backflow while shutdown would leads to overflow (refer to fig.12.12). 

 

Base on the actual requirement to bend piping, and use connective assembly of water outlet in terminal box 

for pipe layout. 

Caution: 

The joints in drain system must be sealed to avoid water leakage. 

 

The  height  from  floor  to  the  end  of  drainpipe  or  the  bottom  of  drain  slot  must  more  than  50  mm.  Don’t 

immerse the end of drainpipe or the bottom of drain slot into water. When drain condensate liquid to raceway, 

please bend the drainpipe to a U-sharped hydroseal for avoiding stench transmitted by drainpipe to indoor. 

Note: 

All the pictures in this manual are for explanation purpose only. They may be slightly different from the 

air conditioner you purchased (depend on model).The actual shape shall prevail. 

 

 

fig. 12.11

 

 

fig. 12.12

 

Drainage test

 

 

Check whether the drainpipe is unhindered 

 

New built house should have this test done before paving the ceiling. 

1.  Remove the test cover, and stow water of about 2000ml to the water receiver through the stow tube. 

2.  Turn on the power, and operate the air conditioner under the "COOLING" mode. Listen to the sound of the 

drain  pump.  Check  whether  the  water  is  discharged  well  (a  lag  of  1min  is  allowed  before  discharging, 

according to the length of the drain pipe), and check whether water leaks from the joints. 

Caution: 

If there is any malfunction, please resolve it immediately.

 

3.  Stop the air conditioner for three minutes, check if everything is ok. If the drain hose is located unreasonable, 

water overflow will cause the Alarm indicator lamp flashing (For both cooling and heating type or cooling only 

type), even the water leak out from the water receiver. 

4.  Check  the  drain  pump  whether  drain  water immediately  when alarm  sound for  the  high  water  lever.  If  the 

water lever can't come down below to the limited water lever, the air conditioner will stop. Restart it until turn 

off the power and drain off all the water. 

5.  Turn off the power, drain the water away. 

 

The  drain  plug  is  used  to  empty  the  water-receiver  for  maintenance  of  the  air  conditioner.  Please  stuff  it 

imposition at all times during operation to avoid leakage.

 

 

32

 

 

 

  Four-way Cassette DC Fan Coil Unit  

 

Содержание MUCS-20-W9

Страница 1: ...www mundoclima com Cassette 4 Ways FCU DC Service manual English CL04433 to CL04435 MUCS W9...

Страница 2: ...nal Appearance 3 2 Features 3 3 Product lineup 4 4 Accessories 5 5 Specifications 6 6 Capacity Table 7 7 Sound Levels 26 8 Dimension 26 9 Service Spaces 30 10 Wiring Diagrams 31 11 Troubleshooting 32...

Страница 3: ...high efficiency Wireless remote control with LED display wired control is optional Safety grill for safety maintenance Built in drain water pump with 750mm pumping head Optional extended drainage pan...

Страница 4: ...durable motor The motor bearing can operate 80 000 hours continuously and easy for maintenance Low noise Advanced 3 D spiral fan design reduces air resistance and operating sound The motor bearing wi...

Страница 5: ...t M6 4 Tubing Fittings 2 Soundproof insulation sheath Drainpipe Fittings 1 Out let pipe 1 Out let pipe sheath 1 Out let pipe clasp 5 Tightening band Remote controller Its Frame 1 Remote controller R05...

Страница 6: ...7 Panel Net dimensions W H D mm 950 45 950 950 45 950 Packing size W H D mm 1035 90 1035 1035 90 1035 Net weight kg 6 6 Gross weight kg 9 9 Body Net dimensions W H D mm 840 300 840 840 300 840 Packin...

Страница 7: ...1 21 27 27 19 6 93 3 06 1 49 38 84 6 89 3 61 1 48 38 51 6 86 4 15 1 47 38 18 6 82 4 69 1 47 37 86 6 79 5 22 1 46 37 54 20 7 89 3 65 1 7 48 61 7 86 4 19 1 69 48 21 7 82 4 73 1 68 47 82 7 78 5 27 1 67...

Страница 8: ...27 3 24 3 24 0 7 10 18 3 85 3 85 0 83 13 63 20 3 38 2 15 1 1 10 64 3 34 2 69 0 72 10 71 3 4 3 09 1 1 10 98 3 88 3 79 0 83 13 77 5 15 0 92 0 92 0 16 0 86 1 38 1 38 0 24 1 29 2 27 2 27 0 39 2 65 2 94 2...

Страница 9: ...22 85 6 7 6 31 1 44 24 82 7 35 7 35 1 58 29 07 19 8 98 3 97 1 93 40 84 8 93 4 69 1 92 40 48 8 89 5 4 1 91 40 12 8 84 6 11 1 9 39 77 8 8 6 8 1 89 39 42 20 10 25 4 74 2 2 51 23 10 2 5 46 2 19 50 8 10 1...

Страница 10: ...3 3 0 73 7 21 4 21 4 21 0 91 10 77 5 02 5 02 1 08 14 49 20 4 17 2 72 1 44 10 2 4 21 3 44 0 91 10 74 4 38 4 03 0 94 11 51 5 03 4 95 1 08 14 57 5 15 1 22 1 22 0 21 1 03 1 82 1 82 0 31 1 54 2 63 2 63 0 4...

Страница 11: ...1 95 37 53 9 43 8 74 2 02 40 15 10 27 10 18 2 21 46 48 19 12 67 5 59 2 72 66 32 12 58 6 57 2 7 65 58 12 5 7 53 2 68 64 84 12 42 8 48 2 67 64 12 12 34 9 42 2 65 63 4 20 14 39 6 63 3 09 82 52 14 3 7 6 3...

Страница 12: ...5 6 4 9 4 66 1 05 11 67 5 96 5 96 1 28 17 61 7 06 7 06 1 52 23 45 20 5 98 3 58 1 96 17 57 5 72 4 39 1 23 16 33 6 25 5 63 1 35 19 09 7 1 6 91 1 53 23 68 5 15 1 9 1 9 0 33 1 92 2 8 2 8 0 48 2 84 3 96 3...

Страница 13: ...62 0 38 5 04 5 98 0 35 4 24 5 33 0 31 3 46 4 66 0 27 2 59 55 5 10 5 1 83 70 77 9 88 1 72 63 65 9 27 1 62 56 89 8 66 1 51 50 5 8 9 85 1 07 28 02 9 23 1 25 05 8 62 0 94 22 24 8 01 0 87 19 59 10 9 4 0 8...

Страница 14: ...0 59 5 26 15 9 81 0 57 4 97 8 88 0 51 4 2 7 94 0 46 3 44 6 98 0 4 2 6 55 5 15 23 2 65 67 13 14 33 2 5 60 33 13 43 2 34 53 89 12 54 2 19 47 82 8 14 33 1 56 26 76 13 44 1 46 23 92 12 54 1 36 21 23 11 65...

Страница 15: ...10 15 0 59 7 9 01 0 52 4 86 7 62 0 44 3 07 5 7 0 33 2 17 55 5 16 94 2 95 115 9 15 93 2 78 104 13 14 93 2 6 92 99 13 93 2 43 82 46 8 15 82 1 72 45 82 14 81 1 61 40 9 13 81 1 5 36 26 12 81 1 39 31 88 10...

Страница 16: ...7 Sound Levels H M L dB A 44 40 34 MUCS 24 W9 MUCS 36 W9 48 44 41 49 43 39 MUCS 20 W9 19 Four way Cassette DC Fan Coil Unit...

Страница 17: ...MUCS 20 W9 20 Four way Cassette DC Fan Coil Unit MUCS 24 W9...

Страница 18: ...MUCS 36 W9 21 Four way Cassette DC Fan Coil Unit...

Страница 19: ...8 Dimension Model A B C D E F MUCS 20 W9 180 140 85 350 145 195 MUCS 24 W9 MUCS 36 W9 180 140 155 350 155 205 22 Four way Cassette DC Fan Coil Unit...

Страница 20: ...9 Service Spaces Model A B C 230 170 260 300 190 330 MUCS 20 W9 MUCS 24 W9 MUCS 36 W9 23 Four way Cassette DC Fan Coil Unit...

Страница 21: ...CN13 CN19 CN18 POWER IN 3 2 V1 1 N L V2 XT1 4 RED RED BLUE BLUE RED BLUE BLACK BLUE ONLY 4 PIPE ONLY 4 PIPE G Y ALARM CN3 L N POWER S4 1 2 ON ENC1 S2 1 2 3 4 ON S1 1 2 3 4 ON S3 1 2 3 4 ON ON OFF CN1...

Страница 22: ...ECTOR SWITCH OVER HEAT H AUXILIARY HEATER CS WATER LEVEL SWITCH PUMP PUMP MOTOR Notes 1 SW1 must be set as the Table B 2 Two control mode is only connected with a valve valve 1 Four control models are...

Страница 23: ...oller Wait for the comeback of power Switch on the power Replace the fuse Replace the batteries or check the controller Air flowing normally but completely can t cooling Temperature is not set correct...

Страница 24: ...top up to the set time The TIMER on indicator goes off after a lapse of certain time Check whether the timer operation is started when the TIMER ON is indicated on the display Up to the set time the a...

Страница 25: ...insulation tightly around the hole of the unit as shown The ends of the side plate and the inner insulation must be completely adhered without leaving any clearance along the circumference of the hol...

Страница 26: ...become loose because of concrete shrinking b After installing the body please fasten the installation paper board onto the air conditioner with bolts M6 12 to determine in advance the sizes and posit...

Страница 27: ...n floor or against the wall or on bulgy objects Never crash or strike it 1 Remove the air inlet grill a Slide two grid switches toward the middle at the same time and then pull them up Refer to fig 12...

Страница 28: ...ir in grid in the procedure of reversed order 6 Relocate the installation cover a Fasten the rope of installation cover on the bolt of the installation cover b Press the installation cover into the pa...

Страница 29: ...water receiver through the stow tube 2 Turn on the power and operate the air conditioner under the COOLING mode Listen to the sound of the drain pump Check whether the water is discharged well a lag...

Страница 30: ...in power distribution The distribution has to be of low impedance normally the required impedance reaches at a 32A fusing point 2 No other equipment has to be connected with this power line 3 For deta...

Страница 31: ...12 7 2 Wiring figure 34 Four way Cassette DC Fan Coil Unit...

Страница 32: ...e user s requirement install the remote controller frame where the remote controller s signal can reach the indoor unit smoothly Test operation Set the air conditioner under the mode of COOLING with t...

Страница 33: ...SAT 34 93 652 53 57 www mundoclima com C N POLES 249 P1 ESPA A SPAIN 34 93 446 27 80 08013 BARCELONA...

Отзывы: