background image

9

R0.4~0.8

A

45°±  2

90°± 4

Flared opening

Φ

6.35

14.2-17.2N·m

8.3-8.7mm

Φ

9.53

32.7-39.9N·m

12-12.4mm

Φ

12.7

49.5-60.3N·m

15.4-15.8mm

Φ

15.9

61.8-75.4N·m

18.6-19mm

Φ

19.1

97.2-118.6N·m

22.9-23.3mm

1 Copper piping
2

 

 

3 Nitrogen connection
4 Hand valve
5

 

6 Nitrogen

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

 

 

 

   

 

 

 

 
 

 

 

 

 

 

 

 

 

   

 

 

 

   

 

 

   

 

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

 

   

   

   

 

   

 

 

 

 

 

 

 

 

 

   

 

 

 

   

 

 

     

 

 

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

   

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

 

   

 

 

 

 

 

   

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

 

 

 

   

 

 

 

   

 

 

   

 

 

 

   

 

 

   

   

 

 

   

 

 

 

 

 

 

   

 

 

   

 

 

   

   

 

 

 

   

     

 

 

 

   

 

 

 

 

 

 

 

 

 

   

   

 

 

 

 

   

       

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

   

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

   

   

 

 

 

 

   

   

 

 

   

 

   

 

 

 

 

 

 

 

   

 

   

 

Unit 

body

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

   

 

   

 

 

 

Figure 4-16

External

diameter (mm)

Tightening torque

 

 

 

   

   

 

 

 

 

 

   

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

   

 

 

 

 

 

 

     

 

     

   

 

 

   

   

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

   

 

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

Figure 4-18

 

   

 

 

   

 

 

   

 

 

    

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

   

 

   

 

 

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

Flared opening

diameter (A)

 

 

 

   

 

   

 

 

   

 

   

 
       
  

          

           

 

 

          

 

           

 

 

          

 

          

 

            

 

           

 

 

              

 

         

 

           

 

 

            

 

            

 

             

 

 

           

 

            

 

           

             

 

           

 

           

 

            

 

        

             

 

             

 

           

 

           

 

 
       
  

         

 

            

 

 

          

 

           

 

 

         

 

          

 

            

 

          

 

  

              

 

         

 

            

 

          

 

 

            

 

        

 

 

 

           

 

            

 

           

             

 

           

 

           

 

            

 

        

             

 

             

 

           

 

           

 

 
       
  

         

 

            

 

 

          

 

           

 

 

         

 

          

 

            

 

          

 

  

              

 

         

 

            

         

  

           

        

 

            

 

           

           

         

 

 

        

   

 

         

   

 

       

 

             

 

             

 

           

 

           

 

 
       
  

         

 

            

 

 

          

 

           

 

 

         

 

          

 

            

 

          

 

  

              

 

         

 

            

         

  

           

        

 

 

 

            

 

          

 

          

 

        

 

         

 

           

 

          

 

 

           

 

 

            

 

 

           

 

          

 

 

            

 

           

Caution

 

Apply

 

the

 

proper

 

tightening

 

torque

 

according

 

to

 

the 

installation

 

conditions.

 

Excessive

 

torque

 

may

 

damage

 

the

 

socket 

cap

 

and little torque will not tighten

 

the

 

cap

 

sufficiently,

leading to leaks.

            

         

 

        
            
            

 

  
             
  
             
  

Figure 4-17

Precautions when welding refrigerant pipes

 

Before

 

welding the

 

refrigerant

 

pipes, please

 

fill

 

the pipes

 

with

 

nitrogen

  

to exhaust

 

the

 

air

 

in

 

the

 

pipes.

 

If

 

no

 

nitrogen

 

is

 

filled

 

during the

 

welding

  

process,

 

a

 

large amount

 

of

 

oxide

 

film

 

will

 

form

 

inside

 

the

 

pipes,

 

which

  

may

 

cause

 

the

 

air conditioning system to malfunction.

 

Welding

 

can

 

be

 

carried

 

out

 

on

 

the

 

refrigerant

 

pipes

 

after

 

the

 

nitrogen

 

gas

  

has been replaced or refilled.

 

When

 

the

 

pipe

 

is

 

filled

 

with

 

nitrogen

 

during the

 

welding process,

 

the

 

nitrogen

 

must

 

be reduced to 0.02 MPa via the pressure release valve. 

See Figure 4-18.

4.6

 

Refrigerant Piping Installation

4.6.1

 

Length

 

and

 

Height

 

Difference

 

Requirements

 

for

 

Piping

  

Connections to the Indoor and Outdoor Units

The

 

length

 

and

 

height

 

difference

 

requirements

 

for

 

the

 

refrigerant

 

piping 

vary

 

for

 

different

 

indoor

 

and

 

outdoor

 

units.

 

Refer

 

to

 

the

 

installation

 

manual

 

of 

the outdoor unit.

4.6.2

 

Piping Material and Size

1. Piping material: Copper pipes for air handling.
2. Piping

 

size:

 

Choose

 

and

 

purchase

 

copper

 

pipes

 

that

 

correspond

 

to

 

the 

length

 

and

 

size

 

calculated

 

for

 

the

 

selected

 

model

 

in

 

the

 

installation

 

manual 

of the outdoor unit and your actual project requirements.

4.6.3

 

Piping Layout

1. Seal

 

the

 

two

 

piping ends

 

properly

 

before

 

connecting

 

the

 

indoor

 

and 

outdoor

 

piping.

 

Once

 

unsealed,

 

connect

 

the

 

piping

 

of

 

the

 

indoor

 

and 

outdoor

 

units

 

as

 

quickly

 

as

 

possible

 

to

 

prevent

 

dust

 

or

 

other

 

debris

 

from 

entering

 

the

 

piping

 

system

 

through

 

the

 

unsealed

 

ends,

 

as

 

this

 

may 

cause

 

the

 

system to malfunction.

2. If

 

the

 

pipe

 

needs

 

to

 

go

 

through

 

walls,

 

drill

 

the

 

opening

 

in

 

the

 

wall

 

and 

place accessories like casings and covers properly on the opening.

3. Place

 

the

 

refrigerant

 

connecting

 

piping

 

and

 

the

 

communication

 

wiring

 

for 

the

 

indoor

 

and

 

outdoor

 

units

 

together,

 

bundle

 

them

 

tightly

 

to

 

make

 

sure

 

air

does

 

not

 

enter

 

and

 

does not produce water condensation.

4. Insert

 

the

 

bundled

 

piping

 

and

 

wiring

 

from

 

outside

 

the

 

room

 

through

 

the

wall

 

opening.

 

Be

 

careful

 

when

 

laying

 

out

 

the

 

piping.

Do not damage the piping.

4.6.4

 

Piping Installation

For the installation of the outdoor unit's

 

refrigerant pipe, please refer to the 

installation manual provided with the outdoor unit.
All

 

gas

 

and

 

liquid

 

piping

 

must

 

be

 

properly

 

insulated;

 

otherwise,

 

this

 

may

 

cause 

water

 

to

 

leak.

 

Use

 

heat

 

insulating

 

materials

 

that

 

can

 

withstand

 

high 

temperatures

 

above

 

120°C

 

to

 

insulate

 

the

 

gas

 

pipes.

 

In

 

addition,

 

the 

refrigerant piping insulation

 

should

 

be

 

reinforced

 

(20

 

mm

 

or

 

thicker)

 

in 

situations

 

where

 

there

 

is

 

high

 

temperature

 

and/or

 

high

 

humidity

 

(when 

sections

 

of

 

the refrigerant

 

piping

 

is

 

higher

 

than

 

30°C

 

or

 

when

 

the

 

humidity 

exceeds

 

RH 80%).

 

Otherwise,

 

the

 

surface

 

of

 

the

 

heat

 

insulating

 

material

 

may 

be

 

exposed.

Before

 

the

 

works

 

are

 

carried

 

out,

 

check if

 

the

 

refrigerant

 

is the

 

R410A.

If

 

the

 

wrong refrigerant is used, the unit may malfunction.

Other

 

than

 

the

 

specified

 

refrigerant,

 

do

 

not

 

let

 

air

 

or

 

other

 

gases

enter

 

the

 

refrigeration circuit.

If

 

the

 

refrigerant

 

leaks

 

during

 

installation,

 

make

 

sure

 

you

 

fully

 

ventilate

the

 

room.

Use

 

two

 

wrenches

 

when

 

installing

 

or

 

dismantling

 

the

 

piping,

 

a

common

 

wrench and a torque wrench. See Figure 4-15.

Normal wrench
Torque wrench
Pipe socket cap

Pipe fittings

 

Figure 4-15

Slot

 

the

 

refrigerant

 

piping

 

into

 

the

 

brass

 

nut

 

(accessory

 

14),

 

and

 

expand

 

the 

pipe

 

socket.

 

Refer

 

to

 

the

 

following

 

table

 

for

 

the

 

pipe

 

socket size

 

and

the proper tightening torque.

Before

 

the

 

socket

 

cap

 

is

 

installed

 

on

 

the

 

pipe

 

socket,

 

apply

 

some

 

oil 

oil

 

onto

 

the

 

socket

 

(both

 

inside

 

and

 

outside),  afterwards

 

rotate

 

it  

three or four

 

times before tightening the cap. See Figure 4-17.

Apply oil

      

             

 

            

 

           

 

Pressure release

 

valve

Section

 

being

 

welded

4.6.5

 

Air Tightness Test

Carry

 

out

 

the

 

air

 

tightness

 

test

 

on

 

the

 

system

 

according

 

to

 

the

 

instructions

 

in

 

the 

outdoor unit installation manual.

Caution

 

The

 

Air

 

Tightness

 

Test

 

helps

 

ensure

 

that

 

the

 

air

 

and

 

liquid

 

shut off

  

valves of the outdoor unit are all closed (keep factory settings).

4.6.6

 

Heat

 

Insulation

 

for

 

Indoor Unit Gas-Liquid

 

Piping 

Connections

Heat

 

insulation

 

is

 

carried

 

out

 

on

 

the

 

gas

 

and liquid  indoor unit piping 

sides, respectively.

a. The

 

piping

 

on

 

the

 

gas

 

side

 

must

 

use

 

heat

 

insulation

 

material

 

that

 

can 

withstand temperatures of 120°C and more.

b. For

 

the

 

indoor unit piping

 

connections,

 

use

 

the copper pipes

 

insulation

 

sleeve to carry out the insulation and close all gaps.

Facing upwards

Piping side

Refrigerant pipe 

insulation

Figure 4-19

4.6.7

 

Vacuum

Create

 

a

 

vacuum

 

in

 

the

 

system

 

according

 

to

 

the

 

instructions

 

in

 

the outdoor 

unit

 

installation manual.

Caution

 

For

 

the

 

vacuum,

 

make

 

sure

 

that

 

the outdoor unit

 

air

 

and

 

liquid 

cut-off

 

valves are all closed (keep factory settings).

4.6.8

 

Refrigerant

Charge

 

the

 

system

 

with

 

refrigerant

 

according

 

to

 

the

 

instructions

 

in

 

the 

outdoor unit installation manual.

Содержание MVD DC2 Series

Страница 1: ...CL23460 CL23476 English Floor Standing MVD DC2 Installation and User Manual www mundoclima com MVD DC2...

Страница 2: ...al shocks and fire Install at a strong and firm location which is able to withstand the equipment s weight If the strength is not enough or installation is not properly done the set will drop and caus...

Страница 3: ...to install an earth leakage breaker may result in electric shocks Connect the outdoor unit wires then connect the indoor unit wires You are not allow to connect the air conditioner with the power sou...

Страница 4: ...ts Mounting Screw 4 All the illustrations of this manual are for explanatory purpose only The appearance functions and physical objects may differ please refer to the actual product Air outlet Air inl...

Страница 5: ...r discharge piping and plastic parts 4 2 Choosing an Installation Site 1 Choose a site that fully complies with the following conditions and user requirements to install the air conditioning unit Well...

Страница 6: ...ion surroundings WOOD STRUCTURE Put the square timber horizontally on the roof beam and then install the hanging bolts Timber on beam Hanging bolts Embedding bolts Sliding insert Blade shape insert St...

Страница 7: ...6 5 Dimensions Liquid side E Gas side F BOLT HOLES A B 200 128 C 47 D Refrigerant pipe connection point Refrigerant pipe connection point Fig 4 11 Covered equipment...

Страница 8: ...12 7 4 5 1240 495 984 375 6 4 12 7 7 1 1360 591 1104 391 9 5 15 9 5 6 1360 591 1104 391 6 4 12 7 G H 915 470 915 470 915 470 1133 470 1253 566 1253 566 200 80 H G C D 8 0 1360 591 1104 391 9 5 15 9 1...

Страница 9: ...ture in during installation 4 5 1 Connecting Pipes Procedure 5 1 1 Measure the necessary length of the connecting pipe and follow the instructions 1 Connect the indoor unit first and then the outdoor...

Страница 10: ...Do not damage the piping 4 6 4 Piping Installation For the installation of the outdoor unit s refrigerant pipe please refer to the installation manual provided with the outdoor unit All gas and liqui...

Страница 11: ...sure all the connections in the piping system are properly sealed to prevent water leaks 5 2 Water Discharge Test Before testing make sure that the water discharge pipe is smooth and check if each con...

Страница 12: ...ng with the power on Do not bind the refrigerant piping power cords and communication wiring together When the power cord and communication wiring are parallel the distance between the two lines must...

Страница 13: ...terial to seal and protect the perforated wires Poor sealing may lead to condensation and entry of small animals and insects that may cause short circuits in parts of the electrical system causing the...

Страница 14: ...Capacity HP number has not been set 8 Test Run 8 1 Precautions Before Test Run Indoor and outdoor units are properly installed Piping and wiring are correct No refrigerant piping system leaks Smooth...

Страница 15: ...ked by dirt or dust water leaks may occur when the unit is Do not allow this unit or its remote control to come into contact Do not touch the unit or its remote control with wet hands as doing so can...

Страница 16: ...o not play with the appliance This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if...

Страница 17: ...l receiver Operation lamp MANUAL OPERATION TIMER DEF FAN ALARM Anti cold air defrosting indicator Check regularly Figure 11 1 Please note how you can best save energy and achieve the best cooling heat...

Страница 18: ...that outlet air is either cooler or hotter than the set room temperature Avoid direct exposure to outlet air as it may be too cool or hot 2 Take out the air filter 3 Clean the air filter During the op...

Страница 19: ...or up to 12 minutes under some operating conditions If the OPERATION LED on the unit s panel is lighting the system is working normally and the unit will start after the intentional delay is complete...

Страница 20: ...e day The outside temperature is unusually high 19 A power cut has occurred the power of the premises has been cut off The remote control batteries are dead Arrange for a professional technician to ch...

Страница 21: ...onditioner operation will stop up to the set time 20 14 3 Remote Control Troubleshooting Warning Certain troubleshooting steps that a professional technician may perform when investigating an error ar...

Страница 22: ...tioned Damaged main PCB E6 E7 Indoor EEV coil error Eb Outdoor unit error Ed MS box PCB malfunction Emergency stop A0 MS self check failure U4 MS failure F8 IDU address repeat Error code display F7 an...

Страница 23: ...SAT 34 93 652 53 57 www mundoclima com C N POLES 249 P1 08013 BARCELONA SPAIN 34 93 446 27 80...

Отзывы: