FAN POWERED TERMINAL UNIT WITH
EPIC ECM MOTOR
SERIES FLOW • CONSTANT OR VARIABLE VOLUME
MODELS: 35S, 35SW AND 35SE • UNIT SIZES 1 – 6
DATE
B SERIES
SUPERSEDES DRAWING NO.
2 - 6 - 23
3500
11 - 15 - 22
35S-1
Page 1 of 2. For heat options; see page 2.
Dimensions are in inches (mm).
DESCRIPTION:
• 18 ga. (1.31) galvanized steel
channel frame with 20 ga.
(1.00) casing components.
• 16 ga. (1.61) galvanized steel
inclined opposed blade damper.
45° rotation. CW to close.
•
Ultra-high efficiency ECM
fan motor. EPIC fan volume
controller.
• Multi-point
averaging
Diamond Flow sensor. Supplied
with balancing tees.
• Full size access panels on
three sides.
•
3/4" (19) dual density
insulation, exposed edges
coated to prevent air erosion.
Meets requirements of NFPA
90A and UL 181.
• Single point electrical and /or
pneumatic main air connection.
• Discharge opening for flanged
duct connection.
• Full primary air valve low
voltage NEMA 1 type enclosure
for factory mounted DDC and
analog electronic controls.
•
Controls mounted as
standard on RH side as shown.
Terminals ordered with LH
controls (optional) are inverted
and discharge duct hanging
elevation will therefore change.
OPTIONS:
Digital Controls:
q
Factory mounted (supplied
by others)
q
Field mounted (supplied by
others)
q
Nailor EZvav. See separate
submittal.
Liner:
q
Steri-liner
q
Steri-liner + Perforated metal
q
Fiber-free
q
Perforated metal
q
Solid metal
q
1" (25) fiberglass
q
Low temperature
construction
Other:
q
Left-hand controls location
q
Toggle disconnect switch
q
Fan unit fusing
q
24/24V Isolation transformer
q
Cross Flow Sensor
q
'Q' Option – Induced Air
Inlet Attenuator
q
Top entry induced air inlet
q
1" (25) Throwaway
q
2" (51) Filter rack only
q
Hanger brackets.
q
1/4-turn fasteners (access
panel)
q
FN2 90° Line Voltage
Enclosure
L
W
OPTIONAL
TOP
INLET
FAN
5 3/4"
(146)
TL
TW
DRIVESHAFT
W
2
'Q' OPTION
INDUCED
AIR
ATTENUATOR
MULTI-POINT
FLOW SENSOR
1" (25)
DH
B
DW
H
2
PRIMARY
AIR
OPTIONAL
INDUCED AIR
INLET FILTER
IW
IH
8"
(203)
PRIMARY
AIR
PRIMARY
AIR
IW + 2" (51)
INDUCED
AIR
IH +
2" (51)
OPTIONAL
FILTER
11"
(279)
14" (356)
DIA. =
NOM. -
1/8" (3)
H -
1" (25) H
HINGED FAN
CONTROLS
ENCLOSURE
HINGED FAN
CONTROLS
ENCLOSURE
14" (356)
6 3/4"
(171)
5 3/4"
(146)
OPTIONAL
90° FN2
CONTROLS
ENCLOSURE
W
15"
(381)
W2
OPTIONAL
PRIMARY
AIR VALVE
CONTROLS
ENCLOSURE
5 1/2"
(140)
Model 35S
•
Basic Unit
Unit
Size
EPIC ECM Motor FLA
Motor HP 120V 208V 240V 277V
1
*
2.1
1.4
1.3
1.2
2
*
4.0
2.7
2.6
2.6
3
*
5.0
3.4
3.3
3.3
4
*
6.9
4.6
4.5
4.2
5
*
9.0
6.1
5.8
5.6
6
*
11.9
7.3
7.3
7.2
*
The ECM is a variable horsepower motor. Refer to
Selectworks schedule for actual power consumption.
FLA = Full load amperage. All motors are single
phase/60 Hz.
Dimensional Data
Unit
Size
Inlet
Size
W W2
H
L
B
Induced Air Inlet
Outlet
Discharge
DW x DH
Filter Size
Side (std.)
IW x IH
Top (opt.)
TL x TW
Side Inlet
(std.)
Top Inlet
(opt.)
1
5, 6, 8**
(127, 152, 203)
20
(508)
35
(889)
14
(356)
36
(914)
6
(152)
8 x 10
(203 x 254)
10 x 14
(254 x 356)
8 1/8 x 4 1/4
(206 x 108)
10 x 12
(254 x 305)
14 x 16
(356 x 406)
2
6, 8
(152, 203)
18
(457)
33
(838)
14
(356)
36
(914)
3 1/2
(89)
8 x 10
(203 x 254)
10 x 14
(254 x 356)
9 1/4 x 10 1/2
(235 x 267)
10 x 12
(254 x 305)
14 x 16
(356 x 406)
3
6, 8, 10, 12
(152, 203, 254, 305)
18
(457)
33
(838)
18
(457)
36
(914)
3 1/2
(89)
12 x 14
(305 x 356)
14 x 14
(356 x 356)
9 1/4 x 10 1/2
(235 x 267)
14 x 16
(356 x 406)
16 x 16
(406 x 406)
4
8, 10, 12, 14
(203, 254, 305, 356)
26
(660)
41
(1041)
18
(457)
41
(1041)
6
(152)
14 x 14
(356 x 356)
12 x 22
(305 x 559)
12 x 10 1/2
(305 x 267)
16 x 16
(406 x 406)
16 x 25
(406 x 635)
5
10, 12, 14
(254, 305, 356)
26
(660)
41
(1041)
18
(457)
41
(1041)
5
(127)
14 x 14
(356 x 356)
12 x 22
(305 x 559)
13 1/4 x 11 1/2
(337 x 292)
16 x 16
(406 x 406)
16 x 25
(406 x 635)
6
12, 14, 16
(305, 356, 406)
30
(762)
45
(1143)
19
(483)
44
(1118)
6
(152)
16 x 15
(406 x 381)
14 x 26
(356 x 660)
13 1/4 x 11 1/2
(337 x 292)
17 x 18
(432 x 457)
18 x 28
(457 x 711)
Electrical Data
**
ECM Only.
q
FN3 Remote Line Voltage Controls Enclosure
(See submittal FN3)
q
Du
s
t tight enclosure seal
q
Remote user disconnect
Seismic Certification:
q
Seismic Source International (Standard)
q
HCAI (formerly OSHPD, California)
q
Special Features: _________ .
Listed