IOM-EZVAVINST
Date: 10-2016
Supersedes: 7-2016
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
Page 24 of 48
Installation and Operation Manual
●
EZvav Digital Controls
Procedure to restore application (continue)
PROCEDURE
STEPS
STE DISPLAY
2
Select the restore settings display.
1. From the
CNFG
display, press the
∆
or
buttons
to show the
CNFG
display.
2. Press the button to select the
CNFG
options.
The display changes to
STPT
.
3. Press the
∆
or buttons to change the display to
RSTR
.
Caution:
Choosing
RSTR
deletes all previously
entered values and returns the controller to
the manufacturer’s settings. Only the BACnet
communications settings will remain unchanged.
4. Press the button to select
RSTR
.
3
Choose the application.
1. Press the
∆
or buttons to choose
ENGLISH
or
METRIC
.
Metric
The sensor displays temperature in Celsius and
uses metric values for units of measure.
English
The sensor displays temperature in Fahrenheit
and uses English values for units of measure.
2. Press the button to save the entry and advance to
the next function.
∆
∆
∆
Section 6: Balancing Airflow
Topics in this section are for control technicians or engineers who will be balancing the airflow in the controllers.
The airflow balancing procedure described in this section requires the following items.
•
Accurate method to measure airflow.
•
An STE-8001W36 or STE-8201W36 wall sensor. If the system does not include one of these sensors, temporarily disconnect
the installed sensor and connect an STE-8001W36 as a service tool.
•
The engineering design specifications for the minimum and maximum airflow set points.
•
Password 2 which is described in the topic Getting started with configuration on page 14.
Users may change the active heating and cooling set points without accessing the configuration functions. This procedure is
covered in the topic Changing the Room Set Point on page 13.
Note: If the VAV terminal unit is a heat only or cooling only unit, the airflow set points for the unused mode must be set within
the range of the mode in use. Failure to set the unused set points correctly will result in unpredictable or erroneous air balancing
settings. See Set the airflow set points on page 19 for the procedure to adjust the set points.
Note: Starting the balancing procedure erases all previous airflow correction factors. The airflow readings displayed by the
STE-8001W36 are the actual uncorrected airflow readings as measured by the controller.
Tip: Once the following procedure is started, all steps must be completed in order.