(2) Remove the installation covers at the four corners
.
Wrench off the bolts, loose the rope of the installation covers, and remove them. (Refer to fig. 12.10)
(3) Install the panel
a. Align the swing motor on the panel to the tubing joints of the body properly.
b. Fix hooks of the panel at swing motor and its opposite sides to the hooks of corresponding water receiver.
Then hang the other two panel hooks onto corresponding hangers of the body.
Caution:
Do not coil the wiring of the swing motor into the seal sponge.
c.
Adjust the four panel hook screws to keep the panel horizontal, and screw them up to the ceiling evenly.
d. Regulate the panel in the direction of the arrow slightly to fit the panel's center to the center of the ceiling's
opening. Guarantee that hooks of four corners are fixed well.
e. Keep fastening the screws under the panel hooks, until the thickness of the sponge between the body and
the panel's outlet has been reduced to about 4~6mm. The edge of the panel should contact with the ceiling well.
•
If the gap between the panel and ceiling still exists after fastening the screws, the height of the indoor
unit should be modified again.
•
You can modify the height of the indoor unit through the openings on the panel's four corners; if the lift of
the indoor unit and the drainpipe is not influenced.
(4) Hang the air-in grid to the panel, and then connect the lead terminator of the swing motor and that of
the control box with corresponding terminators on the body respectively.
(5) Relocate the air-in grid in the procedure of reversed order.
(6) Relocate the installation cover.
a. Fasten the rope of installation cover on the bolt of the installation cover.
b. Press the installation cover into the panel slightly.
11.6 Connect the Drain Pipe
Install the drainpipe of the indoor unit
The drainpipe can use PVC pipe (external diameter about 37
~
39mm, inner diameter is 32mm).
Joint drainpipe connector to the end side of water pumping pipe, and fix drainpipe together with water outflow
pipe and thermal insulation tube by clasp of water outflow pipe (attached).
Caution:
Don’t use forcing strength to crack the water-pumping pipe.
Water-pumping pipe and drainpipe from main body must be wrapped by insulation tube evenly, and bound
by tighten band for obstructing air getting in and coagulation.
Prevent from water backflow into unit inside during shutdown, the drain pipe shall place down side and drain
water to outdoor (drain side), the gradient of the drain pipe should be higher than (1/100), without salient and
water remain.(Refer to fig.12.11 a)
When connecting drainpipe, don’t drag the pipe that would pull the main unit. For this, please arrange
bearing points every 0.8 to 1.0 meter to avoid pipe be bended (See fig.12.11 b).
When connect a lengthen drainpipe, apply protective tube to wrap its indoor parts for ensuring the lengthen
part connected tightly.
In case the drainpipe outlet is higher than pumping connective pipe of the main body, the drainpipe must be
arranged upwards vertically by using connective assembly of the water outlet for vertical bending, and the
height of the drainpipe shall set to the defrosting pan surface no more than 1000mm, otherwise, too much
31
Four-way Cassette DC Fan Coil Unit
Содержание MUCS-20-W9
Страница 1: ...www mundoclima com Cassette 4 Ways FCU DC Service manual English CL04433 to CL04435 MUCS W9...
Страница 17: ...MUCS 20 W9 20 Four way Cassette DC Fan Coil Unit MUCS 24 W9...
Страница 18: ...MUCS 36 W9 21 Four way Cassette DC Fan Coil Unit...
Страница 31: ...12 7 2 Wiring figure 34 Four way Cassette DC Fan Coil Unit...
Страница 33: ...SAT 34 93 652 53 57 www mundoclima com C N POLES 249 P1 ESPA A SPAIN 34 93 446 27 80 08013 BARCELONA...