1. GENERAL USE OF THE ADSORPTION DRYER
MYCOND DESS-80 adsorption dehumidifiers are normally used where dry air is essential for the various manufacturing
processes for the chemical, pharmaceutical and food or confectionary industry or where a dry environment is needed
for the storage and handling of moisture-sensitive products and raw materials. Tried and proven air drying by means
of adsorption is highly flexible when it comes to remedying air humidity problems. It gives the user independent
control of the air humidity, which makes it possible to achieve much lower dew points than refrigeration drying.
The devices are intended for use in occupied and unoccupied indoor rooms. When used outdoors, the units must be
protected against the effects of weather.
The dehumidifier works in a continuous process made up of two air flows with different flow rates (ratio of 3:1). The
greater air flow (process air) is dried when it passes through the dehumidifier, while the smaller regeneration air flow
is used to heat the rotor material and remove the adsorbed moisture from the desiccant. Moisture removed from the
process air is transferred to the regeneration air by the slow turning of the rotor.
2. SETTING UP THE DEVICES
Note:
1. There are two handles on the side of the MYCOND DESS-80 as well as a handhold depression on the top.
They are used exclusively for carrying the compressor.
2. The units must be secured against rolling away or slipping during transport. Never stack more than 3 dryers
on top of each other.
3. When set-up close to stairs or ledges, the units must be secured against rolling away or tipping.
4. If possible, only put the units in rooms that are not constantly in use by people.
5. Prevent any tripping hazards caused by placement of the hoses. Consider hanging the hoses up in public
areas.
6. The dryers must have a power supply with 16 A fuse protection. The use of a starting current limiter is
recommended in old buildings in order to prevent premature triggering of fuses.
7. The electrical connection must be protected with a residual current operated circuit breaker (30 mA).
8. Under no circumstances is there to be an explosive atmosphere in the application area.
INSTALLATION
To exclude recirculation, care must be given during the installation to ensure that the emitted humid regeneration
air or the dried air is not drawn in again by the dehumidifier. Cold process air with relatively high humidity can cause
condensation inside the dehumidifier at the humid air outlet. Due to the high moisture content at the humid air out-
let, condensation can occur inside the pipe. We recommending installing the pipe at the humid air outlet at an angle