Technical Data
User manual 59719_hdb_en_12
20 / 65
4.2
Art.-No. 59819
4.2.1
Electrical data
Total current US
Fig. 4-2: Total current US
Module supply
Operating voltage US
24 V
Operating voltage range US
18 ... 30 V
Total current US
≤50 °C (see Derating)
≤4 A
Power consumption when idling
≤40 mA
Galvanic isolation
No
0
0,5
I [A]
1
2,5
1,5
2
-30
0
T [°C]
-10
20
10
3
30
-20
40
50
60
70
IO-Link
Communication speed
COM3
Transfer rate
230,400 bit/s
Bus protocol
IO-Link V1.1.2, compati-
ble with IO-Link V1.1.3
IO-Link cycle time
≥1 ms
VendorID
0x012F
DeviceID
0x0C000A
Process data
4 byte (inputs),
2 byte (outputs)
Sensor power supply
Connection/female connector
M12
Operating voltage
24 V
Power supply
Per port
≤0.5 A
Input (DI)
Connection/female connector
M12
Cable cross section
≤0.75 mm²
Cable length
≤30 m
Input characteristic
EN 61131-2
Type 1 + Type 3
Input filter
1 ... 10 ms, adjustable