Section 80
00-02-0829
2018-02-26
-
51 -
4.5.7 Output Configuration Handshake
After the output channels settings are sent to the PDM, the stored settings are then broadcast
back to the configuring device in order to verify the intended configuration. Only after the
settings are in agreement should the output be enabled.
CAUTION:
Use this message to verify the output settings prior to enabling any
output.
This CAN message is broadcast by the PDM to communicate the settings of a group of output channels.
Depending on the Feedback and Diagnostics Identifier byte, the message pertains to Output Channels 1-6 or 7-
12 respectively.
Transmission Repetition
20 – 500 ms
Data Length
8 bytes
Data Page
0
PDU Format (PF)
239
Proprietary A, PDU1 format
PDU Specific (PS)
17 (11h)
DA (Source Address of the configuring display or
controller)
Priority
5
Parameter Group Number
61184 (EF00h) -
Feedback and Diagnostics
Start Position Length
Parameter Name
Reference
1
1 byte
Feedback and Diagnostics Identifier (135 or 136)
2.5
4 bits
Current Limit (Output Channel 1 or 7)
2.3
2 bits
Feedback Type (Output Channel 1 or 7)
2.2
1 bit
Automatic Reset (Output Channel 1 or 7)
2.1
1 bit
High-Side or H-Bridge (Output Channel 1 or 7)
3.5
4 bits
Current Limit (Output Channel 2 or 8)
3.3
2 bits
Feedback Type (Output Channel 2 or 8)
3.2
1 bit
Automatic Reset (Output Channel 2 or 8)
3.1
1 bit
High-Side or H-Bridge (Output Channel 2 or 8)
4.5
4 bits
Current Limit (Output Channel 3 or 9)
4.3
2 bits
Feedback Type (Output Channel 3 or 9)
4.2
1 bit
Automatic Reset (Output Channel 3 or 9)
4.1
1 bit
High-Side or H-Bridge (Output Channel 3 or 9)
5.5
4 bits
Current Limit (Output Channel 4 or 10)
5.3
2 bits
Feedback Type (Output Channel 4 or 10)