N-TRON SWITCH GROUNDING TECHNIQUES FOR 1000 SERIES 

 
 

The grounding philosophy of any control system is an integral part of the design.  N-Tron switches are designed 
to  be  grounded,  but  the  user  has  been  given  the  flexibility  to  float  the  switch  when  required.    The  best  noise 
immunity and emissions (i.e. CE) are obtained when the N-Tron switch chassis is connected to earth ground via 
a drain  wire.  Some N-Tron switches  have metal  din-rail brackets  that can ground the switch if the din-rail is 
grounded.  In some cases, N-Tron switches with metal brackets can be supplied with optional plastic brackets if 
isolation is required. 

Users may run a drain wire & lug from the screw provided on the back face of the 
enclosure.   In the event the provided grounding screw has been lost, care should 
be taken to limit the penetration of the outer skin by less than 1/4".  Failure to do 
so may cause irreversible damage to the internal components of the switch.  
 

Note:

 

Ensure the power supply is grounded properly before applying power to the 

grounded switch.  This may be verified by using a voltmeter to determine that there 
is no voltage difference between the power supply’s negative output terminal and 
the chassis grounding point of the switch.   

 

 
 
As  an  alternative  grounding  method,  both  V-  legs  of  the  power  input 
connector are connected to chassis internally on the PCB.  Connecting 
a  drain  wire  to  earth  ground  from  one  of  the  V-  terminal  plugs  as 
shown here  will ground  the switch and the  chassis.   The power leads 
from the power source should be limited to 3 meters or less in length. 

 

 
 

Note:

 

Before  applying  power  to  the  grounded  switch,  you  must  use  a  volt  meter  to  verify  there  is  no  voltage 

difference between the power supply’s negative output terminal and the switch chassis grounding point.  

 

If the use of shielded cables is required, it is generally recommended to only connect the shield at one end to 
prevent  ground  loops  and  interfere  with  low  level  signals  (i.e.  thermocouples,  RTD,  etc.).    Cat5e  cables 
manufactured to EIA-568A or 568B specifications are required for use with N-Tron Switches.  
 

 

 
In  the  event  all  Cat5e  patch  cable  distances  are  small  (i.e.  All  Ethernet  devices  are  located  the  same  local 
cabinet and/or referenced to the same earth ground), it is permissible to use fully shielded cables terminated to 
chassis ground at both ends in systems void of low level analog signals. 
 
 

DRAIN WIRE WITH LUG CONNECTING SWITCH 
CHASSIS TO KNOWN GOOD GROUNDING POINT. 

DRAIN WIRE WITH 
LUG CONNECTING 
SWITCH CHASSIS 
TO KNOWN GOOD 
GROUNDING 
POINT. 

METALLIC 
DIN-RAIL CLIP 

Содержание 1002MC-LX-YY

Страница 1: ...Revised 2014 01 23 1 1000 Series Gigabit Media Converter Industrial Gigabit Ethernet Switch User Manual Installation Guide...

Страница 2: ...00BaseLX singlemode fiber switch 1003GX2 B Custom mix and match 1003GX2 switch 1005TX 5 port gigabit Ethernet switch Where YY is 10 for 10km max fiber segment length 40 for 40km max fiber segment leng...

Страница 3: ...n contained in this document is subject to change without notice N Tron Corporation makes no warranty of any kind with regard to this material including but not limited to the implied warranties of me...

Страница 4: ...circuit est sous tension sauf si la zone est connue pour tre non dangereux WARNING Use 110 C or higher rated copper wire 0 22Nm 2 lb in tightening torque for field installed conductors ALERTE Utilisez...

Страница 5: ...les during periods of lightning activity ALERTE Ne pas travailler sur le mat riel ou les c bles pendant les p riodes d activit de la foudre WARNING Observe proper DC Voltage polarity when installing p...

Страница 6: ...utilize the RJ45 shielded connectors The 1002MC MCE is a two port unmanaged media converter that converts 10 100 1000Base T copper to 1000BaseSX LX full duplex fiber The 1003GX2 GXE2 is a three port...

Страница 7: ...G Clean only with a damp cloth INSTALLATION Read the following warning before beginning the installation Lire l avertissement suivant avant de commencer l installation WARNING ALERTE Never install or...

Страница 8: ...it snaps into place To remove the unit from the 35mm industrial DIN rail pull forward on the unit until it disengages from the bottom of the DIN rail Rotate the bottom of the unit towards you and up...

Страница 9: ...ty LED SPD1000 1000 Speed LED LEDs The table below describes the operating modes LED Color Description ON Power is Applied OFF Power is OFF LNK ACT ON Link established no Activity on cable BLINKING Li...

Страница 10: ...lug is 0 5 Nm 0 368 Pound Foot All LEDs will flash ON Momentarily Verify the Power LED stays ON GREEN Note Either V1 or V2 can be connected to power for minimal operation For redundant power operation...

Страница 11: ...ve output terminal and the chassis grounding point of the switch As an alternative grounding method both V legs of the power input connector are connected to chassis internally on the PCB Connecting a...

Страница 12: ...he same switch i e loop is an illegal operation and will create a broadcast storm which will crash the network Alerte Cr ation d un port de connexion du port sur le m me commutateur c boucle est une o...

Страница 13: ...cause harmful interference in which case the user will be required to correct the interference at his own expense INDUSTRY CANADA This Class A digital apparatus meets all requirements of the Canadian...

Страница 14: ...ipple Less than 100 mV Input Wire Size 12 24 AWG Environmental Operating Temperature 40 C to 85 C Storage Temperature 40 C to 85 C Operating Humidity 10 to 90 Non Condensing Operating Altitude 0 to 10...

Страница 15: ...pprovals Safety For use in Class I Division 2 Groups A B C and D Hazardous Locations UL 508 Industrial Control Equipment ANSI ISA 12 12 01 2007 for use in Class I and II Division 2 and Class III Divis...

Страница 16: ...le Less than 100 mV Input Wire Size 12 24 AWG Environmental Operating Temperature 40 C to 85 C Storage Temperature 40 C to 85 C Operating Humidity 10 to 90 Non Condensing Operating Altitude 0 to 10 00...

Страница 17: ...pprovals Safety For use in Class I Division 2 Groups A B C and D Hazardous Locations UL 508 Industrial Control Equipment ANSI ISA 12 12 01 2007 for use in Class I and II Division 2 and Class III Divis...

Страница 18: ...e Inrush Current 13 Amp 0 61 ms max 24VDC Input Ripple Less than 100 mV Input Wire Size 12 24 AWG Environmental Operating Temperature 40 C to 85 C Storage Temperature 40 C to 85 C Operating Humidity 1...

Страница 19: ...d Class III Divisions 1 and 2 Hazardous Classified Locations Groups A B C D T4 cUL C22 2 No 14 M05 cUL C22 2 No 213 M1987 for use in Class I Division 2 Hazardous Locations EMI EN61000 6 4 EN55011 Clas...

Страница 20: ...RANTIES EXCLUSIVE IF AN N TRON PRODUCT DOES NOT OPERATE AS WARRANTED ABOVE CUSTOMER S SOLE REMEDY FOR BREACH OF THAT WARRANTY SHALL BE REPAIR REPLACEMENT OR REFUND OF THE PURCHASE PRICE PAID AT N TRON...

Отзывы: