CAUTION
If the outdoor unit is installed higher than the
indoor unit:
-It is recommended that vertical suction risers
not be upsized. Proper oil return to the
compressor should be maintained with suction
gas velocity. If velocities drop below 7.62m/s
(1500fpm (feet per minute)), oil return will be
decreased. An oil trap should be installed every
6m of vertical suction line riser.
The outdoor unit is installed higher than the
indoor unit
Oil traps
CAUTION
•
If the indoor unit is installed higher than the
outdoor unit:
An oil trap should be installed every 10m
of vertical suction line riser.
-If oil flows back into the outdoor unit’s
compressor, this might cause liquid
compression or deterioration of oil return.
Oil traps in the rising gas piping can prevent
this.
The indoor unit is installed higher than the
outdoor unit
79