7506GX2 

Managed Industrial  

Gigabit Ethernet Switch 

 

 

 

       

User Manual & 

Installation 

Guide 

 

 
 
 
 
 
 
 

 
 

Содержание 7506GX2 Series

Страница 1: ...Revised 2011 07 21 Page 1 of 158 7506GX2 Managed Industrial Gigabit Ethernet Switch User Manual Installation Guide...

Страница 2: ...on System 27 Administration SNMP 32 Administration Fault 34 DHCP Server Setup Profiles 35 DHCP Server Setup IP Maps 37 DHCP Server View Bindings 42 DHCP Relay Local IP Setup 43 LLDP Configuration 46 L...

Страница 3: ...s 134 Show or Set CIP Configuration 135 Save or Reset the Configuration Settings 136 Show or Set IGMP Configuration 136 Show or Set Mirror Configuration 137 Show or Set N Ring Configuration 138 Show o...

Страница 4: ...it Ethernet Switch Installation Guide The N TRON 7506GX2 Series Industrial Gigabit Ethernet Switch offers outstanding performance and ease of use It is ideally suited for connecting Ethernet enabled i...

Страница 5: ...NTSFP SX LC Style Connector up to 550m NTSFP LX 10 LC Style Connector up to 10km NTSFP LX 40 LC Style Connector up to 40km NTSFP LX 80 LC Style Connector up to 80km MANAGEMENT FEATURES SNMP v1 v2 v3...

Страница 6: ...6GX2 Industrial Ethernet Switch Accessories NTCD SD Configuration Device Ideal for saving or restoring switch configuration parameters quickly without the need for a computer or software One configura...

Страница 7: ...rranties of merchantability or fitness for a particular purpose In no event shall N Tron Corp be liable for any incidental special indirect or consequential damages whatsoever included but not limited...

Страница 8: ...BSITE www n tron com E MAIL N TRON_Support n tron com ENVIRONMENTAL SAFETY WARNING Disconnect the power and allow to cool 5 minutes before touching ELECTRICAL SAFETY Must be used with Listed UL Indust...

Страница 9: ...htening torque for field installed conductors 5 The USB Port is for temporary connection only Do not use connect or disconnect unless area is known to be non hazardous Connection or disconnection in a...

Страница 10: ...Revised 2011 07 21 Page 10 of 158 Remove all the equipment from the packaging and store the packaging in a safe place File any damage claims with the carrier CLEANING Clean only with a damp cloth...

Страница 11: ...rail at a 15 angle as shown Rotate the bottom of the unit to the back away from you until it snaps into place To remove the unit from the 35mm industrial DIN rail pull forward on the unit until it dis...

Страница 12: ...al NOTE The RJ45 data ports have two LEDs located on each connector The bottom LED indicates the SPEED and the top LED indicates LINK ACTIVITY LEDs The table below describes the operating modes LED Co...

Страница 13: ...h ON Momentarily Verify the Power LED stays ON GREEN Notes Only 1 power supply must be connected to power for minimal operation For redundant power operation V1 and V2 inputs must be connected to sepa...

Страница 14: ...is is not an option and users must terminate their own ends on the Cat5E cables one of the two color coded standards shown to the right should be utilized If a user does not follow one of these two co...

Страница 15: ...output terminal and the chassis grounding point of the switch As an alternative grounding method both V legs of the power input connector are connected to chassis internally on the PCB Connecting a dr...

Страница 16: ...Revised 2011 07 21 Page 16 of 158 RJ45 CONNECTOR CRIMP SPECIFICATIONS Please reference the illustration below for your Cat5 cable specifications...

Страница 17: ...onnect the USB port of your PC and the 7506GX2 Series Switch using a standard USB cable You will require a cable with a Type A connector for the PC end and a Type B connector for the 7506GX2 Series en...

Страница 18: ...ion for a shared medium in this mode Auto Negotiation In Auto Negotiation mode the port hardware detects the mode of operation of the station that is connected to this port and sets its mode to match...

Страница 19: ...because that is the most common operation But if desired the port can be included in VLAN 1 by configuring VLAN 1 last If switch ports are configured to transmit and receive untagged frames end devic...

Страница 20: ...P when desired SNMP Traps The 7506GX2 switch supports up to 5 SNMP Trap Stations to which SNMP Traps will be sent The switch supports five standard traps Link Up Link Down Cold Start Warm Start and Au...

Страница 21: ...en a problem is detected on the Primary Coupler link the Primary Coupler link will block network traffic and the Standby Coupler link will forward network traffic While the N Link Master and Slave are...

Страница 22: ...mic range of IP addresses available to any client device or specific IP addresses based on the clients MAC address Client ID Option 61 or Relay Agent connection Option 82 LLDP Link Layer Discovery Pro...

Страница 23: ...ent generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications Operation of this dev...

Страница 24: ...07 21 Page 24 of 158 Web Software Configuration Web Management Enter the switch s IP address in any web browser and login to the web management feature of the N Tron switch Default User Name admin Pa...

Страница 25: ...ist of configurable settings that the switch will support This section of the manual will go through each and every choice listed on the left hand side of the screen and explain how to configure those...

Страница 26: ...here is a menu which is shown fully opened below The pages opened by each of the individual selections are described in the rest of this section The use of each of these pages is also described in thi...

Страница 27: ...itch was turned ON or RESET Name It shows the name of the product which allows alphanumeric and special characters _ only Contact The person to contact for system issues which should be someone within...

Страница 28: ...Revised 2011 07 21 Page 28 of 158...

Страница 29: ...CP clients to specify their unique identifier The identifier may be the MAC address switch name or entered as a text string or hex characters Fallback IP Address Contains the configured Fallback IP Ad...

Страница 30: ...Subnet Mask Gateway Name Contact information and the Location of the switch through the web management features depending on the IP Configuration It is recommended to change the TCP IP information th...

Страница 31: ...hanged from the default IP address then the switch will use the Fallback addresses if the IP configuration isn t received from a DHCP server in 2 minutes after initial boot If Fallback address is used...

Страница 32: ...nity Names are also shown here By selecting the Modify button you will be able to change any of the fields listed This allows the user to set an IP address for a Trap station or change the Community N...

Страница 33: ...Revised 2011 07 21 Page 33 of 158 Administration SNMP Continued...

Страница 34: ...nk or N Ring Signal fault occurs Power signal faults consist of V1 and V2 N Link Faults can also be set for notification The Power and N Link notifications may consist of any combination of the option...

Страница 35: ...processing a broadcast message Server ID Descriptive name of the DHCP server Profile Name Descriptive name of the network profile Address Pool Range of IP addresses which the profile can use Subnet A...

Страница 36: ...Revised 2011 07 21 Page 36 of 158 DHCP Server Setup Profiles Continued...

Страница 37: ...is required Network Profile An existing network profile to which the IP map applies Low IP The starting IP address of a range High IP The ending IP address of a range The Static Range type of mapping...

Страница 38: ...ture Remote ID A unique identifier that designates the N TRON relay agent switch Add Checkbox used to add an IP map for the corresponding port Port No The actual port number Port Name Descriptive name...

Страница 39: ...Revised 2011 07 21 Page 39 of 158 DHCP Server Setup IP Maps Continued...

Страница 40: ...ric Port Count The number of ports on the particular relay agent switch Add Checkbox used to add an IP map for the corresponding port Port No The actual port number Remote ID The identifier that corre...

Страница 41: ...ndividual client The following information is required Network Profile An existing network profile to which the IP map applies IP The static IP address to offer to a client Unique ID The unique identi...

Страница 42: ...fier The client associated with the binding entry Client Hardware Address MAC The client s MAC address Client IP Address The actual IP address assigned to the binding entry Status Indicates the curren...

Страница 43: ...Setup tab under the DHCP Relay Local IP category shows the current state of the relay agent By selecting the Modify button you can configure general settings of the relay agent as well as configure se...

Страница 44: ...her the port will perform relay agent functionality The choices are Disabled The port will function without relay agent processing Enabled The port will relay DHCP client originated broadcast packets...

Страница 45: ...Revised 2011 07 21 Page 45 of 158 DHCP Relay Local IP Setup Continued...

Страница 46: ...t settings are toggled The default is 2 seconds Notification Interval Specifies the interval between successive Notifications generated by the switch If a port sends out a notification and another por...

Страница 47: ...LLDP Transmission on the switch Receive Enables or Disables Receiving of LLDP Frames from neighbor switches Allow Management Data Allow the Transmission of Management type information For example IP A...

Страница 48: ...ch the neighbor information was received Neighbor MAC MAC address of neighbor switch Corresponds to the LLDP Chassis ID TLV Neighbor IP IP address of neighbor switch Corresponds to the LLDP Management...

Страница 49: ...tal number of LLDP frames received by the local switch Discarded Frames The total number of frames discarded due to incorrect TLV s in frame Error Frames Total count of all LLDP frames received with o...

Страница 50: ...e High Priority State This configurable field displays the port priority status of each port When enabled for a port all frames received on that port will be forced to the highest priority queue regar...

Страница 51: ...ck on the Port Number to configure each port individually This will allow the user to change the port s settings for the following fields which are explained above Admin Status Speed and Duplex Flow C...

Страница 52: ...d In Locked mode Secured Ports shows the ports that are presently secured Note when N Ring and or N Link are used the N Ring N Link ports will not have MAC Security enabled The Modify button allows th...

Страница 53: ...ation Configuration page which allows the administrator to add new entries delete existing entries or edit authorized ports of existing entries Selecting Delete removes the associated entry Selecting...

Страница 54: ...currence of the intruder is listed The log is ordered by most recent first based on the system time The maximum number of entries is 100 If more than 100 intruders are detected the oldest entries are...

Страница 55: ...to receive the copies of Ethernet frames that are being transmitted out and also being received in from any other port that is being monitored The Mirroring tab under the Ports category displays the...

Страница 56: ...1 07 21 Page 56 of 158 Ports Mirroring Continued Following the Modify button you can enable the status of port mirroring and select source ports and the destination port that the source ports will be...

Страница 57: ...ton you can select a trunk group Note RSTP must be disabled in order to use the Trunking feature Two ports of the same speed can constitute a valid trunk Only 1 Trunk per switch can be created All tru...

Страница 58: ...on the settings on this browser page When Force High Priority is enabled the port based priority is included in the TQ decision for all ports and all frames received on a port will use the default QOS...

Страница 59: ...Revised 2011 07 21 Page 59 of 158...

Страница 60: ...of MIB parameters Each port has a separate counter for each parameter This gives users the ability to see what kind of packets are going over which ports At the bottom of the page for each port there...

Страница 61: ...e Statistics category shows all the ports on the switch and will display a bar graph showing the percentage of bandwidth being used These figures and bars are for a general feeling of what the bandwid...

Страница 62: ...ress frames when a VID violation is detected Discard Non Tagged for Ports Specifies whether or not non tagged ingress frames are dropped by the selected ports Note that for convenience in most frequen...

Страница 63: ...cters _ only Allow Management Specifies whether or not all ports in this VLAN are management ports Change PVID of Member Ports Specifies whether or not the PVID of the member ports is set to this VLAN...

Страница 64: ...s page allows users to modify this variable to meet their needs After selecting the Modify button the user will be presented with a page that allows the number to be entered and updated The default ag...

Страница 65: ...e associated with each respective port number This can be used to statically assign a MAC address access to a single port on the switch Following the Add button on the page above the administrator mus...

Страница 66: ...ill be displayed in a list on the main page under Unicast MACs tab Following the Remove button on the example above an administrator can select a static MAC address from the list using a pull down men...

Страница 67: ...a valid Multicast Group Address and associate it with a port number or list on the switch Once the administrator clicks on the Add button the changes will take effect instantly Note If there are multi...

Страница 68: ...ch Using the pull down menu the administrator should select the desired address to be removed Then click on the Remove button at the bottom of the page Note If there are multiple ports on different VL...

Страница 69: ...nerates no Ethernet traffic for this purpose but can still present some information gathered passively The IP field shows an Auto detected or manually entered IP address If there is a MAC address for...

Страница 70: ...evised 2011 07 21 Page 70 of 158 When an IP has been manually entered a button is provided to Delete IP and invoking it will allow the administrator to delete the manual association of an IP to that M...

Страница 71: ...ry will display the RSTP information for the first VLAN Using the pull down menu at the top of the page an administrator can choose which VLAN to configure RSTP on Once the VLAN is selected the admini...

Страница 72: ...n that VLAN The administrator or user can see the current RSTP status of the ports on that VLAN by clicking on the here link to view RSTP Port Configuration at VLAN Note It is recommended that RSTP ri...

Страница 73: ...t RSTP status of the ports on that VLAN This will show information such as the Path Cost and the Port State If the switch sees a redundant path it will put the port with the highest Path Cost into Blo...

Страница 74: ...07 21 Page 74 of 158 RSTP Configuration Continued If the administrator selects one of the ports on the previous screen he or she can change the Port s Path Cost Priority and the status of Admin Edge...

Страница 75: ...configuration settings By default IGMP is enabled Following the Modify button the administrator will see a list of configurable fields for the IGMP configuration Once these fields are filled in to me...

Страница 76: ...76 of 158 IGMP Configuration Continued The IGMP Status pull down allows the user to enable or disable IGMP completely The Query Mode pull down allows the user to set query mode for Automatic the defau...

Страница 77: ...inued The Router Mode pull down allows the user to choose router mode Auto allows for dynamically detected and manually set router ports Manual allows only for manually set router ports None allows no...

Страница 78: ...ups tab under the IGMP category will display a list of IGMP groups based on the Group IP and the port number that it is associated with The Show Routers tab under the IGMP category will display a list...

Страница 79: ...ions The factory default is that the Router Multicast Data Filter is enabled for all ports so any router ports do NOT get DATA frames with KNOWN multicast destination addresses unless a join to a spec...

Страница 80: ...Revised 2011 07 21 Page 80 of 158 IGMP RFilter Continued Modifying rfilter port settings...

Страница 81: ...nd the interval between packets Following the Modify button on the above example the administrator can modify the variable to change the frequency with which N View reports information Increasing the...

Страница 82: ...Page 82 of 158 N View Ports The Ports tab under the N View category will display a list of all the configured ports on the N Tron switch unit along with the ports transmitting multicast packets and MI...

Страница 83: ...83 of 158 N View Ports Continued Following the Modify button on the above example the administrator can modify these two variables to enable or disable multicast out of the port and if MIB stats are...

Страница 84: ...or example Switch is currently using N Ring Aging Time 20 Seconds Once these fields are filled in to meet the needs of the administrator s network the changes may be saved by clicking the Update butto...

Страница 85: ...Revised 2011 07 21 Page 85 of 158 N Ring Configuration Continued The N Ring Mode is one of three as below If N Ring Mode is Manager then a pull down allows selection of available ports as N Ring ports...

Страница 86: ...ges It is up to the administrator to ensure that VLANs are configured correctly on the N Ring manager and all N Ring members 2 When the N Ring manager and all N Ring Members are in defaults changing t...

Страница 87: ...al sign on information from ring members The default is 1000 Sign On Match Packets The number of times the switch count must match before starting the sign on process The default is 3 Sign On Interval...

Страница 88: ...Revised 2011 07 21 Page 88 of 158 N Ring Advanced Configuration Continued...

Страница 89: ...he N Ring category will display the N Ring status Below is an example of N Ring Status from a switch in defaults N Ring Auto Member that is not an N Ring Manager and has not become an Active N Ring Me...

Страница 90: ...Revised 2011 07 21 Page 90 of 158 N Ring Status Continued Below is an example of N Ring Status from an N Ring Manager with a healthy N Ring...

Страница 91: ...tus from an N Ring Manager with a faulted N Ring The red fields on the N Ring Map show problems Ports that are red indicate that the port is not linked MAC addresses that are red indicate that there i...

Страница 92: ...low shows N Ring Manager Status when a Higher N Ring Port TX2 TX8 FX2 or GB2 is not receiving self health frames all the way around the N Ring though the other low TX1 TX7 FX1 or GB1 N Ring port is Th...

Страница 93: ...er N Link Slave N Ring Member N Link Master N Ring Member Partner Link N Ring Segment Control Link N Ring Auto Member N Rng Manager N Link Coupler N Ring Member N Link Couper N Ring Member N Ring Auto...

Страница 94: ...ator may also need to configure the Default Coupler port on the N Link Slave There must be a direct link between the Master and Slave Control ports Use of media converters or other switches is not sup...

Страница 95: ...the Modify button on the above example the administrator will see a list of configurable fields for the N Link configuration as below The port configured as the Default Coupler Port will be used as th...

Страница 96: ...as below If N Link mode is Master then the administrator must configure the Control Port default T3 and the Primary Coupler Port default T4 Once these fields are filled in to meet the needs of the ad...

Страница 97: ...tches is not supported This port will be detected automatically Coupler Port The port being used to establish a redundant path for ethernet data transmission Coupler Port State Blocking Forwarding Sta...

Страница 98: ...Revised 2011 07 21 Page 98 of 158 N Link Status Continued Below is an example of N Link Status from an N Link Coupler switch Below is an example of N Link Status from an N Link Master switch...

Страница 99: ...21 Page 99 of 158 N Link Status Continued Below is an example of N Link Status from an N Link Slave switch Below is an example of N Link Status from an N Link Master and Slave where the Primary Couple...

Страница 100: ...N Link Status Continued Below is an example of N Link Status from an N Link Master and Slave where the Standby Coupler link is broken Below is an example of N Link Status from an N Link Master and Sla...

Страница 101: ...Revised 2011 07 21 Page 101 of 158 N Link Status Continued Below is an example of N Link Status from an N Link Master and Slave where the Partner link is broken...

Страница 102: ...ed Packet Interval for Class 1 multicast connections in milliseconds Requests for less than this value will be rejected Default 1 second Unicast RPI The minimum Requested Packet Interval for Class 3 u...

Страница 103: ...The ODVA Device Type is Communications Adapter 0x0C hex Major Revision The Major Revision of the CIP implementation Minor Revision The Minor Revision of the CIP implementation Serial Number hex CIP Se...

Страница 104: ...case they need to reload their custom configurations at a later time It is important not to cycle power on the switch or interrupt the data connection between the TFTP server and the switch while you...

Страница 105: ...file to the switch via TFTP This allows for upgrades of Firmware on the switch in the field and without having to send the switch back to N Tron for future updates It is important not to cycle power o...

Страница 106: ...158 Support Web Site and E mail If at any point in time you get confused or would like additional support directly from N Tron you may visit N Tron s web site or e mail N Tron directly with the links...

Страница 107: ...splay all the ports that are installed in the N Tron switch unit and will list the BPCL Percentage for each port BPCL defaults to 1 A Modify button is provided to change these fields Following the Mod...

Страница 108: ...anagement features of the switch and their access permissions Following the Add button on the above example the administrator can add another user and assign the user a username a password and the use...

Страница 109: ...the user s name and clicking the Remove button A page should follow indicating that the user was successfully removed from the list Note There are a maximum number of 5 users per switch User permissio...

Страница 110: ...administrator can see a graphical depiction of the N Tron switch Ports that are linked will appear in green while ports that are not linked will appear in black The example below shows an N Tron switc...

Страница 111: ...Revised 2011 07 21 Page 111 of 158 In the logical view below the Configuration Device is installed as indicated by the green color...

Страница 112: ...alled The Reset button will discard all unsaved changes reset the switch and load the most recently saved configuration settings Note Upon restart if a configuration device NTCD is installed the switc...

Страница 113: ...Revised 2011 07 21 Page 113 of 158 If the configuration device NTCD is not installed this browser page will indicate that as below...

Страница 114: ...link is clicked on you will see the Overview page that will have some basic definitions and more specific choices at the top of the screen Although this page is not as detailed as the manual it gives...

Страница 115: ...158 Help Administration Following the Administration link on the help page the administrator or user can see some information regarding the configuration options in the Administration category on the...

Страница 116: ...Page 116 of 158 Help DHCP Following the DHCP link on the help page the administrator or user can see some information regarding the configuration options under the DHCP categories on the left side of...

Страница 117: ...21 Page 117 of 158 Help LLDP Following the LLDP link on the help page the administrator or user can see some information regarding the configuration options in the LLDP category on the left side of th...

Страница 118: ...1 Page 118 of 158 Help Ports Following the Ports link on the help page the administrator or user can see some information regarding the configuration options in the Ports category on the left side of...

Страница 119: ...19 of 158 Help Statistics Following the Statistics link on the help page the administrator or user can see some information regarding the configuration options in the Statistics category on the left s...

Страница 120: ...21 Page 120 of 158 Help VLAN Following the VLAN link on the help page the administrator or user can see some information regarding the configuration options in the VLAN category on the left side of th...

Страница 121: ...e 121 of 158 Help Bridging Following the Bridging link on the help page the administrator or user can see some information regarding the configuration options in the Bridging category on the left side...

Страница 122: ...21 Page 122 of 158 Help RSTP Following the RSTP link on the help page the administrator or user can see some information regarding the configuration options in the RSTP category on the left side of th...

Страница 123: ...21 Page 123 of 158 Help IGMP Following the IGMP link on the help page the administrator or user can see some information regarding the configuration options in the IGMP category on the left side of th...

Страница 124: ...Page 124 of 158 Help N View Following the N View link on the help page the administrator or user can see some information regarding the configuration options in the N View category on the left side of...

Страница 125: ...Page 125 of 158 Help N Ring Following the N Ring link on the help page the administrator or user can see some information regarding the configuration options in the N Ring category on the left side of...

Страница 126: ...Page 126 of 158 Help N Link Following the N Link link on the help page the administrator or user can see some information regarding the configuration options in the N Link category on the left side of...

Страница 127: ...7 21 Page 127 of 158 Help CIP Following the CIP link on the help page the administrator or user can see some information regarding the configuration options in the CIP category on the left side of the...

Страница 128: ...58 Help Firmware Config Following the Firmware Config link on the help page the administrator or user can see some information regarding the configuration options in the Firmware Config category on th...

Страница 129: ...21 Page 129 of 158 Help BPCL Following the BPCL link on the help page the administrator or user can see some information regarding the configuration options in the BPCL category on the left side of th...

Страница 130: ...58 Help User Management Following the User Management link on the help page the administrator or user can see some information regarding the configuration options in the User Management category on th...

Страница 131: ...07 21 Page 131 of 158 Help Other Following the Other link on the help page the administrator or user can see some information regarding other links or categories on the left hand side of the web mana...

Страница 132: ...escription of this command will be displayed Syntax cmd Parameters cmd The command for which to get help Examples N TRON Admin The above command displays all the available commands N TRON Admin abcd U...

Страница 133: ...delete Delete MAC address add Add MAC address mac MAC Address port Port Number cpu 1 Send to CPU also static 1 This is a static address 0 Non Static vid VLAN ID 0 4095 Example N TRON Admin arl show No...

Страница 134: ...e switch configuration on the configuration device Example N TRON Factory cfgdev info Port A 0xd080 Board ID 0x0005 5 Configuration device information Name SDS128M Model 3 Version 1 Page Size 200 Tota...

Страница 135: ...Interval 10 ms Cache Interval 2000 ms Identity Information Product Name N TRON 7506GX2 Vendor 1006 N TRON Device Type 0x0C Communications Adapter Major Revision 1 Minor Revision 1 Serial Number 0xAFFB...

Страница 136: ...Configuration Command Name igmp Description Show or set IGMP configuration If no parameters are specified this command will show the IGMP configuration same as show parameter Syntax igmp show status s...

Страница 137: ...red frames tx portlist Set the source ports to mirror frames that are transmitted rx portlist Set the source ports to mirror frames that are received Examples N TRON Admin mirror show Mirror Status Di...

Страница 138: ...ring show N Ring Mode Auto Member Aging Time 20 N TRON Admin nring ports ID Port Set 1 T1 T2 2 T3 T4 3 GB1 GB2 N TRON Admin nring mode m ports 2 Do you Want to Save Changes and Restart the System Now...

Страница 139: ...unt Number of echo requests to send w timeout Timeout in milliseconds to wait for each reply Example N TRON Admin ping 192 168 1 119 N TRON Admin ping n 6 192 168 1 119 N TRON Admin ping t 192 168 1 1...

Страница 140: ...e nabled or d isabled dp Set the default QOS priority for the port The range is 0 7 dscp state Set the DSCP Priority for the port to e nabled or d isabled 8021p state Set the 802 1p Priority for the...

Страница 141: ...w Show configuration ro name Set the Authorized Community Name for SNMP Get requests rw name Set the Authorized Community Name for SNMP Set requests trap name Set the Authorized Community Name for SNM...

Страница 142: ...Show System Information Command Name Sysinfo Description Show system information Syntax Sysinfo Parameters None Example N TRON Admin sysinfo N TRON Admin sysinfo N TRON 700 7000 7500 Series Model 750...

Страница 143: ...et mask for static config mode and IP fallback g static_gateway Static gateway address for static config mode and IP fallback Example N TRON Admin sysip IP Configuration Mode Static Static IP Address...

Страница 144: ...xamples N TRON Admin system name Private switch browser disabled IP Configuration Static IP Address 192 168 2 201 Subnet Mask 255 255 252 0 Gateway 192 168 1 1 MAC Address 00 07 af fb a2 c0 System Up...

Страница 145: ...Revised 2011 07 21 Page 145 of 158 VLAN Addition and Deletion Example The screen capture below is the factory default VLAN configuration Clicking on the Modify button allows one to add a new VLAN...

Страница 146: ...a reserved name with a special meaning Choices such as Allow Management and Change PVID of Member Ports are made at this time as well as the ports which are going to belong to the new VLAN Additional...

Страница 147: ...icast address to the lowest VLAN ID that is associated with one of the ports assigned to the static multicast address If the lowest VLAN ID contains all the ports assigned to the static multicast addr...

Страница 148: ...Revised 2011 07 21 Page 148 of 158 And the New VLAN may be deleted when it is no longer required...

Страница 149: ...1 07 21 Page 149 of 158 And the New VLAN is removed Note that the new configuration of the switch must be saved if the configuration must survive a power cycle NOTE Changes have been made that have no...

Страница 150: ...ameras When used properly it will effectively isolate two or more groups from each other in a logical manner This means that Broadcast Multicast and Unicast frames in one VLAN will not interfere with...

Страница 151: ...ort s Notes TX1 Untagged MAC on port TX2 Packet Discarded TX1 VID 2 MAC on port TX2 TX2 Unicast Traffic TX1 VID 4 MAC on port TX2 Packet Discarded TX1 VID 2 MAC on port TX5 TX2 Floods VLAN 2 TX3 Untag...

Страница 152: ...ntagged MAC on port TX2 TX2 Adds VID 2 to packet TX1 VID 2 MAC on port TX2 TX2 Unicast Traffic TX1 VID 4 MAC on port TX2 Packet Discarded TX1 VID 2 Unknown MAC TX2 Floods VLAN 2 TX3 Untagged Unknown M...

Страница 153: ...VID 2 in the packet TX1 VID 4 MAC on port TX2 Packet Discarded TX1 VID 4 MAC on port TX3 Packet Discarded TX1 VID 2 MAC on port TX2 TX2 Strips VID off packet TX3 Untagged MAC on port TX6 TX6 Unicast T...

Страница 154: ...off packet Floods VLAN 4 TX2 Untagged MAC on port TX1 VID 2 TX1 Unicast Traffic TX2 Untagged MAC on port TX5 VID 2 TX5 Unicast Traffic TX2 VID 2 or 3 MAC on port TX5 VID 2 and 3 TX5 Strips VID off pac...

Страница 155: ...00 02 TX1 TX3 TX8 Goes to ports TX1 TX3 TX8 TX3 Untagged 01 00 00 00 00 01 TX2 TX4 TX8 Goes to ports TX2 TX4 TX8 TX6 Untagged 01 00 00 00 00 02 TX8 Goes to port TX8 TX3 Untagged 01 00 00 00 00 02 TX6...

Страница 156: ...0 to 10 000 ft Shock and Vibration bulkhead mounting Shock 200g 10ms Vibration Seismic 50g 5 200Hz Triaxial Reliability MTBF 2 Million Hours Warranty 3 years from the date of purchase Connectors 10 10...

Страница 157: ...suitable for use in Class I Div 2 Groups A B C and D or non hazardous locations only EMI FCC Title 47 Part 15 Subpart B Class A ICES 003 Class A EMS IEC 61000 4 2 ESD IEC 61000 4 3 RF IEC 61000 4 4 E...

Страница 158: ...ce WARRANTIES EXCLUSIVE IF AN N TRON PRODUCT DOES NOT OPERATE AS WARRANTED ABOVE CUSTOMER S SOLE REMEDY FOR BREACH OF THAT WARRANTY SHALL BE REPAIR REPLACEMENT OR REFUND OF THE PURCHASE PRICE PAID AT...