background image

Page 5 of 24

9/18  IOM-FFDINST

Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.

INSTALLATION

The Fan Filter Diffuser is fully assembled from the factory with the exception of the HEPA filter and lamps (if applicable) which

are shipped separately.

Step 1

Carefully remove the unit from the shipping carton and inspect for damage that may have occurred during

shipping. If shipping damage is found, do not install. Call the manufacturer to report damage.

Step 2

Wipe down the unit to remove shipping dust and debris.

Step 3

Raise unit into ceiling and lower onto gasketed opening. Gasket should be a closed-cell material approved for the

environmental conditions. It is recommended to further support the unit from above using the tabs welded to the plenum.

Step 4

A qualified technician should wire the unit to the appropriate power supply per applicable codes and standards.

Refer to the wiring diagram (Figure 4) on page 23 of these instructions.
92FFD, 92FFD-SS – V18 120 VAC Supply

92FFD, 92FFD-SS – V19 208 VAC Supply

92FFD, 92FFD-SS – V20 240 VAC Supply

92FFD, 92FFD-SS – V21 277 VAC Supply

Step 5

Blow out/clean entire duct system leading to the unit to remove construction debris. This is especially important

for motor accessible units as they do not have a pre-filter. Wash pre-filter (if applicable), per “Cleaning the Fan

Filter Unit Pre-filter” below.

Step 6

Install the HEPA filter per the “Removal and Replacement of the HEPA Filter with Gel Seal” section on page 6.

CLEANING THE FAN FILTER DIFFUSER PRE-FILTER

WARNING!  Disconnect the unit from the electrical power source before attempting to service the unit.

Note: For maximum performance, wash pre-filter every three to six months at minimum.

Step 1

Turn off the unit with the rocker switch located on the unit.

Step 2

Disconnect the unit at the power source or at the service panel.

Step 3

Using a driver, remove the screw holding the hinged door. This allows access to the pre-filter. Slide the pre-filter

out of the motor enclosure.

Step 4

Wash the filter with hot water and a mild detergent and rinse thoroughly. Do not use a caustic solution to clean the

filter. Blow dry or let air dry and slide the filter back into the motor enclosure. 

Filter should be completely dry

before reinstalling into unit.

Step 5

Using a driver, re-secure the cover with the screw.

A NOTE ABOUT VAV BOXES AND DUCTED APPLICATIONS

In applications where the Fan Filter Diffuser unit will be installed downstream of variable airflow devices such as VAV boxes, air

valves, or variable air handlers, proper care in unit set-up needs to be taken.

The unit should not be programmed to run as constant airflow in this application.

Two variable controllers trying to reach

their respective set point will continuously adjust. This will cause issues such as surging, starving and eventual shut down of

the fan filter unit. The units should be ordered with a constant torque program. This will remove the dirty filter ramp-up feature

and the cfm display will no longer be accurate. However, this is still preferable to a PSC system due to the energy efficiency of

an EC versus a PSC motor.

Ducted applications While the fan filter unit can handle some positive or negative static pressure, optimal performance and

reliability will be achieved with an inlet static pressure of 0.0 w.c. or slightly negative.

To reach an accurate 0.0 w.c. inlet static, it is recommended that the primary air balancing of the duct system be done before

installing the fan filter unit. When the duct is at optimal static, install the unit per these instructions and adjust the airflow to the

design setting. Verify the airflow with an airflow hood. 

It is recommended that all fan filter units in the system be energized before any upstream devices to prevent the FFD blower

wheel from spinning backwards. While the motor can generally overcome this, if the airflow needed to overcome high static is

too great, it may not. This will cause the motor to shut down. Continual running of the motor backward may result in reduced

reliability of the EC motor.

Содержание 92FFD

Страница 1: ...Fan Filter Diffuser Models 92FFD 92FFD SS Read completely and save these instructions for future reference M A N U A L M A N U A L I O M INSTALLATION OPERATION MAINTENANCE ...

Страница 2: ... Kit FPH RP36 FPH 120 24 VAC Transformer FPH RP37 FPH 208 240 24 VAC Transformer FPH RP38 FPH 277 24 VAC Transformer FPH RP39 FPH Network Power Control Circuit Board FPH RP40 FPH Face Mounted Airflow Display Board FPH RP41 FPH Multi input Control Board Dimensions are in inches mm WARNING TO REDUCE THE RISK OF FIRE ELECTRIC SHOCK OR INJURY TO PERSONS ALLOW ONLY QUALIFIED TECHNICIANS TO INSTALL AND ...

Страница 3: ... produce 0 0 w c static pressure at the fan unit inlet Use dampers if necessary when installing multiple fan units on the same duct line See page 5 for details Install the fan unit into the ceiling Support its weight from structure above Connect ductwork to fan unit if applicable Seal the fan filter unit to the ceiling using gasketing and caulking if required Connect main power wiring Connect cont...

Страница 4: ...of the Fan Filter Diffuser 2 Warning 2 Installation Checklist 3 FFD Installation 5 Cleaning the FPH Pre filter 5 Removal and Replacement of the Gel Seal HEPA Filter 6 Removal and Replacement of the EC Motor 7 Access to Electrical Components 8 On Off Switch Airflow Adjustment 10 Resettable Fuse Main Power Switch 11 Digital Airflow Control 11 PAO Challenge System 12 Controls MODBUS BACnet 13 BACnet ...

Страница 5: ... the hinged door This allows access to the pre filter Slide the pre filter out of the motor enclosure Step 4 Wash the filter with hot water and a mild detergent and rinse thoroughly Do not use a caustic solution to clean the filter Blow dry or let air dry and slide the filter back into the motor enclosure Filter should be completely dry before reinstalling into unit Step 5 Using a driver re secure...

Страница 6: ...ilter easier loosen the nuts until flush with the end of the threaded stud USE TWO PEOPLE TO SUPPORT THE FILTER and rotate the filter clips toward the offset hole until clip is clear of the filter Step 5 Allow gravity to pull the filter away from the unit If installing a new filter discard the filter in an appropriate manner Step 6 Unpack the new filter and inspect for shipping damage If damage is...

Страница 7: ...rivets located around the motor housing cover Set cover aside Clean out metal shavings and rivet parts from the unit NOTE If duct is attached to cover be careful not to damage duct Disconnect duct if necessary Step 5 Disconnect the 6 pin power cable and the 4 pin data cable from the motor Step 6 Using the 7 16 11 nut driver remove the six nuts holding the motor Step 7 Lift the motor fan ring assem...

Страница 8: ...cedures Step 3 Use a 5 16 10 hex driver to remove screws holding electrical access panel Swing panel up to release from the tabs Step 4 To remove transformer Step 4a Disconnect all wires from terminals See wiring diagram for replacing wires Step 4b Using a 1 8 3 drill bit drill out the two rivets Clean debris Step 4c Use new 1 8 3 rivets or 6 screws to install replacement transformer Step 5 To rem...

Страница 9: ...sing a flat screwdriver release the mid panel by rotating the three 3 fasteners a 1 4 turn counter clock wise Allow panel to swing down to vertical and remove from unit Set aside Step 6 Use a 5 16 10 hex driver to remove screws holding electrical access panel find them in the 1 4 6 round holes in foam Slide panel over to release from the slots Step 7 To remove transformer Step 7a Disconnect all wi...

Страница 10: ...Page 10 of 24 9 18 IOM FFDINST Nailor Industries Inc reserves the right to change any information concerning product or specification without notice or obligation ...

Страница 11: ...nnect can be added by others per local codes and regulations NOTE 277 VAC units do not have the fuse NOTE When a unit from a room side removable blower motor and or controls is installed in an area with no access above the ceiling the main power switch must be turned on before installing into the ceiling DIGITAL AIRFLOW CONTROL The FPM includes a Digital Airflow Control unit to adjust the airflow ...

Страница 12: ...test is performed Step 1 Using a flat screwdriver release the face frame by rotating the four 4 fasteners a 1 4 turn counter clock wise Unhook the safety cables from the filter clips Set the frame aside Step 2 Remove cap from PAO concentration port brass Attach UPSTREAM hose 1 4 6 ID from photometer to PAO concentration port Step 3 Remove cap from PAO challenge supply port aluminum Attach DOWNSTRE...

Страница 13: ... be determined before ordering 3 0 10 V 0 5 V DC Control 4 0 20 mA 4 20 mA Control 5 Full range of network controls including connection to BAS BMS through MODBUS RTU RS 485 control BAC Net IP BACNet MS TP LON Works available with additional hardware Additionally monitoring and controls of the fan filter unit can be done through closed loop control from sensors such as pressure transducers thermos...

Страница 14: ...gs next page 5 Connect to power 9 30 VDC 12 24 VAC 2 5 W 6 Verify operation see ACGW007 User Guide MOUNTING The ACGW007 can be mounted to a flat surface or to a DIN rail Remove the DIN rail cleat prior to mounting to a flat surface so that the two mounting flanges will be in contact with the surface and not raised Page 14 of 24 9 18 IOM FFDINST Nailor Industries Inc reserves the right to change an...

Страница 15: ...et MS TP Baud Rate The Baud Rate should be set to match upstream BMS BACnet MS TP Baud Rate 3 S0 S2 BACnet MS IP or BACnet MS TP Switches S0 S2 select upstream BACnet protocol Verify switches S0 S2 are set in agreement with your system 4 S3 AutoDiscovery Switch OFF Switches S3 enables AutoDiscovery S3 should be in the OFF position to allow for control of AutoDiscovery using the web browser interfa...

Страница 16: ...ms in new systems WHAT TO EXPECT One unit will be clearly labelled MASTER UNIT This unit will contain the ACC1001 25 and power supply The power supply can be left in the master unit control box and control board can be mounted anywhere in the space including at the master unit Page 16 of 24 9 18 IOM FFDINST Nailor Industries Inc reserves the right to change any information concerning product or sp...

Страница 17: ...pecification without notice or obligation A JPS Bias input power isolated B JP2 Accessory output voltages C JVDC Selector for 10 V regulated or unregulated rectified and filtered bus voltage D J1 EC Motor Port E JVS1 INP1 10 V signal range selector F JP1 INP1 and INP2 analog digital inputs G JVS2 INP2 10 V signal range selector H JLED External FAULT output J JPUD2 INP2 digital input pull up or 20 ...

Страница 18: ...ded to be used with analog setpoint input ADDRESS SELECTION When adjusted to the ON position each DIP switch pole represents a value as follows Calculate the address value of existing switch settings by adding the values of each DIP switch pole in the ON position per the table below Construct switch settings for a desired address value by successively subtracting the largest pole value that is les...

Страница 19: ...wer supplied connect COM VSEL with V RFU shunt Full wave rectified power supplied 33 VDC INP1 on JP1 wiring block is for monitoring only 0 10 VDC 0 5 VDC 0 20 mA 4 20 mA INP2 on JP1 wiring block is for closed loop feedback monitoring Controller airflow by room pressure or particle counter Page 19 of 24 9 18 IOM FFDINST Nailor Industries Inc reserves the right to change any information concerning p...

Страница 20: ...specification without notice or obligation DIP Switch Pole Value 1 1 2 2 3 4 4 8 5 16 6 32 7 64 8 128 ON DIP 1 2 3 4 5 6 7 8 30 ON DIP 1 2 3 4 5 6 7 8 3 ON DIP 1 2 3 4 5 6 7 8 4 ON DIP 1 2 3 4 5 6 7 8 5 ON DIP 1 2 3 4 5 6 7 8 6 ON DIP 1 2 3 4 5 6 7 8 7 ON DIP 1 2 3 4 5 6 7 8 8 ON DIP 1 2 3 4 5 6 7 8 9 ON DIP 1 2 3 4 5 6 7 8 10 ON DIP 1 2 3 4 5 6 7 8 2 ON DIP 1 2 3 4 5 6 7 8 1 ON DIP 1 2 3 4 5 6 7 ...

Страница 21: ...MONITORING THROUGH CONTROLLER NOTES Pressure transducer provides 0 10 VDC output signal Powered by 33 VDC supply Page 21 of 24 9 18 IOM FFDINST Nailor Industries Inc reserves the right to change any information concerning product or specification without notice or obligation ...

Страница 22: ...RING THROUGH CONTROLLER NOTES Pressure transducer provides 4 20 mA output signal Powered by 33 VDC supply Page 22 of 24 9 18 IOM FFDINST Nailor Industries Inc reserves the right to change any information concerning product or specification without notice or obligation ...

Страница 23: ...ntrol for higher blower output Check the power supply for proper voltage amperage and distribution frequency Replace the HEPA filter if airflow remains low High Airflow Adjust the digital speed control for lower blower output Non Laminar Airflow and or Excessive Contamination Insure that upstream is clear of large obstructions Ensure that no other air moving devices are operating in such a way to ...

Страница 24: ... or reperformance by Nailor hereunder shall not extend the applicable Warranty Period The parties shall mutually agree on the specifications of any test to determine the presence of a defect Unless otherwise agreed upon by Nailor in writing the Buyer shall bear the costs of access de installation re installation and transportation of the unit to the Nailor facility and back to the Buyer s designat...

Отзывы: