VR-16 – short operating manual
Feb 8, 2017
6/8
Version 1.0
2.4
Error Memory ( E )
Once Error Memory is selected, the display shows the current set value. Go from one
selection to another with short presses of the M button (Figure 7). Confirm your selection
by pressing R (Reset / set) button for a long time. Once a selection is confirmed, you return
to the basic mode. The selection allows you to choose whether the device will remember
the error mode after power returns. ON mode means that the error mode is remembered
when power returns even if it no longer is valid and OFF mode means that switching off
power resets the fault mode if the fault is removed.
Figure 7 Selecting error memory ON / OFF with short presses of the M (Menu) button. Confirm your
selection by pressing R (Reset / set) button for a long time.
3
Modes during operation
3.1
Normal operation
The device is in its basic mode when the current sensor is connected and power is switched
on. Power is not supplied through the current sensor (Figure 8). When the current is below
the fault limit, the display shows sensor current (Figure9). You can go from basic mode to
Menu selection.