3/11
IOM-AECVAV
INSTALLATION AND OPERATION MANUAL
ANALOG ELECTRONIC CONTROLS
VAV TERMINAL UNITS
Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.
Page 1 of 10
CTE-5100 Series Thermostats:
The CTE-5100 series thermostats are designed to be used with the CSP-5002 controller actuator. CTE-5100’s are provided with limited and
unlimited outputs. The limited output(s) is (are) used to provided minimum and maximum limits to a CSP-5002. The unlimited output(s) is
(are) used to operate fan and heat sequences.
Models are available for cooling, cooling with reheat, cooling / heating changeover and day/night or set-back applications. Temperature
averaging and/or overrides may be accomplished. Consult Nailor control submittal for applicable thermostat model.
Models:
CTE-5101
Single setpoint; Direct Acting
Supply Voltage:
16 Vdc (14 - 20 Vdc)
CTE-5103
Dual setpoint; Direct & Reverse Acting
Output Range:
0 to 10Vdc
CTE-5104
Dual setpoint; Direct & Reverse Acting
Connections:
Wire clamp type: 14-22 AWG
CTE-5105
Dual setpoint; both Direct Acting
Temperature Range:
55
O
F - 85
O
F (13
O
C - 29
O
C)
Thermostat Action:
Proportional Band:
CTE-5101
Direct Acting (DA) T1/T3
CTE-5101/3/5
2
O
F, (1.1
O
C) w/limits output (T1/T2)
CTE-5103
Direct Acting (DA) T1/T3, Reverse Acting (RA) T2/T4
4
O
F, (2.2
O
C) w/o limits output (T3/T4)
CTE-5104
Direct Acting (DA) T1/T3, Reverse Acting (RA) T2
CTE-5104
2
O
F, (1.1
O
C) w/limits output (T1)
CTE-5105
Direct Acting (DA) T1/T2/T3/T4
2
O
F, (1.1
O
C) w/limits output (T2/T3)
Base Material:
Black ABS, UL Flame Class 94HB
Size
2 9/16" (65 mm) x 3 7/16" (87 mm)
Table 1.
Thermostat Specifications.
Installation:
Thermostats must be mounted horizontally,(or vertically by using an optional vertical scale plate), utilizing the HMO-5030/5031 backplates
for mounting to a standard 2" x 4" electrical box, or the optional HMO-5023 drywall bracket for mounting to hollow walls. Thermostats should
be mounted on a wall in an area not affected by sunlight or drafts, to sense the average room temperature.
Electrical box mounting:
Install the HMO-5030/5031 backplate to the electrical box using the two 6-32 screws, supplied with backplate – do not tighten. The backplate
is provided with one slotted mounting hole for leveling. Level the backplate and tighten the two mounting screws. Pull thermostat wires
through backplate and decorative trim plate. Connect thermostat wires to the thermostat according to the wiring diagram supplied with the
unit. Position the trim between the back plate and the thermostat, secure the assembly with the two 6-32 x 2" self tapping screws supplied.
Hollow wall mounting:
Loosely mount the HMO-5023 bracket to the thermostat using the two 6-32 x 2" screws. Pull all thermostat wiring through the opening on
the bracket. Connect thermostat wires to the thermostat according to the wiring diagram supplied with the unit. Center and align the
thermostat while tightening the mounting screws.
Thermostat
5101
5103
5104
Terminals Description
Terminals
5105
V1
X
X
X
Velocity input for readout, connect to “out” on CSP-5002
T3
X
X
X
Upper setpoint output w/o limits (0 -10 Vdc)
R1
X
X
X
T1 override, connect to "-" if unused. Voltage applied subtracts from T1
T1
X
X
X
Upper setpoint output w/limits. Adjustable at pot.on front of thermostat
+
X
X
X
16 Vdc power supply input
12V
X
X
X
12 Vdc power output
A
X
X
X
Temperature averaging input
-
X
X
X
Ground reference
T2
X
X
Lower setpoint, output w/limits. * Adjustable at pot. on front of thermostat
R2
X
X
T2 override connect to "-" if unused **
T4
X
Lower setpoint output w/o limits (0 -10 Vdc)
V2
X
Velocity input for readout
* Except 5104; T2 lower setpoint output is w/o limits.
** R2 is auxiliary limit trigger on model 5104. Voltage above 1 Vdc @ R2 indexes T1 to the auxiliary flow limit. Install jumper R2-T2 for
automatic indexing of aux. flow setting.
Table 2.
Thermostat Wiring Terminals and Description.