Alarm relay
Operational mode:
normally opened or normally closed
Alarm function:
MAX, MIN oder sensor fault
Fail-LED/red:
permanent light → limiting value alarm
Relay contact:
1 opener or closer
Switching capacity:
max. 30 VA at AC, max. 15 W at DC
Switching voltage:
max. 30 VDC or 125 VAC
Switching current:
max. 0,5 A
Min-Contact voltage:
10 mVDC
Min-Contact current:
10 µA
Contact material:
AgPd+Au or PdRu+Au
Interfaces
USB:
Front socket connection (USB-B mini) for PC/Notebook
RS485:
2400, 4800, 9600 or 19200 bps, device address: 1-255
Power supply
Type:
energy supply class A.C.3 or D.C.4 by IEC 654 part 2
AC:
24 VAC, -
20%
to
+20 %, 50
-60 Hz
DC:
24 VDC, -
20 %
to
+30 %
Power consumption:
max. 2 W
Power-LED/green:
good condition
of the supply
Electromagnetic Compatibility
This product meets the specifications according to the EMC directive 2014/30/EU.
More Data
Fail-LED/red:
slow blink → no sensor connection
fast blink → FRAM
-memory error
Form of construction:
Housing for 35 mm DIN rail (EN 50022)
Dimension:
22,5 x 99 x 114,5 mm
Ambient temperature:
-10 to +60°C
Protection class:
IP 20
Weight:
150 g
4.1. Dimensions of the housing
Fig. 3