Dehumidi
fi
er MKD-series
3.9.2 MK90D
Error messages
Illustration
Cause
Remedy
Red light on right
warning LED
HIGH
TEMP
on display .
Water container is full
or fault on water pump
(accessory)
See emptying guide
below, or check pump
outlet
Red light on right
warning LED
HIGH
TEMP
on display
Pressure or temperature
in high pressure element
too high
Check
fi
lter and
dehumidi
fi
er for dirt
in airways
Red light on right
warning LED
AMBIENT TEMP
on display
Room temperature out
of normal range
Place the dehumidi
fi
er
in the speci
fi
ed
temperature range,
between 3°-32°
Red light on right
warning LED
SENSOR FAIL
on
display. One of the
internal sensors is
defective. Use the +/-
keys to toggle between 3
possible errors
SENSOR FAIL
1: EVAP FAIL
Evaporator
thermometer defective
Requires an authorised
service technician
2: COND FAIL
Condenser
thermometer defective
Requires an authorised
service technician
3: ROOM FAIL
The internal room
thermometer is
defective
Requires an authorised
service technician
Red light on right
warning LED
LP
STOP
on display
Leak in cooling circuit
Requires an authorised
service technician
190TEN-1071-C1304