Output Mode
There are two ways to configure the outputs. All configuration is done through the same PGN. PGN 61408 is used for multiple messages by use of a
different value put into the “command” byte of the PGN. This value is used a an index or pointer as to where the information goes in the module.
1. All Output Configuration
(only used if you want all the outputs to be configured the same)
Configuring all of the outputs is done through the “MODE1” byte in PGN 61408. The J1939 message structure,
Name
Data Type
Byte
Bits
Description
Command
Byte
1
Command for index pointer (which message your sending)
Ctrl Mode Reset
2 bit
2
1,2
Enables Controller Mode Output Reset. Enabled (01) = cycling the output will reset the fault,
if (00) power cycle required for fault reset
Enable
(Status Msg 1)
3,4
Enables the constant transmission of status message 1
Enable
(Status Msg 2)
5,6
Enables the constant transmission of status message 2
Enable
(Amp Msg)
7,8
Enable the constant transmission of amperage message
Enable 24 vdc
3
1,2
Enables the low and over voltage fault limits for 24 vdc system
Save
Configuration
3,4
Saves the configuration to the module (otherwise changes only valid until a power cycle occurs),
set to 1 to write configuration to module
5,6
7,8
4
1,2
3,4
5,6
7,8
FREQ1
Word
5
Sets the configuration of the frequency for all channels (30-1140 Hz) value = 0x 01-FE
6
MODE1
4 bit
7
Sets the configuration of ALL the outputs, overides Command 53 and 54.
(0=Mode 1 NOT USED, 1=ON/OFF, 2=Data 0-4000, 3= Percent 0-100.0%(0-1000))
MODE2
4 bit
Sets the configuration of ALL the inputs. (NOT USED ON THIS MODULE)
ID1
Byte
8
User defined byte for configuration ID, this will be transimitted in the STAT message.
* PGN is different depending on Node ID offset. See PGN’s used sheet
5.2.3 CONFIGURING OUTPUTS
PGN
61408 (0xEFE0)
Source Address
(0x?? (CSA*))
PDU Format
239 (0xEF)
PDU Specific
224 (0xE0)
Built Message
(0x
18EFE0??
)
Transmit rate
50 ms
Msg timeout
200 ms
Priority
6
DP
0
Command Value
82 (0x52)