Munters Aerotech VX Series Скачать руководство пользователя страница 11

11

© Munters Corporation, July 2020

QM1105r3

Operation

4.

INITIAL  START-UP: 

  With  electrical  power  off,  verify  that  the  fan  propeller  turns  freely 

and that all fasteners are secure. Turn on electrical power and confirm that the fan 
operates smoothly.

ADJUSTMENTS:

  Set the fan control to the temperature shown on your ventilations system 

drawing, or to a value which will provide the desired environmental conditions.

Single Phase Fans:

  When variable speed controls are used, the fan's idle speed will need 

to be set to the recommended minimum airflow rate. Refer to the procedures included with 
each control. The table below provides airflow rates at various propeller speeds for fans 
wired for 240 VAC.

A = Fan with cone & shutter

B = Fan with hood & shutter

   CFM

0.025” Static Pressure

0.05” Static Pressure

14” Fans

A

B

A

B

RPM

VOLTS

RPM

VOLTS

RPM

VOLTS

RPM

VOLTS

100

620

141

620

141

740

150

740

150

120

630

142

630

142

750

151

750

151

150

640

142

640

142

760

152

760

152

200

660

143

670

144

780

153

790

153

300

710

145

720

146

820

154

820

154

400

760

148

780

149

860

156

870

156

500

810

151

840

153

910

158

930

160

600

840

153

880

155

950

161

980

162

800

940

158

980

160

1030

164

1070

166

1000

1030

163

1070

165

1120

168

1180

170

1200

1130

168

1210

173

1210

173

1280

177

1600

1370

182

1480

197

1400

186

1500

205

1950

1640

218

1630

230

16” Fans

150

590

96

600

96

700

103

720

104

175

600

96

610

97

710

103

730

104

200

610

97

620

98

720

104

740

105

300

640

98

660

99

740

105

760

106

400

670

100

700

102

770

106

780

107

500

700

102

740

104

800

108

810

108

600

730

103

780

106

830

109

840

110

800

790

107

860

111

880

112

920

114

1000

850

110

940

115

940

115

1000

117

1250

930

114

1020

119

1020

118

1100

124

1500

1020

119

1110

124

1090

123

1200

128

1750

1100

123

1220

129

1180

127

1350

136

2000

1190

127

1330

134

1260

131

1460

142

2500

1380

136

1600

160

1430

140

1630

172

3000

1600

160

1640

173

3170

1680

190

1720

230

WARNING

!

Disconnect Power 

before servicing

WARNING

!

Moving parts, disconnect 

power before servicing.

4.1 Operation

Содержание Aerotech VX Series

Страница 1: ...1 Munters Corporation July 2020 QM1105r3 Instruction Manual VX Fans Direct Drive Models VX14F1 VX16F1 VX18F1 VX24F1 VX24F3 VX26F1 VX26F3 Aerotech VX Fan Direct Drive 14 26 Fans VX26 VX14 VX24 ...

Страница 2: ... Please read all instructions carefully before beginning installation Warranty For Warranty claims information see the Warranty Claims and Return Policy form QM1021 available from the Munters Corporation office at 1 800 227 2376 or by e mail at aghort info munters com Conditions and Limitations Products and Systems involved in a warranty claim under the Warranty Claims and Return Policy shall have...

Страница 3: ...List 4 1 2 Fan Dimensions 5 2 Installation Instructions 6 8 2 1 Install 6 2 2 PT Style Shutter 7 2 3 PZ Style Shutter 8 3 Electrical Wiring 9 4 Operation 11 5 Maintenance 13 6 Winterizing 14 6 1 Winterizing 14 6 2 Winter Weather Protection 14 7 Troubleshooting 15 8 Exploded View and Parts List 16 17 ...

Страница 4: ... Fans ID Qty Cat No Description A 12 KS2105 14 x 1 5 Lag Screw SS Before beginning installation check the overall condition of the equipment Remove packing materials and examine all components for signs of shipping damage Any shipping damage is the customer s responsibility and should be reported immediately to your freight carrier Fan is shipped complete with all accessories ...

Страница 5: ...C Phase 1 or 3 3 Phase fans only available for VX24 VX26 FAN DIA NO OF BLADES A B C D E F G Dia O D WALL OPENING I D framed 14 7 45 16 12 205 8 173 8 165 8 7 145 8 171 2 W 171 2 H 16 4 43 4 16 251 2 221 4 183 4 51 2 1611 16 221 2 W 221 2 H 18 5 43 4 16 251 2 221 4 183 4 51 2 1811 16 221 2 W 221 2 H 24 4 53 4 20 311 2 281 4 193 4 51 2 2411 16 281 2 W 281 2 H 26 3 51 2 22 33 293 4 181 8 107 16 27 30...

Страница 6: ...he previous page See Figure 1 Wall Opening See Chart on previous page Step 2 Insert fan into framed opening from inside and fasten in place using 8 Lag Screws A Flash and caulk around opening See Figure 2 2x4 Framing Lag Screw A VX Fan Figure 2 OUTSIDE INSIDE Note Outlet of fan comes unguarded it is recommended that a Munters Discharge Cone with Guard a Fan Hood with Guard or a guard by others is ...

Страница 7: ...Z PV Style Shutter Step 3 Insert PZ PV shutter into back of fan See Figure 3A Fasten shutter in place by rotating the side and top shutter clips over the shutter flanges See Figure 3B Installation is now complete proceed to electrical wiring section PZ PV Shutter Figure 3A Figure 3B ...

Страница 8: ... 4 minimum and bottom requires 2 minimum Step 5 Insert PT shutter into back of fan See Figure 5A Fasten shutter in place by rotating the side and top shutter clips over the shutter flanges See Figure 5B Installation is now complete proceed to electrical wiring section 2 Minimum Framing for fan Bottom Wall Opening See Chart on Page 5 Wall Framing 4 Minimum Framing for Fan Top and Sides Wall Framing...

Страница 9: ...be used See Figure 6A See form QM1400 for proper size Three Phase Fans motor overload protection should be provided for each fan A three pole motor starter or slow blow motor fuses must be used See Figure 6B If a frequency drive inverter is used confirm that motors are rated for inverter duty at the voltage used Shielded power cable between frequency drive and each motor is highly recommended Inst...

Страница 10: ...mum operating frequency of 30 Hz 3 Will require three pole contractors with overload protection by others As the power cable exits the back of motor form a drip loop and then run power cable down along leg of motor mount and Zip tie the cable to leg to prevent cable from getting tangled See Figure 7 Then run the cable out the drain hole to the circuit breaker or control panel Continued on next pag...

Страница 11: ... 151 750 151 150 640 142 640 142 760 152 760 152 200 660 143 670 144 780 153 790 153 300 710 145 720 146 820 154 820 154 400 760 148 780 149 860 156 870 156 500 810 151 840 153 910 158 930 160 600 840 153 880 155 950 161 980 162 800 940 158 980 160 1030 164 1070 166 1000 1030 163 1070 165 1120 168 1180 170 1200 1130 168 1210 173 1210 173 1280 177 1600 1370 182 1480 197 1400 186 1500 205 1950 1640 ...

Страница 12: ... 560 150 1750 500 143 520 144 560 150 600 153 2000 530 145 550 147 580 152 630 157 2250 560 148 590 151 610 154 670 160 2500 580 150 620 153 630 157 690 163 2750 610 152 660 156 660 159 720 166 3000 640 155 690 160 680 162 740 168 3500 690 160 760 167 730 167 790 172 4000 750 166 820 172 790 172 860 179 4500 820 172 900 183 850 178 940 191 5000 890 181 990 202 920 187 1020 210 5500 970 195 1060 23...

Страница 13: ...UTTER Carefully clean dust from shutter blades and frame so that shutter opens and closes freely A brush or cloth should be used GUARD Clean any dust or feathers from fan guards using a brush Dirty guards can reduce airflow 3 CHECK FASTENERS For safety all fasteners should be inspected 1 month after initial operation and yearly thereafter Tighten any loose connections 4 INSPECT FAN CONTROL With po...

Страница 14: ... off building roof weather protection must be provided A weather shelter may be constructed to cover the entire fan See Figure 8 or snow guards may be placed on the roof See Figure 9 Building Wall Provide Weather Shelter Over Fans 6 Min Fan with Discharge Cone Figure 8 Note Snow guards are designed to prevent sudden dangerous snow and ice slides when attached to the building roof according to manu...

Страница 15: ... Frequency drive improperly adjusted 1 Motor loose on mount 2 Propeller damaged 3 Motor shaft bent 1 Set to a lower temperature 2 Replace fuse or reset breaker 3 Realign motor in fan housing 4 Repair or replace control 5 Repair or replace motor 1 See Operation Step 2 for adjustment guidelines 2 Unjam and clean shutter 3 Clean guard 1 Sand fan housing to remove high spot 2 Repair or replace motor o...

Страница 16: ... Munters Corporation January 2020 16 QM1105r3 Exploded View 8 ...

Страница 17: ... PVC Coated 1 FH1009 16 18 Fan Motor Mount PVC Coated 1 FH1010 24 Fan Motor Mount PVC Coated 1 FH2526 26 Fan Motor Mount PVC Coated 1 5 FM1010 14 DD Motor HP 1625 RPM 48 Fr 1 ph 115 230V 1 FM1043 16 DD Motor HP 1625 RPM 48 Fr 1 ph 115 230V 1 FM1009 18 DD Motor HP 1625 RPM 48 Fr 1 ph 115 230V 1 FM1108 24 26 DD Motor HP 1075 RPM 48 Fr 1 ph 115 230V 1 FM1074 24 26 DD Motor HP 1140 RPM 48 Fr 3 ph 230 ...

Страница 18: ...235 Italy Munters Italy S p A Chiusavecchia Phone 39 0183 52 11 Japan Munters K K Phone 81 3 5970 0021 Korea Munters Korea Co Ltd Phone 82 2 761 8701 Mexico Munters Mexico Phone 52 818 262 54 00 Russia Munters AB Phone 7 812 448 5740 Singapore Munters Pte Ltd Phone 65 744 6828 South Africa and Sub Sahara Countries Munters Pty Ltd Phone 27 11 997 2000 Spain Munters Spain S A Phone 34 91 640 09 02 S...

Отзывы: