULT, 4 = 00S
System Node Total 1
30405
uint16_t
1 = 32 NODES ALLOWED
Duct Shape 1
30406
uint16_t
1 = Rect, 2 = Round, 3 = FLAT OVAL
Design Flow Max 1 Setting
30407
float
Max Flow to scale Analog Outputs
Duct Area 1
30408
float
Duct area size in ft
2
or m
2
System Status 2
30409
uint16_t
1 = ALL_OK, 2 = IN ALARM, 3 = IN FAULT, 4 = 00S
System Node Total 2
30410
uint16_t
1 = 32 NODES ALLOWED
Duct Shape 2
30411
uint16_t
1 = Rect, 2 = Round, 3 = FLAT OVAL
Design Flow Max 2 Setting
30412
float
Max Flow to scale Analog Outputs
Duct Area 2
30413
float
Duct area size in ft
2
or m
2
DISCREET INPUTS FOR SYSTEM VARIABLES
DESCRIPTION
ADDRESS
DATA TYPE
DESCRIPTION
Sensor Enabled
10000
boolean
Bit0-Bit15 Sensor Enabled
Sensor Enabled
10001
boolean
Bit16-Bit31 Sensor Enabled
System Units
10002
boolean
Coil 1: 1 = Sl, Bit 0: 0 = US
System Conditions
10002
boolean
Coil 2: 1 = Std, Bit 0: 0 = Actual
Rules for Discrete Inputs (2x)
Up to 32 Registers can be requested from 20000 addresses or 20002 addresses.
Any other address returns "Illegal Address"
No more than 32 registers can be requested. Anymore than 32 will return "Illegal Address"
System Conditions has a maximum of (2) registers from the base address 20004
COILS FOR SYSTEM VARIABLES
DESCRIPTION
ADDRESS
DATA TYPE
DESCRIPTION
K-factor 1
00001
boolean
1 = ON, 0 = OFF
K-factor 2
00002
boolean
1 = ON, 0 = OFF
System Reset
00003
boolean
1 = RESET
K-factor 1
00004
boolean
Returns the state of the K-factor
K-factor 2
00005
boolean
Returns the state of the K-factor
DESCRIPTION
ADDRESS
DATA TYPE
DESCRIPTION
report slave ID
17
ASCII
Returns string "ELECTRA-flo G5"