FAN POWERED TERMINAL UNITS
C
FAN POWERED TERMINAL UNITS •
C56
10-5-22
FAN POWERED TERMINAL UNITS • 35S SERIES
NOTES:
• The ECM is pressure independent and
constant volume in operation at factory
or field set point within the shaded area.
Airflow does not vary with changing
static pressure conditions. The motor
compensates for any changes in external
static pressure or induced air conditions
such as filter loading.
• Airflow can be set to operate on
horizontal performance line at any point
within shaded area using the solid state
volume controller provided.
• Fan curves shown are applicable to 120,
208, 240 and 277 volt, single phase
ECM's. ECM's, although DC in operation,
include a built-in AC/DC converter.
Electrical Data
*
The EPIC ECM is a variable horsepower motor.
Refer to Selectworks schedule for actual power
consumption.
FLA = Full load amperage.
All motors are single phase/60 Hz.
Performance Data
ECM Motor Fan Curves – Airflow vs. Downstream Static Pressure
35S Series • Series Flow
Unit
Size
EPIC ECM Motor FLA
Motor HP 120V 208V 240V 277V
1
*
2.1
1.4
1.30
1.2
2
*
4.0
2.7
2.6
2.6
3
*
5.0
3.4
3.3
3.3
4
*
6.9
4.6
4.5
4.2
Unit Size 2
900
800
700
600
500
400
300
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
0.75
"w.g.
0 25 50 75 100 125 149 174
187
Pa
DISCHARGE STATIC PRESSURE
MAXIMUM
MINIMUM
425
378
330
283
236
189
142
AIRFLOW
l/s CFM
MAX. COOLING
1 ROW HW COIL
2 ROW HW COIL
3 ROW HW COIL
Unit Size 4
1600
1500
1400
1300
1200
1100
1000
900
800
700
600
500
400
300
200
MAXIMUM
MINIMUM
755
708
661
613
566
519
472
425
378
330
283
236
189
142
94
AIRFLOW
l/s CFM
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
0.75
"w.g.
0 25 50 75 100 125 149 174
187
Pa
DISCHARGE STATIC PRESSURE
MAX. COOLING
HW COIL:
1 ROW
2 ROW
3 ROW
Unit Size 3
1400
1300
1200
1100
1000
900
800
700
600
500
400
300
200
100
AIRFLOW
MAXIMUM
MINIMUM
l/s CFM
661
613
566
519
472
425
378
330
283
236
189
142
94
47
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
0.75
"w.g.
0 25 50 75 100 125 149 174
187
Pa
DISCHARGE STATIC PRESSURE
MAX. COOLING
1 ROW HW COIL
2 ROW HW COIL
3 ROW HW COIL
Unit Size 1
550
500
450
400
350
300
250
200
150
100
50
AIRFLOW
MAXIMUM
MINIMUM
l/s CFM
260
236
212
189
165
142
118
94
71
47
24
0.0 0.1 0.2 0.3 0.4 0.5
"w.g.
0 25 50 75 100 125
Pa
DISCHARGE STATIC PRESSURE
MAX. COOLING
1 ROW HW COIL
2 ROW HW COIL
3 ROW HW COIL