2

System overview

the Multipoint Control Box 8 zone system comprises of one of each of the following 
components:

• 

Multipoint Control Box 8 zone module

• 

24 VaC transformer

In addition to the control box module and transformer you will require at least one wall 
switch module and multiple zone dampers for multizone on/off control:

• 

Multipoint 2, 3 or 4 zone wall switch (MPWs234).

• 

Multipoint 5 or 6 zone wall switch (MPWs56).

• 

Multipoint 7 or 8 zone wall switch (MPWs78).

• 

My Zone touchpad (MZtP8). Refer to this manual for Fujitsu Bridge installation.

Electrical requirements

Power input to Controller .......................................24 volt aC ± 10% 
line frequency .......................................................50 Hz

Environmental requirements

operating temperature ..........................................0°C to 50°C 
altitude...................................................................0 to 2000 meters 
operating Relative Humidity .................................. 10% to 80% 
avoid static electricity hazards
avoid electromagnetic radiation sources
avoid dust contamination
avoid highly corrosive environments 

Cabling requirements

All data cables (wall switch) should be 6 core (5 + 1 shielded) flat cable with 6p6c plugs. 

Data cables should be kept as far from power cables as practical (minimum 300mm). 

Motor cables can be 6 core flat cable with 6p6c plugs, or 4 core flat cable with 6p4c plugs.

Multipoint Control Box 8 Zone Module

the Multipoint Control Box 8 zone module is the core component of the Multipoint 
Zoning system. all zone motors and wall switches connect to and receive power from 
the control box module. all wall switch and motor connections are made using the plug 
in cable system for easy installation, terminal connections are provided for the 24V 
power supply.

up to 2 wall switch modules may be connected to the control box module as standard. 
to connect more than 2 wall switches an expansion module is required. 

the control box module is physically designed to offer simple installation and operation 
and may be either Din rail or surface mounted.

Содержание Multipoint Control Box 8

Страница 1: ...l Box 8 Installation Manual Spill Zones Plug Play 8 7 6 5 Zone Motors 4 3 2 1 Zone Motors www metalflex com au MPCBT8 Touchpads 24VAC Supply A N Clock Option Fujitsu Bridge MOTOR OUTPUTS MOTOR OUTPUTS ON 1 2 3 4 5 6 7 8 ...

Страница 2: ...magnetic radiation sources Avoid dust contamination Avoid highly corrosive environments Cabling Requirements All data cables wall switch should be 6 core 5 1 shielded flat cable with 6p6c plugs Data cables should be kept as far from power cables as practical minimum 300mm Motor cables can be 6 core flat cable with 6p6c plugs or 4 core flat cable with 6p4c plugs Multipoint Control Box 8 Zone Module...

Страница 3: ...ir handling unit or in the mechanical services switchboard The wall switch should be mounted in a central location within the air conditioned space They are designed to be flush mounted to a cavity wall but may be surface mounted through the use of a mounting block not less than 15mm deep The motorised dampers can be mounted at the takeoff point of the rigid duct or mounted in line in the flexible...

Страница 4: ...e wall switch See image next page Once the number of zones for the wall switch has been selected place the zone labels in the appropriate position on the front of the switch prior to sticking the overlay in place Wall Switch Zone Number Assignment MPWS234 MPWS234 Jumper Position Zones Controlled JP1 Top 1 2 3 and 4 JP2 Middle 1 2 and 3 JP3 Bottom 1 and 2 Wall Switch Zone Number Assignment MPWS56 M...

Страница 5: ...Multipoint control box 8 Installation Manual 5 MPWS234 Multipoint Multipoint Multipoint MPWS56 Multipoint Multipoint MPWS78 Multipoint Multipoint ...

Страница 6: ...per motor being used In the event of a power loss and restore to the controller ie blackout the controller will resume operation with all zones in the on off state last set by the user Basic Connection Diagram Spill Zones Plug Play 8 7 6 5 Zone Motors 4 3 2 1 Zone Motors www metalflex com au MPCBT8 Touchpads 24VAC Supply A N Clock Option Fujitsu Bridge MOTOR OUTPUTS MOTOR OUTPUTS ON 1 2 3 4 5 6 7 ...

Страница 7: ... handles and pull the tool to remove the cables outer sheath and expose the insulated inner conductors Ensure the insulation on the inner conductors is not damaged Cable connections are polarity conscious It is essential that every cable termination for each installation is performed with the coloured inner conductors in the same order and position in the plug Any two cable ends should appear iden...

Страница 8: ...Reece Group 118 Burwood Highway Burwood Victoria 3125 Australia Tel 1800 032 566 Reece Group Pty Ltd 118 Burwood Highway Burwood Victoria 3125 Australia Tel 1800 032 566 Made in PRC ...

Отзывы: