Section 80
00-02-0829
2018-02-26
-
32 -
4.3.2.3 Feedback Type
Feedback type is always set to Current. The other modes are not supported on the IX3212-24.
00 Position feedback (not supported on the IX3212-24)
01 Rate feedback (not supported on the IX3212-24)
10 Power feedback (not supported on the IX3212-24)
11 Current feedback (always)
Data Length:
2 bits
Resolution:
4 states / 2 bits
0 offset
Data Range:
3
Operational Range: same as data range
Type:
Status (measured)
PGN:
PGN 61184 –
Output Configuration Handshake
4.3.2.4 Automatic Reset
Automatic Reset specifies if the PDM shall autonomously reset the output or remain in the OFF state during an
over-current event. Once an output is turned OFF by the PDM, the output needs to be commanded OFF prior to
commanding the output.
0 Automatic reset (5 attempts to reset before remaining OFF)
1 No automatic reset (remain in OFF state)
Data Length:
1 bit
Resolution:
states / 1 byte
0 offset
Data Range:
0
Operational Range: same as data range
Type:
Status (command)
PGN: