CAUTION
The operation lamp is flashing rapidly (5Hz). This lamp is still
flashing rapidly after turn off the power and turn on again.
(Refer to Table 8-1, Table 8-2 and Table 8-3)
Remote controller receives malfunction or the button does not
work well.
A safety device such as a fuse, a breaker frequently actuates.
Obstacles and water enter the unit.
Water leaks from indoor unit.
Other malfunctions.
If one of the following malfunctions occur, stop operation, shut
off the power, and contact with your dealer.
If the system does not properly operate except the above
mentioned cases or the above mentioned malfunctions is
evident, investigate the system according to the following
procedures.
(Refer to Table 8-4)
Please cut off the power supply when appearing the
above malfunction, check if the voltage provided is out of
range, check if the installation of air-conditioner is
correct, then electrify again after 3 minutes power off. If
the problem is still existent, please contact the local
service station or the equipment provider.
Table 7-1a
MALF U N C T I ON & PROT EC T I ON D EF I N E
D I SPLAY
LED 4
LED 3
LED 2
LED 1
E 8
E 1
E 2
E 3
E 4
E 7
E E
E d
F3
F4
In-Out door unit C OMM. C heck ing
channel is abnormal
R oom TEMP. s ens or check ing
channel is abnormal
Pipe TEMP. Sens or check ing
channel is abnormal(T2)
EPPR OM malf unct ion
Indoor fan motor speed out of control
Wat er-lev el alarm malf unct ion
Out door malf unct ion
Indoor twins communication malfunction
Other malfunction of twins
Light
Flas hing at 2.5H Z
Flas hing at 0 . 5 H Z
DIGITAL TUBE
ALARM
DEF.FAN
TIMER
OPERATION
Pipe TEMP. Sens or check ing
channel is abnormal(T2B)
NO.
1
2
3
4
5
6
7
8
9
10
Table 8-1 Indoor unit error codes
8. TROUBLESHOOTING
8.1 Troubles and causes of air conditioner
OWNER'S MANUAL
Run Lamp
(flashes)
1
E0
OFF
1
Indoor EEPROM error
2
E1
OFF
2
Communication malfunction beetwen indoor and outdoor units
3
E3
OFF
4
Indoor fan speed malfunction
4
E4
OFF
5
Indoor room temperature sensor (T1) open circuit or short circuit
5
E5
OFF
6
Indoor coil temperature sensor (T2) open circuit or short circuit
6
EC
OFF
7
Regfrigerante leakage detection malfunction
7
EE
OFF
8
Water-level alarm malfunction
8
E8
OFF
9
Communication malfunction beetwen two indoor units (for Twin systems)
9
E9
OFF
10
Other malfunction of Twins systems
10
Ed
OFF
11
Outdoor unit is faulty (for old comunicaction protocol)
11
F0
ON
1
Current overload protection
12
F1
ON
2
Outdoor room temperature sensor (T4) open circuit or short circuit
13
F2
ON
3
Outdoor coil temperature sensor (T3) open circuit or short circuit
14
F3
ON
4
Outdoor discharge temperature sensor (T5) open circuit or short circuit
15
F4
ON
5
Outdoor EEPROM error
16
F5
ON
6
Outdoor fan speed malfunction
17
F6
ON
7
Coil temperature sensor (T2b) open circuit or short circuit (for some Multi)
18
F7
ON
8
Lifting panel comunication checking chanel is abnormal
19
F8
ON
9
Lifting panel malfunction
20
F9
ON
10
Lifting panel is not closed
21
P0
FLASH
1
Inverter module IPM protection
22
P1
FLASH
2
High/Low voltage protection
23
P2
FLASH
3
High temperature protection of compressor top
24
P3
FLASH
4
Outdoor low temperature protection
25
P4
FLASH
5
Compressor drive error
26
P5
FLASH
6
Mode conflict (for some Multi models)
27
P6
FLASH
7
Low pressure protection of compressor
28
P7
FLASH
8
Sensor of outdoor IGBT is faulty
29
CP
--
--
Remote contact OFF enabled
Timer Lamp
Code
Nº
Description
25