INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS
VERTICAL TURBINE PUMP - NVT SERIES
Ref. No. NVT-IOM/2020/V.01
Water tank should provide sufficient and reliable water supply for the fire protection system. The depth of the tank should
match with the pump length and it should be confirmed by cross-checking with the pump dimensional drawing.
Ensure the proper submergence of the pump for reliable operation of the pump. The minimum submergence level is given
in the Fig. No.
18
. The maximum quantity of water required for the fire fighting system at any condition, for the amount of
time for which the fire pump is designed to operate, should be above this level (i.e. this is the lowest pumping water level).