4. Define:
•
Heat Curve: Choose heaters' operating method. Default: Linear
o
Linear: When using an analog output sensor, the variable heater aims to keep the
temperature within the Heater Temperature Band.
•
Response Time: This parameter defines how often the temperature is sampled and the output
updated accordingly. During this time period Heater control is idle, the temperature is not
being sampled, and the output doesn’t change. Range: [0-999], default 15.
Note that in Variable Heating, the output decreases in a curve as the temperature approaches the Off
Temperature (Figure 37).
•
Figure 37: Variable Heating: Curve