6.4 Replacing UPS Internal Batteries 

Follow the steps and Charts as below to replace batteries: 

1. 

Take off the LCD box, and remove 

the screws.

 

 

 
 

2.  Slide  and  Pull  the  front  panel 
leftward and then take it off. 

 
 
 
 
 

 

3.  Disconnect  the cable from the UPS 
and battery pack.   

 

4.  Remove  the  right  inner  battery 
bracket.   

 

 

5.  Pull  the  battery  pack  out  onto  flat 
area. 

 

6.  Install new battery pack into UPS.   

 

7.  Screw  up  the  battery  bracket  and 
reconnect the battery cable A and B 

 

8.  Re-install  the  front  panel  back  to 
UPS. 

6.5 Testing New Batteries 

For a battery test, please check: 

 

The batteries must be fully charged. 

 

The UPS must be in Normal mode with no active alarms. 

 

Don’t take on/off the load. 

To test batteries: 
1.  Connect the UPS to utility power for at least 48 hours to charge the batteries. 

Содержание PowerMust 1513S NetGuard

Страница 1: ...AFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for 1500VA 2000VA 3000VA series that should be followed during installation and maintenance of the UPS and batter...

Страница 2: ...wever for the exact warranty period and the warranty terms you should contact your reseller as both the warranty period and the terms may vary per Country Region Problem solving Please check the chapt...

Страница 3: ...ON PORT 8 5 1 RS 232 AND USB COMMUNICATION PORTS 8 5 2 EMERGENCY POWER OFF EPO 9 5 3 NETWORK MANAGEMENT CARD OPTIONAL 9 6 UPS MAINTENANCE 10 6 1 UPS AND BATTERY CARE 10 6 2 STORING THE UPS AND BATTERI...

Страница 4: ...anel Communication and control of UPS is available through serial or USB ports located on the rear panel The serial port will support communications directly with a server Features Microprocessor cont...

Страница 5: ...ied service personnel knowledgeable of batteries and required precautions Keep unauthorized personnel away from batteries Proper disposal of batteries is required Refer to your local codes for disposa...

Страница 6: ...Setup and Rack Mount Setup Tower setup This series of UPS can be placed horizontally and vertically As a tower configuration it is provided with the optional UPS stands to stabilize the UPS when the U...

Страница 7: ...ighten the screw and the load can then be connected Fig 7 Fig 6 Fig 7 4 Operation 4 1 Display Panel The UPS has a four button graphical LCD with dual color backlight Standard back light is used to lig...

Страница 8: ...allows users to configure the settings and the settings string will flash Confirm settings Press and hold the Enter button for one second Exit Settings mode Press and hold the Enter button for 3 secon...

Страница 9: ...being used by the protected equipment Each LCD level bar indicates a 20 of the total UPS output capacity UPS Status Display String Description The following table shows the description of the LCD dis...

Страница 10: ...s mode the UPS accepts AC input voltage range for 30 20 Battery mode When the UPS is operating during a power outage the alarm beeps once every four seconds and the LCD display string shows bATT to in...

Страница 11: ...tings mode Press more than 3 seconds to enter setting mode 2 Select settings items Press to select setting items as GF 3 Enter settings item Press more than one second to enter the setting item 4 Sele...

Страница 12: ...24Vdc and 20mA and be a dedicated latching type switch not tied into any other circuit The EPO signal must remain active for at least 20ms for proper operation EPO Connections Wire Function Terminal...

Страница 13: ...Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions Keep unauthorized personnel away from batteries Batteries can present a risk of electr...

Страница 14: ...r battery bracket 5 Pull the battery pack out onto flat area 6 Install new battery pack into UPS 7 Screw up the battery bracket and reconnect the battery cable A and B 8 Re install the front panel bac...

Страница 15: ...tion Table7 Electrical Specification Model 1513S 2018S 3027S Capacity VA Watt 1500VA 1350W 2000VA 1800W 3000VA 2700W Input Input voltage range 0 300VAC Frequency range 50 60Hz 5Hz for Normal Mode 40 8...

Страница 16: ...emperature 0 to 40 C Humidity 20 80 relative humidity non condensing Altitude 1500m Storage Temperature 15 to 45 C Table10 Dimensions and weights Model 1513S 2018S 3027S UPS Case Net weight kg 17 8 21...

Страница 17: ...nding every second and OVLD on screen Output overload Check load level indicator and remove some load Continuously sounding and red display The UPS fails Please contact your local dealer 8 2 General T...

Страница 18: ...rol your UPS This unique software provides complete power protection for computer system while power failure With the software users can monitor any UPS status on the same LAN Furthermore a UPS can pr...

Отзывы: