background image

03

WHISPA III

®

5000, 9000 & 12000 RCU

1.0

2.0

3.0

4.0

1.0  Safety Instructions

2.0  Heating System Design

3.0  Selection and Sizing for Heating

l

Heat output performance figures for the three sizes of
WHISPA III

®

RCU fan convectors are given in the Technical

Data section of this manual.

l

Since WHISPA III

®

RCU fan convectors are supplied with fan

speed control, it is important to size the unit to match the 
calculated heat loss requirements of the room with the unit
operating at the low fan speed (I).

l

The higher fan speed can then be used for more rapid 
heating from cold in extreme conditions.

l

When establishing the temperature difference, i.e. entering
water to room temperature, allowance should be made for
temperature drop in the system. It is the water temperature
at the fan convector that dictates the output.

4.0  Location

l

The WHISPA III

®

RCU fan convector is designed for recessed

wall applications.

l

WHISPA III

®

RCU fan convectors are designed for normal 

2" x 4" stud wall framing, with 5/16" thick cover 
extending beyond the wall surface once installed.

l

The size of the opening required to be cut for installation is
shown in Fig 1. 

READ THIS INSTRUCTION MANUAL THOROUGHLY BEFORE BEGINNING INSTALLATION.

This appliance is intended for indoor use only. For
your safety please install and use this unit with the
following precautions:

l

This appliance must not be fitted in a bathroom or other 
similar high humidity area.

l

According to the National Electrical Code all electrical work
must be carried out by authorised/licensed professionals.

l

To provide continued protection against electric shock, 
this appliance must be grounded.

l

Isolate the electrical supply before commencing any electrical
work.

l

A suitable socket outlet with isolating switch must be 
available, or fitted to supply the unit.

l

In the event of a fault with this product, immediately isolate
from the electrical supply.

l

The minimum wall cavity depth required for installation is 
3

1

/

2

".

The WHISPA III

® 

RCU should be used on closed circulation, two

pipe, pump assisted central heating systems or as a stand alone
zone or it can be fitted on a series loop with mono-flo or venturi
Tees.

Before proceeding with the installation, the heating system 
design must be considered and the unit correctly sized to meet
the heat loss requirements of the room at normal fan speed. 

For optimum fan convector performance the system must be 
capable of providing sufficient water flow through the heat 
exchanger. This means that:

1. Care must be taken in sizing both the pump and piping.

2. The minimum pipe size from boiler to fan convector must be

at least 

1

/

2

".

3. Where the unit is fitted on to a system with other emitters a

separate circuit for the fan convector should be considered
to provide adequate water flow.

4. The system water must be above 110°F for the fan to switch

on and for satisfactory operation the mean water temperature
should be above 140°F. 

5. Optimum performance of this unit will require effective

balancing of the whole system.

6. This unit should NOT be used to replace a radiator in an 

existing heating system unless an adequate flow of water can
be guaranteed through the unit.

7. The loop must be pumped. WHISPA III

®

fan convectors are

not suitable for gravity circulation systems.

EN

33359 Whispa RCU (US) FR.qxp  15/04/2019  11:00  Page 4

Содержание WHISPA III 9000

Страница 1: ...AFTER SALES MANUAL MANUEL D INSTALLATION D UTILISATION ET D ENTRETIEN Product Serial Number Num ro de s rie du produit Please leave this manual with the end user Ce manuel doit tre disposition de l u...

Страница 2: ...tential hazard DANGEROUS VOLTAGES To indicate hazards arising from dangerous voltages HOT SURFACE To indicate that the marked item can be hot and should not be touched without great care PROTECTIVE EA...

Страница 3: ...ontinued protection against electric shock this appliance must be grounded l Isolate the electrical supply before commencing any electrical work l A suitable socket outlet with isolating switch must b...

Страница 4: ...for the unit enters on the lower left hand corner of the unit see Fig 2 l Prepare the opening in the wall to accept the unit as shown in Fig 1 Depending on the wall framing layout the 9 000 and 12 000...

Страница 5: ...completed l The electrical installation must comply with local or national wiring regulations l A hole is provided at the lower left hand corner of the unit for a BX or Romex connector l A 24V room t...

Страница 6: ...supplied l Once the connections to the heating loop are complete the unit must be vented using the air purge valve Fit a length of hose to the purge valve so that any water from the heating circuit es...

Страница 7: ...07 WHISPA III 5000 9000 12000 RCU 7 0 Water Connection continued Fig 4 Front cover fixing screws 7 0 EN 33359 Whispa RCU US Manual FR qxp 15 04 2019 11 00 Page 8...

Страница 8: ...5652 6187 6718 7245 7767 4369 5437 6524 7623 8739 9866 11003 12149 13307 14472 3019 3733 4454 5180 5911 6649 7389 8136 8887 9640 3845 4785 5740 6709 7690 8682 9682 10692 11709 12734 2657 3284 3918 45...

Страница 9: ...erature The fan speed can be set to boost by switching the fan speed switch to II A low speed setting is recommended for normal operation with the higher speeds for boost heating when required Low Lim...

Страница 10: ...ng unit below 110 F Problem Remedy Turn up room thermostat Switch on breaker Check all wiring reset breaker Check boiler Programmer ON Boiler ON and set to high Circulating pump running Note Operation...

Страница 11: ...taking care not to damage the fan or heat exchanger Part Number Description Quantity Spares List Motor Fan Assembly WHISPA III 5000 RCU 7100088 1 Motor Fan Assembly WHISPA III 9000 RCU 7100090 1 Motor...

Страница 12: ...un danger potentiel TENSIONS DANGEREUSES Pour indiquer tout danger li aux tensions dangereuses RISQUE DE BR LURE Pour indiquer que la pi ce en question peut tre chaude et doit tre manipul e avec le p...

Страница 13: ...areil la masse l Isoler le produit de toute alimentation lectrique avant de commencer l installation lectrique l Une prise de courant adapt e avec un sectionneur doit tre disponible ou install e pour...

Страница 14: ...c ble de 120V CA pour l appareil entre via son coin inf rieur gauche Voir Fig 2 l Pr parer l ouverture dans le mur pour accueillir l appareil comme indiqu la Fig 1 En fonction de l ossature murale le...

Страница 15: ...llation lectrique doit respecter les r glementations locales ou nationales de raccordement l Un trou figure au niveau du coin inf rieur gauche de l appareil pour le convecteur BX ou Romex l Un thermos...

Страница 16: ...rature d eau concern e l Une fois les branchements la bouche de chauffage termin s il convient de ventiler l appareil l aide de la vanne de purge d air Raccorder une longueur de tuyau la vanne de purg...

Страница 17: ...FR 17 WHISPA IIIMD 5000 9000 12000 RCU 7 0 Raccordement au circuit d eau suite Fig 4 Vis de fixation du couvercle avant 7 0 33359 Whispa RCU US Manual FR qxp 15 04 2019 11 00 Page 18...

Страница 18: ...7690 8682 9682 10692 11709 12734 2657 3284 3918 4558 5202 5851 6504 7160 7819 8482 110 120 130 140 150 160 170 180 190 200 Donn es sur les performances de chauffage 5000 RCU 9000 RCU 12000 RCU Interru...

Страница 19: ...t la position II Pour un fonctionnement normal il est recommand d opter pour une vitesse faible Il convient de r server les vitesses plus lev es lorsqu une augmentation de la chaleur est n cessaire Fo...

Страница 20: ...p bas Absence de flux vers le convecteur de ventilation Pompe r gl e bas Vannes d isolation pas compl tement ouvertes Syst me mal quilibr avec appareil priv de d bit d eau chaude Tuyau branch l appare...

Страница 21: ...Groupe moto ventilateur WHISPA IIIMD 9000 RCU 7100090 1 Groupe moto ventilateur WHISPA IIIMD 12000 RCU TBA 1 Interrupteur 3 positions 1300025 1 Thermostat basse limite 1260007 1 Plaque de protection W...

Страница 22: ...Notes 22 WHISPA III 5000 9000 12000 RCU 33359 Whispa RCU US Manual FR qxp 15 04 2019 11 01 Page 23...

Страница 23: ...33359 Whispa RCU US Manual FR qxp 15 04 2019 11 01 Page 24...

Страница 24: ...E DITION 3 heatingthroughinnovation RETTIG USA INC MYSON 45 Krupp Drive Williston VT 05495 T 800 698 9690 F 802 654 7500 info myson com www mysoncomfort com 33359 Whispa RCU US Manual FR qxp 15 04 201...

Отзывы: