Operation
User manual 59719_hdb_en_12
42 / 65
7.1.3
LED indication for inputs and outputs
LED indication
digital inputs/outputs
Tab. 7-4: LED indication for digital inputs/outputs
Error at input or output
If at at least one input or output an error occurs, the LEDs will light in red on
all M12 input slots and output slots.
7.2
IO-Link object directory
7.2.1
DPP
7.2.1.1
Art.-No. 59719, 59819
LED in-
dication
LED state
Voltage at in-
put
Description
Logical
value
Yellow
Permanently on
24 V
Channel on
1
Red
Permanently on
0 V
Short-circuit or over-
load DO
0
Off
0 V
Device off or firmware
update is being per-
formed
0
ISDU
index
DPP
index
Object name
Access Length
in bytes
Meaning / default value
Identification
DIO8
Art.-No. 59719
DIO8
Art.-No. 59819
0x0000
0x00 MasterCommand
W
1
0x01 MasterCycleTime
R/W
1
0x02 MinCycleTime
R
1
0x03 M-sequenceCapa-
bility
R
1
0x04 RevisionID
R/W
1
0x05 ProcessDataIn
R
1
0x06 ProcessDataOut
R
1
0x07 VendorID 1 (MSB)
R
1
0x012F
0x08 VendorID 2 (MSB)
R
1
0x09 DeviceID 1 (octet 2,
MSB)
R/W
1
0x0C
0x0A DeviceID 1 (octet 1,
MSB)
1
0x00
0x0B DeviceID 1 (octet 0,
LSB)
1
0x09
0x0A
0x0C FunctionID 1 (MSB)
R
1
0x0D FunctionID 2 (LSB)
1
0x0E Reserved
R
1
0x0F SystemCommand
W
1
0x0002
SystemCommand
R
1
0x0003
DataStorageIndex
R
variable
0x000D
ProfileCharacteristic R
variable
0x000E
PDInputDescriptor
R
variable
0x000F
PDOutputDescriptor R
variable
0x0010
VendorName
R
64
Murrelektronik GmbH