NAUTILUS 10●520
Three phase in/out
Rev.00
– 09 Luglio 2015
51
Noise suppression
Compliant with EN62040-2
Communication Interface
RS232, RS485, Dry contacts, Intelligent slot, SNMP card (optional),
Relay card (optional)
Environment
Operating temperature
0°C~40°C
Storage temperature
-25°C~55°C
Humidity
0%~95% non condensing
Altitude
< 1500m
Others
Dimensions FRAME
(DxWxH) mm
840x600
x1400
1100x600x2000
860x600
x1600
860x600
x2000
860x1200
x2000
Dimensions MODULE
(DxWxH) mm
580x443x131
Weight
(Kg)
Frame
UPS
150
312
205
310
450
Modulo
UPS
30KVA=33Kg
Compliance to safety std.
CE,EN/IEC 62040-2,EN/IEC 62040-1-1
APPENDIX 2
– Troubleshooting
In case the UPS does not work properly, it may be a problem of incorrect installation, incorrect connections or
incorrect settings. Please check these aspects before contacting the service department. If the problem
remains, contact the after-sales service and provide the following information:
1)
UPS model, power capability, serial number.
2)
Try to describe the problem in details, such as messages on the LCD display, LED status, type
and percentage of load and all that is considered important.
Reading the operation manual carefully can help you to use this UPS correctly. Here is some information for
troubleshooting.
NO.
PROBLEM
POSSIBLE REASON
SOLUTION
1
The LCD display
shows nothing
The power cable or cable
(telephone type) of the front
door is not well connected.
Check the connections
2
Mains is available but
UPS doesn
’t start-up.
Power cable not connected.
Input voltage low;
input switch of the module is
OFF.
Verify that the input voltage and
frequency are within tolerances.
Verify that the module input switch is in
the ON position.
3
The mains is present
and in its tolerances
but the LED of the
mains is off and the
UPS works in battery
mode.
Input switches on the modules
are OFF;
Power cables at the input are
not well connected..
Close the input disconnector;
Make sure the cables are well
connected.
4
The UPS does not
report any failure, but
the load is not
powered
Output cables are not
connected
Make sure that output cables are well
connected.
5
"24 CAN" alarm on
UPS module
communication error
When the number of modules is
set at 2 or more but only one
works properly.
If only one module works, reset the qty
of the modules to one.
6
“45 Inverter off” alarm
on UPS mode
Inverter disconnection within 2
min in normal mode, UPS in
Bypass mode more than 2 min.
Switch from Bypass mode to normal
mode.