       Branch header must be connected with indoor units directly, 
       the further branch connection is not allowed. 

Select branch joint

Select the branch joint according to the total designed capacity 
of indoor units which it connects to. If this capacity is more than 
that of the outdoor unit, then select the connection according to 
the outdoor unit.

The selection of branch header depends on the quantity of 
branches it connects to. 

0.8

1.3

1.6

2

2.8

3.5

4.5

5

22

0.6

18

100

4

112

3.2

90

36

45

56

2.5

71

125

4.3

120

140

80

Capacity 
 ranking 

   Capacity
(horsepower) 

Capacity 
 ranking 

    Capacity
(horsepower) 

Connection method

Table 4-9

Piping sizes at the branch pipe

1

28

When the outdoor unit connects one indoor unit

4.6  Illustration

Outdoor Unit((Take Model 280 for example)

Caution: Suppose in the displayed piping system, the total equi-
valent piping length of air side + liquid side is longer than 90m. 

Fig.4-6

Pipe diameter of the connector in the outdoor unit's body

When capacity of indoor unit greater than the sum of 100%, capacity 
of indoor unit will be attenuated.
When capacity of indoor unit greater than or equal to the sum of 
120%, in order to ensure the effectiveness of machine, and then try to 
open the indoor units at different time.

NOTE

The indoor unit capacity total can not exceed 130% of the outdoor
unit load.
Overloading reduces the corresponding capacity.

The first line Branch Pipe

1

1

1

1

1

1

Indoor unit

$

%

'

(

&

D

E

F

H

I

G

/

/

/

/

/

Four-sided air outlet
56~80

Four-sided air outlet
28~45

Wall mounted 22~45

Thin duct type 71

12.7(Flaring nut)

12.7(Flaring nut)

15.9(Flaring nut)

15.9(Flaring nut)

6.4(Flaring nut)

Wall mounted 56

15.9(Flaring nut)

9.5(Flaring nut)

6.4(Flaring nut)

9.5(Flaring nut)

9.5(Flaring nut)

One-sided air outlet
18~45

12.7(Flaring nut)

6.4(Flaring nut)

One-sided air outlet
56

15.9(Flaring nut)

9.5(Flaring nut)

Low static pressure
18~45

12.7(Flaring nut)

6.4(Flaring nut)

Low static pressure 56

15.9(Flaring nut)

9.5(Flaring nut)

A5 duct type 22~45 

A5 duct type 56~140

12.7(Flaring nut)

6.4(Flaring nut)

Refrigerant 

R410A

A (TYPE)

!"#$%"&'$()*

+",-"&$%"&'$()*$

Table 4-6

(A: the total capacity of indoor units)

Four-way Cassette Type
15~45

12.7(Flaring nut)

6.4(Flaring nut)

Tow-way Cassette Type
22~45

12.7(Flaring nut)

6.4(Flaring nut)

Tow-way Cassette Type
56~71

15.9(Flaring nut)

9.5(Flaring nut)

Console Type 22~45

12.7(Flaring nut)

6.4(Flaring nut)

Ceiling And Floor Type 
36~45

12.7(Flaring nut)

6.4(Flaring nut)

Ceiling And Floor Type 
56~160

15.9(Flaring nut)

9.5(Flaring nut)

Expose And Concealed 
Floor-standing type 22~45

Expose And Concealed 
Floor-standing type 56~80

12.7(Flaring nut)

6.4(Flaring nut)

15.9(Flaring nut)

9.5(Flaring nut)

 

15.9(Flaring nut)

9.5(Flaring nut)

Welding or Flaring 

Flaring

Branch pipe

Indoor unit

     Outdoor unit

Gas side 

Liquid side

Table 4-5

Flaring

Welding or Flaring 

Welding or Flaring 

Welding or Flaring 

Piping connection

                     side

Pipe diameter of outdoor unit's connector(mm)

)../.

)0./1

Model(kW)

28

33.5

26

Table 4-7

Gas Side

Liquid Side 

33.5

Outdoor Unit
      (kW)

Capacity of 
Outdoor unit 
(horsepower)

Maximum 
Quantity of 
Indoor unit

Sum Capacity 
of Indoor unit 
(horsepower)

50%~130%

50%~130%

16

20

10

12

Table 4-8

28

33.5

26

Table 4-10

When outdoor 

unit is top

When outdoor 

unit is bottom

less than 10

MODEL
 (kW)

The max height drop(m)

The length of 

refrigerant 

pipe(m)

The number 

of bends

28

33.5

25

25

20

20

50

50

Installation manual

8

Mini MVD V6M

Содержание MINI MVD V6M

Страница 1: ...English MVD www mundoclima com Installation and owner s manual MINI MVD V6M OUTDOOR UNIT and information requirements CL23274 to CL23275 MVD V280W DGN1 MVD V335W DGN1...

Страница 2: ...d use This unit must be installed by a professional according RD 795 2010 RD 1027 2007 and RD 238 2013 The power supply must be SINGLE PHASE one phase L and one neutral N with his grounded power GND s...

Страница 3: ...ly if there are possible damage Do not install in a place that might increase the vibration of the unit To avoid personal injury with sharp edges be careful when handling parts Perform installation wo...

Страница 4: ...of the conventional refrigerant take out the flare nut attached to the main unit of the air conditioner and use it Before installation Be careful to the following items before installation Air purge...

Страница 5: ...or unit power cord and connecting wire at least 1m away from TV set or radio to prevent noise or picture interference Strong wind Strong wind 3 2 Installation space Unit mm 300 600 300 0 0 0 3 Wall or...

Страница 6: ...the frozen condensed water will block up the water outlet please pull out the rubber stopper of the reserve water outlet If that still fails to satisfy for the water draining please knock open the ot...

Страница 7: ...connected to the indoor unit is at least 0 5m 4 4 Connecting method main pipe The branch pipes of indoor unit The pipe after the first branch do not drect connect with the indoor unit The pipe after...

Страница 8: ...g nut 15 9 Flaring nut 6 4 Flaring nut Wall mounted 56 15 9 Flaring nut 9 5 Flaring nut 6 4 Flaring nut 9 5 Flaring nut 9 5 Flaring nut One sided air outlet 18 45 12 7 Flaring nut 6 4 Flaring nut One...

Страница 9: ...e gas side main pipe size Inner branch pipes are a f the size selection please refers to Table4 6 Note The max length of the branch pipe should not longer than 15m Indoor unit branch pipe The main pip...

Страница 10: ...t to be Added Using vacuum pump to do the vacuum never using refrigerant to expel the air Vacuuming should be done from both liquid side and gas side simultaneously Calculate the added refrigerant acc...

Страница 11: ...rol system connection of the outdoor unit P Q E L N P Q E L N P Q E L N P Q E L N L2 L3 N L1 K2 E O K1 A E Y E P X Q E Power supply for the outdoor unit monitor Outdoor unit Reserved Optional L N K1 K...

Страница 12: ...he signal cable insert electric wires in their respective electric wire pipes and reserve a proper inter wire distance distance between power cables lower than 10 A 300 mm lower than 50 A 500 mm Use a...

Страница 13: ...NOTE Single phase indoor unit Wire controller The reserved wire control function is indicated in broken line table users can purchase the wire controller when necessary in broken line table users can...

Страница 14: ...tilator A Ventilation peristome Leak hunting siren should be installed in places easily keep refrigerant Indoor unit Outdoor unit Indoor unit Room full of leak refrigerant All refrigerant has run up F...

Страница 15: ...ween main board and compressor drive board Inverter module protection Qty of indoor units mismatching High pressure sensor error M HOME for the indoor and outdoor units does not match Phase sequence e...

Страница 16: ...equipment Failure to observe a warning may result in death The appliance shall be installed in accordance with national wiring regulations Do not use the air conditioner for other purposes In order to...

Страница 17: ...t supervision When capacity of indoor unit greater than the sum of 100 capacity of indoor unit will be attenuated When capacity of indoor unit greater than or equal to the sum of 120 in order to ensur...

Страница 18: ...starts immediately after operation The indoor unit of the intelligent inverter centralized air conditioner can be controlled solely but the indoor unit in the same system can not run cooling and heati...

Страница 19: ...ble Irrecoverable Recoverable Recoverable Recoverable Recoverable Recoverable Recoverable Recoverable P8 F1 E1 High pressure protection M HOME for the indoor and outdoor units does not match Display F...

Страница 20: ...d when the system is in cooling operation or at a stop When the drain pump optional accessories is in operation this noise is heard A pishi pishi squeaking sound is heard when the system stops after h...

Страница 21: ...indoor unit heat exchanger is dirty The air filter is dirty Inlet outlet of indoor outdoor units is blocked Doors and windows are open Sunlight directly shine Too much heat resource Outdoor temp is to...

Страница 22: ...r goes off after a lapse of certain time Check whether the timer operation is started when the TIMER ON is indicated on the display Up to the set time the air conditioner will automatically start and...

Страница 23: ...3 6 4 2 6 732C 3 2C 87 5 3 6 37 3 37 62 and hydrogen sulphide G F7 2 88 8 7 62 26 5 26 63 2 5 E6 3 where the air conditioning is on for 24 hours a day As the use of the unit for many years will eventu...

Страница 24: ...oad at given outdoor temperatures Tj Prated c Pdc Pdc Pdc Pdc Cdc 0 25 33 5 kW Seasonal space cooling energy efficiency s c 199 8 Symbol Value Unit Off mode Thermosat off mode Crankcase heater mode St...

Страница 25: ...d heating capacity Degradation co efficient for heat pumps Declared heating capacity for part load at indoor teperature 20 and outdoor temperatures Tj Declared coefficient of performance or gas utilis...

Страница 26: ...y factor for part load at given outdoor temperatures Tj Prated c Pdc Pdc Pdc Pdc Cdc 0 25 28 0 kW Seasonal space cooling energy efficiency s c 201 0 Symbol Value Unit Off mode Thermosat off mode Crank...

Страница 27: ...ed heating capacity Degradation co efficient for heat pumps Declared heating capacity for part load at indoor teperature 20 and outdoor temperatures Tj Declared coefficient of performance or gas utili...

Страница 28: ...www mundoclima com C N POLES 249 P1 08013 BARCELONA SPAIN 34 93 446 27 80...

Отзывы: