(2)  Remove the installation covers at the four corners

Wrench off the bolts, loose the rope of the installation covers, and remove them. (Refer to fig. 12.10) 

(3)  Install the panel 

a.  Align the swing motor on the panel to the tubing joints of the body properly. 

b.  Fix hooks of the panel at swing motor and its opposite sides to the hooks of corresponding water receiver. 

Then hang the other two panel hooks onto corresponding hangers of the body. 

Caution: 

Do not coil the wiring of the swing motor into the seal sponge. 

c. 

Adjust the four panel hook screws to keep the panel horizontal, and screw them up to the ceiling evenly. 

d.  Regulate the panel in the direction of the arrow slightly to fit the panel's center to the center of the ceiling's 

opening. Guarantee that hooks of four corners are fixed well. 

e.  Keep fastening the screws under the panel hooks, until the thickness of the sponge between the body and 

the panel's outlet has been reduced to about 4~6mm. The edge of the panel should contact with the ceiling well.   

• 

If the gap between the panel and ceiling still exists after fastening the screws, the height of the indoor 

unit should be modified again. 

• 

You can modify the height of the indoor unit through the openings on the panel's four corners; if the lift of 

the indoor unit and the drainpipe is not influenced. 

(4)  Hang the air-in grid to the panel, and then connect the lead terminator of the swing motor and that of 

the control box with corresponding terminators on the body respectively. 

(5)  Relocate the air-in grid in the procedure of reversed order. 

(6)  Relocate the installation cover. 

a.  Fasten the rope of installation cover on the bolt of the installation cover.   

b.  Press the installation cover into the panel slightly.   

11.6 Connect the Drain Pipe 

Install the drainpipe of the indoor unit 

 

The drainpipe can use PVC pipe (external diameter about 37

39mm, inner diameter is 32mm).   

 

Joint drainpipe connector to the end side of water pumping pipe, and fix drainpipe together with water outflow 

pipe and thermal insulation tube by clasp of water outflow pipe (attached). 

Caution: 

Don’t use forcing strength to crack the water-pumping pipe. 

 

Water-pumping pipe and drainpipe from main body must be wrapped by insulation tube evenly, and bound 

by tighten band for obstructing air getting in and coagulation. 

 

Prevent from water backflow into unit inside during shutdown, the drain pipe shall place down side and drain 

water to outdoor (drain side), the gradient of the drain pipe should be higher than (1/100), without salient and 

water remain.(Refer to fig.12.11 a) 

 

When  connecting  drainpipe,  don’t  drag  the  pipe  that  would  pull  the  main  unit.  For  this,  please  arrange 

bearing points every 0.8 to 1.0 meter to avoid pipe be bended (See fig.12.11 b). 

 

When connect a lengthen drainpipe, apply protective tube to wrap its indoor parts for ensuring the lengthen 

part connected tightly. 

 

In case the drainpipe outlet is higher than pumping connective pipe of the main body, the drainpipe must be 

arranged upwards vertically by using connective assembly of the water outlet for vertical bending, and the 

height of the drainpipe shall set to the defrosting pan surface no more than 1000mm, otherwise, too much 

 

 

31

 

 

 

  Four-way Cassette DC Fan Coil Unit  

 

Содержание MUCS-20-W9

Страница 1: ...www mundoclima com Cassette 4 Ways FCU DC Service manual English CL04433 to CL04435 MUCS W9...

Страница 2: ...nal Appearance 3 2 Features 3 3 Product lineup 4 4 Accessories 5 5 Specifications 6 6 Capacity Table 7 7 Sound Levels 26 8 Dimension 26 9 Service Spaces 30 10 Wiring Diagrams 31 11 Troubleshooting 32...

Страница 3: ...high efficiency Wireless remote control with LED display wired control is optional Safety grill for safety maintenance Built in drain water pump with 750mm pumping head Optional extended drainage pan...

Страница 4: ...durable motor The motor bearing can operate 80 000 hours continuously and easy for maintenance Low noise Advanced 3 D spiral fan design reduces air resistance and operating sound The motor bearing wi...

Страница 5: ...t M6 4 Tubing Fittings 2 Soundproof insulation sheath Drainpipe Fittings 1 Out let pipe 1 Out let pipe sheath 1 Out let pipe clasp 5 Tightening band Remote controller Its Frame 1 Remote controller R05...

Страница 6: ...7 Panel Net dimensions W H D mm 950 45 950 950 45 950 Packing size W H D mm 1035 90 1035 1035 90 1035 Net weight kg 6 6 Gross weight kg 9 9 Body Net dimensions W H D mm 840 300 840 840 300 840 Packin...

Страница 7: ...1 21 27 27 19 6 93 3 06 1 49 38 84 6 89 3 61 1 48 38 51 6 86 4 15 1 47 38 18 6 82 4 69 1 47 37 86 6 79 5 22 1 46 37 54 20 7 89 3 65 1 7 48 61 7 86 4 19 1 69 48 21 7 82 4 73 1 68 47 82 7 78 5 27 1 67...

Страница 8: ...27 3 24 3 24 0 7 10 18 3 85 3 85 0 83 13 63 20 3 38 2 15 1 1 10 64 3 34 2 69 0 72 10 71 3 4 3 09 1 1 10 98 3 88 3 79 0 83 13 77 5 15 0 92 0 92 0 16 0 86 1 38 1 38 0 24 1 29 2 27 2 27 0 39 2 65 2 94 2...

Страница 9: ...22 85 6 7 6 31 1 44 24 82 7 35 7 35 1 58 29 07 19 8 98 3 97 1 93 40 84 8 93 4 69 1 92 40 48 8 89 5 4 1 91 40 12 8 84 6 11 1 9 39 77 8 8 6 8 1 89 39 42 20 10 25 4 74 2 2 51 23 10 2 5 46 2 19 50 8 10 1...

Страница 10: ...3 3 0 73 7 21 4 21 4 21 0 91 10 77 5 02 5 02 1 08 14 49 20 4 17 2 72 1 44 10 2 4 21 3 44 0 91 10 74 4 38 4 03 0 94 11 51 5 03 4 95 1 08 14 57 5 15 1 22 1 22 0 21 1 03 1 82 1 82 0 31 1 54 2 63 2 63 0 4...

Страница 11: ...1 95 37 53 9 43 8 74 2 02 40 15 10 27 10 18 2 21 46 48 19 12 67 5 59 2 72 66 32 12 58 6 57 2 7 65 58 12 5 7 53 2 68 64 84 12 42 8 48 2 67 64 12 12 34 9 42 2 65 63 4 20 14 39 6 63 3 09 82 52 14 3 7 6 3...

Страница 12: ...5 6 4 9 4 66 1 05 11 67 5 96 5 96 1 28 17 61 7 06 7 06 1 52 23 45 20 5 98 3 58 1 96 17 57 5 72 4 39 1 23 16 33 6 25 5 63 1 35 19 09 7 1 6 91 1 53 23 68 5 15 1 9 1 9 0 33 1 92 2 8 2 8 0 48 2 84 3 96 3...

Страница 13: ...62 0 38 5 04 5 98 0 35 4 24 5 33 0 31 3 46 4 66 0 27 2 59 55 5 10 5 1 83 70 77 9 88 1 72 63 65 9 27 1 62 56 89 8 66 1 51 50 5 8 9 85 1 07 28 02 9 23 1 25 05 8 62 0 94 22 24 8 01 0 87 19 59 10 9 4 0 8...

Страница 14: ...0 59 5 26 15 9 81 0 57 4 97 8 88 0 51 4 2 7 94 0 46 3 44 6 98 0 4 2 6 55 5 15 23 2 65 67 13 14 33 2 5 60 33 13 43 2 34 53 89 12 54 2 19 47 82 8 14 33 1 56 26 76 13 44 1 46 23 92 12 54 1 36 21 23 11 65...

Страница 15: ...10 15 0 59 7 9 01 0 52 4 86 7 62 0 44 3 07 5 7 0 33 2 17 55 5 16 94 2 95 115 9 15 93 2 78 104 13 14 93 2 6 92 99 13 93 2 43 82 46 8 15 82 1 72 45 82 14 81 1 61 40 9 13 81 1 5 36 26 12 81 1 39 31 88 10...

Страница 16: ...7 Sound Levels H M L dB A 44 40 34 MUCS 24 W9 MUCS 36 W9 48 44 41 49 43 39 MUCS 20 W9 19 Four way Cassette DC Fan Coil Unit...

Страница 17: ...MUCS 20 W9 20 Four way Cassette DC Fan Coil Unit MUCS 24 W9...

Страница 18: ...MUCS 36 W9 21 Four way Cassette DC Fan Coil Unit...

Страница 19: ...8 Dimension Model A B C D E F MUCS 20 W9 180 140 85 350 145 195 MUCS 24 W9 MUCS 36 W9 180 140 155 350 155 205 22 Four way Cassette DC Fan Coil Unit...

Страница 20: ...9 Service Spaces Model A B C 230 170 260 300 190 330 MUCS 20 W9 MUCS 24 W9 MUCS 36 W9 23 Four way Cassette DC Fan Coil Unit...

Страница 21: ...CN13 CN19 CN18 POWER IN 3 2 V1 1 N L V2 XT1 4 RED RED BLUE BLUE RED BLUE BLACK BLUE ONLY 4 PIPE ONLY 4 PIPE G Y ALARM CN3 L N POWER S4 1 2 ON ENC1 S2 1 2 3 4 ON S1 1 2 3 4 ON S3 1 2 3 4 ON ON OFF CN1...

Страница 22: ...ECTOR SWITCH OVER HEAT H AUXILIARY HEATER CS WATER LEVEL SWITCH PUMP PUMP MOTOR Notes 1 SW1 must be set as the Table B 2 Two control mode is only connected with a valve valve 1 Four control models are...

Страница 23: ...oller Wait for the comeback of power Switch on the power Replace the fuse Replace the batteries or check the controller Air flowing normally but completely can t cooling Temperature is not set correct...

Страница 24: ...top up to the set time The TIMER on indicator goes off after a lapse of certain time Check whether the timer operation is started when the TIMER ON is indicated on the display Up to the set time the a...

Страница 25: ...insulation tightly around the hole of the unit as shown The ends of the side plate and the inner insulation must be completely adhered without leaving any clearance along the circumference of the hol...

Страница 26: ...become loose because of concrete shrinking b After installing the body please fasten the installation paper board onto the air conditioner with bolts M6 12 to determine in advance the sizes and posit...

Страница 27: ...n floor or against the wall or on bulgy objects Never crash or strike it 1 Remove the air inlet grill a Slide two grid switches toward the middle at the same time and then pull them up Refer to fig 12...

Страница 28: ...ir in grid in the procedure of reversed order 6 Relocate the installation cover a Fasten the rope of installation cover on the bolt of the installation cover b Press the installation cover into the pa...

Страница 29: ...water receiver through the stow tube 2 Turn on the power and operate the air conditioner under the COOLING mode Listen to the sound of the drain pump Check whether the water is discharged well a lag...

Страница 30: ...in power distribution The distribution has to be of low impedance normally the required impedance reaches at a 32A fusing point 2 No other equipment has to be connected with this power line 3 For deta...

Страница 31: ...12 7 2 Wiring figure 34 Four way Cassette DC Fan Coil Unit...

Страница 32: ...e user s requirement install the remote controller frame where the remote controller s signal can reach the indoor unit smoothly Test operation Set the air conditioner under the mode of COOLING with t...

Страница 33: ...SAT 34 93 652 53 57 www mundoclima com C N POLES 249 P1 ESPA A SPAIN 34 93 446 27 80 08013 BARCELONA...

Отзывы: