NETWORKING
When networking the fan filter units whether in a local area network (LAN) or connecting to a BAS / BMS system, each unit is
connected in a straight-through daisy-chain using Cat5e or Cat6 network cables and the on-board RJ45 connectors.
If field cutting network cables, it is important for each end of the cable to be wired identically. However, assembled network
cable are available; field assembled cables are the leading cause of problems in new systems.
WHAT TO EXPECT:
One unit will be clearly labelled MASTER UNIT. This unit will contain the ACC1001-25 and power supply. The power supply
can be left in the master unit control box and control board can be mounted anywhere in the space, including at the master
unit.
Page 16 of 24
9/18 IOM-FFDINST
Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.
UNIT CONTROL BOARD WITH MODBUS CAPABILITY
POWER SUPPLY BOARD
CAN BE LOCATED IN THE
FAN FILTER UNIT OR IN
THE CONTROLS ENCLOSURE.
ACC1001 CONTROL USED AS AN EXAMPLE.
OTHER CONTROLLER OPTIONS ARE AVAILABLE.