VR-16 – short operating manual 

Feb 8, 2017 

 

8/8 

Version 1.0 

 

 

 

 

 

 

3.4

 

Sensor fault 

If the sensor is missing or the device cannot test the sensor for other reasons, the device 
will issue a fault notification. The display will be as shown in Figure 12. Fault is indicated by 
the letter F and a blinking LED light. In fault mode the relay is released. 

 

Figure 12. Display indicates a sensor fault. 

4

 

Acknowledging fault modes 

Fault  modes  can  be  acknowledged  by pressing  the  R (reset /  set)  button  for a  long time. 
Acknowledging is only possible if the fault mode has been removed.  

The fault mode can also be acknowledged by using off the device's voltage for sufficiently 
long while the Error Memory setting is in OFF position. 

Содержание Superintend Trafox VR-16

Страница 1: ...story Version 1 0 New document Version 1 1 Table of Contents 1 Preface 2 2 Menu selections 2 2 1 Limit Menu L 3 2 2 Delay Menu d 4 2 3 Sensor Menu S 5 2 4 Error Memory E 6 3 Modes during operation 6 3 1 Normal operation 6 3 2 Alarm 7 3 3 Warning 7 3 4 Sensor fault 8 4 Acknowledging fault modes 8 ...

Страница 2: ...he current is below the set fault limit the display shows sensor current Figure2 Figure 1 Basic mode Figure 2 Current below set limit in basic mode Go to menus from the basic mode by keeping M Menu button pressed down When you keep pressing down the M button you browse through menus at short delay intervals Select a menu by releasing the M button when the desired menu is displayed Figure 3 When th...

Страница 3: ...essing the M button briefly Confirm your selection by pressing R Reset set button for a long time Once a selection is confirmed you return to the basic mode The limit value choices available are 30mA 100mA 300mA 500mA 1A 3A or 10A Figure 4 Figure 4 Selecting limit value with short presses of the M Menu button Confirm your selection by pressing R Reset set button for a long time ...

Страница 4: ...er by pressing the M button briefly Confirm your selection by pressing R Reset set button for a long time Once a selection is confirmed you return to the basic mode The delay choices available are 100ms 500ms 1s 3s 5s or 10s Figure 5 Figure 4 Selecting delay time with short presses of the M Menu button Confirm your selection by pressing R Reset set button for a long time ...

Страница 5: ...nother by pressing the M button briefly Confirm your selection by pressing R Reset set button for a long time Once a selection is confirmed you return to the basic mode Sensor choices available are 25A 35A 60A 95A 130A or 200A Figure 6 Figure 6 Selecting sensor with short presses of the M Menu button Confirm your selection by pressing R Reset set button for a long time ...

Страница 6: ...mode means that the error mode is remembered when power returns even if it no longer is valid and OFF mode means that switching off power resets the fault mode if the fault is removed Figure 7 Selecting error memory ON OFF with short presses of the M Menu button Confirm your selection by pressing R Reset set button for a long time 3 Modes during operation 3 1 Normal operation The device is in its ...

Страница 7: ... indicated by the letter A and a blinking LED light In alarm mode the relay is released The value of measured current is 158mA Figure 10 Display in alarm mode 3 3 Warning When the current exceeds the set current limit the display will be as shown in Figure 11 Warning is indicated by the letter P and blinking LED light The warning mode is active if the current exceeds the set limit but the overrun ...

Страница 8: ...dicated by the letter F and a blinking LED light In fault mode the relay is released Figure 12 Display indicates a sensor fault 4 Acknowledging fault modes Fault modes can be acknowledged by pressing the R reset set button for a long time Acknowledging is only possible if the fault mode has been removed The fault mode can also be acknowledged by using off the device s voltage for sufficiently long...