Interface description
NDRA91-92
Manual
Page 42
NADO
5.4
QA – Analog output
The analog output enables the normed, analog transmission of distance data
across large distances using a two-wire line. The current of 4 mA to 20 mA
impressed in the line is proportional to the measured distance within an
adjustable distance interval. Parameterization is done via the serial interface.
Properties of the analog output:
Measuring value output range 4 mA ... 20 mA
Indication in case of an error: 3 mA or 21 mA (selectable via the
parameter SE)
Resolution: 16 bit DA-converter
Load ≤ 500 Ohm/0,5W
The command to achieve this is QAx_y (where “_” is equivalent to space
(0x20)). Parameter settings for current output in the event of measurement
failure can be made using the command SEx.
Figure 18 : Signal diagram of
NDRA91
analog output
The value of output current (mA) is calculated as follows:
x < y
𝑄𝐴[𝑚𝐴] = 4 𝑚𝐴 + 16 ∗
𝐷𝑖𝑠𝑡.−𝑥
𝑦−𝑥
∗ 𝑚𝐴
x > y
𝑄𝐴[𝑚𝐴] = 20 𝑚𝐴 + 16 ∗
𝐷𝑖𝑠𝑡.−𝑥
𝑥−𝑦
∗ 𝑚𝐴
Figure 19 : Behavior of analog current output
Value
Description
Specification
x
Lower Limit
x ≠ y
y
UpperLimit
y ≠ x