INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS
VERTICAL TURBINE PUMP - NVT SERIES
Ref. No. NVT-IOM/2020/V.01
6.2. Start up
Start the pump against a closed discharge valve only. Once the pump has reached full speed slowly open the valve
and set to the duty point. Start up of the engine and controllers shall be as given in their respective IOM manuals.
Automatic starting of the pumps shall be based on pressure setting.
6.3. Methods of Stopping
Manual:
Manual shut down shall be accomplished by operation of push-button on the outside of the controller enclosure.
Automatic shutdown after automatic start:
Automatic shutdown shall not be permitted where the pump constitutes the sole supply of fire sprinkler or standpipe
system or where authority having jurisdiction has required normal shutdown.
Automatic shutdown shall be permitted only where the controller is arranged for automatic shutdown after all starting
and returning causes have returned to normal.
7. MAINTENANCE
7.1. Weekly Inspection And Testing
The purpose of the weekly fire pump inspection and test is to ensure the fire pump is in an operation condition free of
physical damage and is capable of providing continuous delivery for required fire protection demands. An additional
purpose of the weekly test is to detect deficiencies that may not be obvious by visual inspection.
7.2. Visual Inspection
»
Check the power indicating light on the controller to verify that there is power to the pump
»
Make sure that the temperature in the pump room is not less than
40
°F (
70
°F for diesel engines without
heaters) during colder months.
»
Check ventilating louvers to make sure that they are free to operate.
»
Check pump discharge valves to make ensure that they are open.
»
Examine piping, fitting, and connections for any physical damage or leakage.
»
Check discharge gauge to make sure that the pressure reading is normal.
»
Check the system pressure gauge to ensure that the system pressure reading is normal.
»
Make sure that the test header valves are closed in properly.
»
Check pressure sensing line leakage and block (open drain valve and check block).
»
Check free rotation of the pumps.
»
Check to make sure the phase reversal alarm pilot light is off.