Configuration & Power Plug
CAN
1
2
4
3
6
5
7
8
1 2
3 4
5 6
7 8
9 10 11 12
13 14 15 16 17 18
Power 1
Power 2
Power 3
Ground(B)
Ground(B)
Ground(B)
Ground(B)
Power 4
Power (Output only)
Power 1 = 13 amps for ports 1 & 2 (Outputs 1A, 1B, 2A, 2B)
Power 2 = 13 amps for ports 3 & 4 (Outputs 3A, 3B, 4A, 4B)
Power 3 = 13 amps for ports 5 & 6 (Outputs 5A, 5B, 6A, 6B)
Power 4 = 13 amps for ports 7 & 8 (Outputs 7A, 7B, 8A, 8B)
Ground(B)=
output ground, internally connected to all Ground B pins
Please note that ALL module power
connections need to be made in order to
receive power on all output ports.
All Ground (B) connections are internally
connected. All connections must be made to
achieve the current rating of the block
A Ground (B) connection must be made for
every 13A consumed by the block
5.2 OUTPUT CONFIGURATION
5.2.1 POWERING THE OUTPUTS