3) Open the terminal box lid and insert the cable from the terminal opening deep into the gasket (See
Figure 8-3 below).
4) Tighten the gland and seal the terminal opening. (See Figure 8-3 below).
Pass the cable through the gasket and tighten it with the gland
to prevent the intrusion of water.
Use a dedicated tool to peel the coating to avoid damage to the
cable core.
Be careful if the shielded wires do not extend the sheath end
face.
Atmospheric pressure is introduced into an instrument via the
cable. If the cable is pressed due to a clamp, bush, or extreme
bend in the middle of the cable, or if the cable is long, the
exhaustion of pressure takes time. In this case, an output error
may be caused because of pressure within the case or a change
in temperature. Conduct wiring not to seal the cable end with
tape or adhesive. Avoid using the cable with poor ventilation
performance (no clearance within the cable).
Always attach a crimp terminal that fits with the core wire.
CAUTION
CAUTION
< Figure 8-3 >
Cable
Gland
Washer
Terminal box lid
Terminal block
Terminal opening
Gasket
Terminal box