AC•THOR
®
/ AC•THOR
®
9s Operating instructions, version a0020806
29
In level 1 the setting possibilities are limited to temperature specifications and switching times for
space heating (only relevant in operating modes M5 and M6), as well as the brightness and duration
of the display settings and brightness of the AC•THOR logo.
A password is required to be able to return to a higher level. The password for level 2 is "1970", that
for level 3, "1965".
Power timeout: With this setting, the timeout of the
AC•THOR
(power timeout) can be set for
several control types.
Hysteresis: switch hysteresis can be set for hot water and room heating. This does not cause too
high a target temperature! After reaching the target temperature, the value is allowed to fall by the
set amount before the heating process is restarted.
Hot water maximum temperature (factory setting 3.0 °C)
Hot water minimum temperature (factory setting 3.0 °C)
Space heating maximum temperature (factory setting 0.5 °C)
Space heating minimum temperature (factory setting 0.5 °C)
Error log: The table shown is intended for analysis by my-PV.
Factory settings:
Factory settings: tapping on the men
u point resets the AC•THOR to its factory settings. This will
cause all altered settings in the unit to be deleted!
CAUTION! No security confirmation is requested!
Check for new firmware:
Internet access is required!
Start check for new updates manually. When a new version is available, it will be stored on the SD
card. This procedure takes several minutes. The AC•THOR will operate normally during this period.
Start firmware update: if a newer software version is present on the SD card, the update can be
started manually. After the update, the unit will be restarted automatically.
Start power firmware update: if a newer output unit software version is present on the SD card, the
update can be started manually. After the update, the unit will be restarted automatically. With
AC•
THOR 9s the update for both power stages is started.
By means of a HTML file (required for Ethernet firmware version a0020000 or higher) data of the
AC•T
HOR can be retrieved and adjustments can be made.
TIP: The Web-Interface offers much more extensive setting
options than the AC
•
THOR Display!
You can only access the web
interface if the AC•THOR is in a network. If it has a direct
connection to the power meter, this access is not possible!
If you cannot access the AC•THOR in the network, check the network settings on the display!
Expiry of the network connection:
1.
A
fter the connection using a patch lead the AC•THOR is assigned a dynamic IP address by the
router. It can then be searched for in the network using the program "my-PV Scanner.exe"
(included in the "Software package
AC•THOR
.zip" on www.my-pv.com). To do this, unpack the