A = Fan with cone & shutter

B = Fan with hood & shutter

   CFM

0.025” Static Pressure

0.05” Static Pressure

18” Fans

A

B

A

B

RPM

VOLTS

RPM

VOLTS

RPM

VOLTS

RPM

VOLTS

300

520

128

530

128

660

134

670

135

400

550

129

560

129

670

135

680

136

500

570

130

590

132

680

136

700

137

600

590

132

610

133

710

137

740

139

700

620

133

640

134

730

138

770

140

800

640

134

660

135

740

139

780

141

1000

700

136

730

138

780

141

830

143

1250

760

139

800

141

840

144

890

147

1500

820

143

860

144

890

147

950

150

1750

880

145

950

149

940

149

1000

153

2000

940

148

1020

152

990

152

1060

155

2500

1070

154

1170

161

1110

157

1220

164

3000

1210

162

1360

171

1240

165

1380

172

3500

1380

172

1530

188

1420

175

1570

190

4000

1570

190

1610

200

4200

1650

207

1680

230

24” Fans

1000

490

144

510

145

1250

520

146

530

147

1500

480

141

490

142

540

148

560

150

1750

500

143

520

144

560

150

600

153

2000

530

145

550

147

580

152

630

157

2250

560

148

590

151

610

154

670

160

2500

580

150

620

153

630

157

690

163

2750

610

152

660

156

660

159

720

166

3000

640

155

690

160

680

162

740

168

3500

690

160

760

167

730

167

790

172

4000

750

166

820

172

790

172

860

179

4500

820

172

900

183

850

178

940

191

5000

890

181

990

202

920

187

1020

210

5500

970

195

1060

230

1000

204

6000

1060

227

26” Fans

1250

510

147

520

148

1500

480

142

530

149

550

152

1750

480

142

500

144

540

151

580

154

2000

500

144

520

146

560

153

610

158

2250

520

146

550

149

580

154

640

161

2500

540

148

580

152

590

156

650

162

2750

560

150

610

155

610

158

670

164

3000

580

152

630

157

630

160

690

166

3500

620

156

680

163

670

164

730

171

4000

660

161

730

169

710

168

780

177

4500

700

165

780

176

740

172

830

182

5000

740

170

840

183

780

177

880

189

5500

780

176

880

188

830

182

930

199

6000

830

181

930

194

870

188

970

205

6500

880

188

980

206

920

194

1030

225

7000

940

196

1040

225

970

205

7500

990

208

1020

222

8000

1050

229

Operation

Chapter 4

Содержание Aerotech VX Series

Страница 1: ...1 Munters Corporation July 2020 QM1105r3 Instruction Manual VX Fans Direct Drive Models VX14F1 VX16F1 VX18F1 VX24F1 VX24F3 VX26F1 VX26F3 Aerotech VX Fan Direct Drive 14 26 Fans VX26 VX14 VX24 ...

Страница 2: ... Please read all instructions carefully before beginning installation Warranty For Warranty claims information see the Warranty Claims and Return Policy form QM1021 available from the Munters Corporation office at 1 800 227 2376 or by e mail at aghort info munters com Conditions and Limitations Products and Systems involved in a warranty claim under the Warranty Claims and Return Policy shall have...

Страница 3: ...List 4 1 2 Fan Dimensions 5 2 Installation Instructions 6 8 2 1 Install 6 2 2 PT Style Shutter 7 2 3 PZ Style Shutter 8 3 Electrical Wiring 9 4 Operation 11 5 Maintenance 13 6 Winterizing 14 6 1 Winterizing 14 6 2 Winter Weather Protection 14 7 Troubleshooting 15 8 Exploded View and Parts List 16 17 ...

Страница 4: ... Fans ID Qty Cat No Description A 12 KS2105 14 x 1 5 Lag Screw SS Before beginning installation check the overall condition of the equipment Remove packing materials and examine all components for signs of shipping damage Any shipping damage is the customer s responsibility and should be reported immediately to your freight carrier Fan is shipped complete with all accessories ...

Страница 5: ...C Phase 1 or 3 3 Phase fans only available for VX24 VX26 FAN DIA NO OF BLADES A B C D E F G Dia O D WALL OPENING I D framed 14 7 45 16 12 205 8 173 8 165 8 7 145 8 171 2 W 171 2 H 16 4 43 4 16 251 2 221 4 183 4 51 2 1611 16 221 2 W 221 2 H 18 5 43 4 16 251 2 221 4 183 4 51 2 1811 16 221 2 W 221 2 H 24 4 53 4 20 311 2 281 4 193 4 51 2 2411 16 281 2 W 281 2 H 26 3 51 2 22 33 293 4 181 8 107 16 27 30...

Страница 6: ...he previous page See Figure 1 Wall Opening See Chart on previous page Step 2 Insert fan into framed opening from inside and fasten in place using 8 Lag Screws A Flash and caulk around opening See Figure 2 2x4 Framing Lag Screw A VX Fan Figure 2 OUTSIDE INSIDE Note Outlet of fan comes unguarded it is recommended that a Munters Discharge Cone with Guard a Fan Hood with Guard or a guard by others is ...

Страница 7: ...Z PV Style Shutter Step 3 Insert PZ PV shutter into back of fan See Figure 3A Fasten shutter in place by rotating the side and top shutter clips over the shutter flanges See Figure 3B Installation is now complete proceed to electrical wiring section PZ PV Shutter Figure 3A Figure 3B ...

Страница 8: ... 4 minimum and bottom requires 2 minimum Step 5 Insert PT shutter into back of fan See Figure 5A Fasten shutter in place by rotating the side and top shutter clips over the shutter flanges See Figure 5B Installation is now complete proceed to electrical wiring section 2 Minimum Framing for fan Bottom Wall Opening See Chart on Page 5 Wall Framing 4 Minimum Framing for Fan Top and Sides Wall Framing...

Страница 9: ...be used See Figure 6A See form QM1400 for proper size Three Phase Fans motor overload protection should be provided for each fan A three pole motor starter or slow blow motor fuses must be used See Figure 6B If a frequency drive inverter is used confirm that motors are rated for inverter duty at the voltage used Shielded power cable between frequency drive and each motor is highly recommended Inst...

Страница 10: ...mum operating frequency of 30 Hz 3 Will require three pole contractors with overload protection by others As the power cable exits the back of motor form a drip loop and then run power cable down along leg of motor mount and Zip tie the cable to leg to prevent cable from getting tangled See Figure 7 Then run the cable out the drain hole to the circuit breaker or control panel Continued on next pag...

Страница 11: ... 151 750 151 150 640 142 640 142 760 152 760 152 200 660 143 670 144 780 153 790 153 300 710 145 720 146 820 154 820 154 400 760 148 780 149 860 156 870 156 500 810 151 840 153 910 158 930 160 600 840 153 880 155 950 161 980 162 800 940 158 980 160 1030 164 1070 166 1000 1030 163 1070 165 1120 168 1180 170 1200 1130 168 1210 173 1210 173 1280 177 1600 1370 182 1480 197 1400 186 1500 205 1950 1640 ...

Страница 12: ... 560 150 1750 500 143 520 144 560 150 600 153 2000 530 145 550 147 580 152 630 157 2250 560 148 590 151 610 154 670 160 2500 580 150 620 153 630 157 690 163 2750 610 152 660 156 660 159 720 166 3000 640 155 690 160 680 162 740 168 3500 690 160 760 167 730 167 790 172 4000 750 166 820 172 790 172 860 179 4500 820 172 900 183 850 178 940 191 5000 890 181 990 202 920 187 1020 210 5500 970 195 1060 23...

Страница 13: ...UTTER Carefully clean dust from shutter blades and frame so that shutter opens and closes freely A brush or cloth should be used GUARD Clean any dust or feathers from fan guards using a brush Dirty guards can reduce airflow 3 CHECK FASTENERS For safety all fasteners should be inspected 1 month after initial operation and yearly thereafter Tighten any loose connections 4 INSPECT FAN CONTROL With po...

Страница 14: ... off building roof weather protection must be provided A weather shelter may be constructed to cover the entire fan See Figure 8 or snow guards may be placed on the roof See Figure 9 Building Wall Provide Weather Shelter Over Fans 6 Min Fan with Discharge Cone Figure 8 Note Snow guards are designed to prevent sudden dangerous snow and ice slides when attached to the building roof according to manu...

Страница 15: ... Frequency drive improperly adjusted 1 Motor loose on mount 2 Propeller damaged 3 Motor shaft bent 1 Set to a lower temperature 2 Replace fuse or reset breaker 3 Realign motor in fan housing 4 Repair or replace control 5 Repair or replace motor 1 See Operation Step 2 for adjustment guidelines 2 Unjam and clean shutter 3 Clean guard 1 Sand fan housing to remove high spot 2 Repair or replace motor o...

Страница 16: ... Munters Corporation January 2020 16 QM1105r3 Exploded View 8 ...

Страница 17: ... PVC Coated 1 FH1009 16 18 Fan Motor Mount PVC Coated 1 FH1010 24 Fan Motor Mount PVC Coated 1 FH2526 26 Fan Motor Mount PVC Coated 1 5 FM1010 14 DD Motor HP 1625 RPM 48 Fr 1 ph 115 230V 1 FM1043 16 DD Motor HP 1625 RPM 48 Fr 1 ph 115 230V 1 FM1009 18 DD Motor HP 1625 RPM 48 Fr 1 ph 115 230V 1 FM1108 24 26 DD Motor HP 1075 RPM 48 Fr 1 ph 115 230V 1 FM1074 24 26 DD Motor HP 1140 RPM 48 Fr 3 ph 230 ...

Страница 18: ...235 Italy Munters Italy S p A Chiusavecchia Phone 39 0183 52 11 Japan Munters K K Phone 81 3 5970 0021 Korea Munters Korea Co Ltd Phone 82 2 761 8701 Mexico Munters Mexico Phone 52 818 262 54 00 Russia Munters AB Phone 7 812 448 5740 Singapore Munters Pte Ltd Phone 65 744 6828 South Africa and Sub Sahara Countries Munters Pty Ltd Phone 27 11 997 2000 Spain Munters Spain S A Phone 34 91 640 09 02 S...

Отзывы: