background image

Symptom

Possible causes

Troubleshooting steps

The unit does not start

Wait for the power to come back on. 

The unit is powered off.

The power switch fuse may have burned out.

Replace the fuse.

 

Replace the batteries.

The temperature setting is not correct.

 

 

 

 

Low cooling effect

Doors or windows are open.

Close the doors and windows.

 

The unit's air filter is dirty.

Clean the filter.

 

 

 

 

 

 

Low heating effect

 

Close doors and windows.

 

14.2  Unit Troubleshooting

 

   

 

 

 

   

 

Air flows normally but 

doesn’t cool

The unit starts or 

stops frequently

Power on the unit. This indoor unit forms part of an air 
conditioning system that has multiple indoor units that 
are all connected. The indoor units cannot be powered 
on individually - they are all connected to one, single 
power switch. Ask a professional technician for advice 
regarding how to safely power on the units.

The  room  contains  many  heat  sources such 

as computers or refrigerators.

 

 

 

Turn off some of the computers during the hottest part 

of the day.

 

 

   

 

 

   

 

 

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

The outside temperature is unusually high.

19

A

 

power

 

cut

 

has

 

occurred

 

(the

 

power

 

of

 

the

 

premises has been cut-off).

The

 

remote

 

control

 

batteries

 

are dead.

Arrange

 

for

 

a

 

professional

 

technician to

 

check

 

out the following:

 

Too

 

much

 

or

 

too

 

little

 

refrigerant.

 

No gas

 

in the

 

refrigerant

 

circuit.

 

The outdoor

 

unit

 

compressors

 

have

 

malfunctioned.

 

The power

 

supply

 

voltage

 

is

 

too

 

high or

 

too

 

low.

 

There

 

is

 

a blockage

 

in the piping

 

system.

Sunlight

 

is

 

shining directly

 

onto the unit.

Close

 

shutters/blinds

 

to

 

shield

 

the

 

unit from

 

direct sunlight.

The  cooling  capacity  of  the  system  will  decrease  
as  the outdoor temperature rises, and if the  
local climatic conditions are not considered 
when selecting the outdoor unit of the system, the 
system may not be able to provide sufficient cooling.

Doors

 

or

 

windows

 

are not

 

completely closed.

Arrange

 

for

 

a

 

professional

 

technician to

 

check out

 

the following:

A

 

refrigerant

 

leak

 

has

 

occurred.

Set the desired

 

temperature on the remote

 

control.

Arrange for a professional

 

air

 

conditioning technician

 

to

 

check out

 

the following:

 

The unit's

 

heat

 

exchanger

 

is

 

dirty.

 

The unit's

 

air

 

inlet or

 

outlet

 

is

 

obstructed.

 

A

 

refrigerant

 

leak

 

has

 

occurred.

Содержание MVD DC2 Series

Страница 1: ...CL23460 CL23476 English Floor Standing MVD DC2 Installation and User Manual www mundoclima com MVD DC2...

Страница 2: ...al shocks and fire Install at a strong and firm location which is able to withstand the equipment s weight If the strength is not enough or installation is not properly done the set will drop and caus...

Страница 3: ...to install an earth leakage breaker may result in electric shocks Connect the outdoor unit wires then connect the indoor unit wires You are not allow to connect the air conditioner with the power sou...

Страница 4: ...ts Mounting Screw 4 All the illustrations of this manual are for explanatory purpose only The appearance functions and physical objects may differ please refer to the actual product Air outlet Air inl...

Страница 5: ...r discharge piping and plastic parts 4 2 Choosing an Installation Site 1 Choose a site that fully complies with the following conditions and user requirements to install the air conditioning unit Well...

Страница 6: ...ion surroundings WOOD STRUCTURE Put the square timber horizontally on the roof beam and then install the hanging bolts Timber on beam Hanging bolts Embedding bolts Sliding insert Blade shape insert St...

Страница 7: ...6 5 Dimensions Liquid side E Gas side F BOLT HOLES A B 200 128 C 47 D Refrigerant pipe connection point Refrigerant pipe connection point Fig 4 11 Covered equipment...

Страница 8: ...12 7 4 5 1240 495 984 375 6 4 12 7 7 1 1360 591 1104 391 9 5 15 9 5 6 1360 591 1104 391 6 4 12 7 G H 915 470 915 470 915 470 1133 470 1253 566 1253 566 200 80 H G C D 8 0 1360 591 1104 391 9 5 15 9 1...

Страница 9: ...ture in during installation 4 5 1 Connecting Pipes Procedure 5 1 1 Measure the necessary length of the connecting pipe and follow the instructions 1 Connect the indoor unit first and then the outdoor...

Страница 10: ...Do not damage the piping 4 6 4 Piping Installation For the installation of the outdoor unit s refrigerant pipe please refer to the installation manual provided with the outdoor unit All gas and liqui...

Страница 11: ...sure all the connections in the piping system are properly sealed to prevent water leaks 5 2 Water Discharge Test Before testing make sure that the water discharge pipe is smooth and check if each con...

Страница 12: ...ng with the power on Do not bind the refrigerant piping power cords and communication wiring together When the power cord and communication wiring are parallel the distance between the two lines must...

Страница 13: ...terial to seal and protect the perforated wires Poor sealing may lead to condensation and entry of small animals and insects that may cause short circuits in parts of the electrical system causing the...

Страница 14: ...Capacity HP number has not been set 8 Test Run 8 1 Precautions Before Test Run Indoor and outdoor units are properly installed Piping and wiring are correct No refrigerant piping system leaks Smooth...

Страница 15: ...ked by dirt or dust water leaks may occur when the unit is Do not allow this unit or its remote control to come into contact Do not touch the unit or its remote control with wet hands as doing so can...

Страница 16: ...o not play with the appliance This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if...

Страница 17: ...l receiver Operation lamp MANUAL OPERATION TIMER DEF FAN ALARM Anti cold air defrosting indicator Check regularly Figure 11 1 Please note how you can best save energy and achieve the best cooling heat...

Страница 18: ...that outlet air is either cooler or hotter than the set room temperature Avoid direct exposure to outlet air as it may be too cool or hot 2 Take out the air filter 3 Clean the air filter During the op...

Страница 19: ...or up to 12 minutes under some operating conditions If the OPERATION LED on the unit s panel is lighting the system is working normally and the unit will start after the intentional delay is complete...

Страница 20: ...e day The outside temperature is unusually high 19 A power cut has occurred the power of the premises has been cut off The remote control batteries are dead Arrange for a professional technician to ch...

Страница 21: ...onditioner operation will stop up to the set time 20 14 3 Remote Control Troubleshooting Warning Certain troubleshooting steps that a professional technician may perform when investigating an error ar...

Страница 22: ...tioned Damaged main PCB E6 E7 Indoor EEV coil error Eb Outdoor unit error Ed MS box PCB malfunction Emergency stop A0 MS self check failure U4 MS failure F8 IDU address repeat Error code display F7 an...

Страница 23: ...SAT 34 93 652 53 57 www mundoclima com C N POLES 249 P1 08013 BARCELONA SPAIN 34 93 446 27 80...

Отзывы: