er MKD-series
2.2 Connection of humidistat
The connection socket for the humidistat is located at the power cable entry.
The humidistat shall be mounted 1–1.5 m. above the
fl
oor and positioned so that it is not exposed directly to
dry air from the unit or incoming moist air from opening and closing doors. It may not be placed close to a
heat source or so that it is exposed to direct sunlight. The humidistat shall be a single stage humidistat and
connected so that the controlling circuit closes as relative humidity increases. The connecting cable shall be
screened and have copper conductors with a minimum cross-section area of 2 x 0.75 mm2.
2.3 Remote signals
If an external alarm or run signal is required use terminal 24 and 25 which are connected by an electronic
relay. The run signal to be connected at terminal 22 and 23. If an error occurs there is no longer connection
and the alarm will start. Max 24V DC and 1,5mA.
7
Installation
190TEN-1071-C1304