© Munters AB, 2018
32
6.11
Variable Heat
VARIABLE HEAT
#01
Heat1
Heat2
Ht Diff
0.0
0.0
Band
10.0
10.0
Min(%)
Max(%)
End Day
30
100
0
30
100
0
•
Heat Diff: Differential from heat temperature to initiate variable heaters. Default: 0.0
•
Band: Temperature range in which the variable heater operates in the power range between
minimum and 100%. For example: the heater temperature is 26°C, the temp diff is -1 and the
temp band is 2. At 25°C the heater will operate at minimum power according to minimum heat.
At 24°C and down the heater will operate at 100% and between 26°C and 24°C there will be
a power band between minimum and 100%. Default: 0.0
•
Minimum Heat: Minimum heaters operation for safety measures. This parameter refers to both
var. heat 1 and var. heat 2. Default: 30%
•
Maximum Heat: Maximum heaters operation for safety measures. This parameter refers to both
var. heat 1 and var. heat 2. Default: 100%
•
End Day: Set the last growth day for the Variable Heaters operation. Default: 0