2.15.2 Selecting Relay output pulse width.
The pulse width can be set between 0msec (off) and
200msec, in steps of 20msec.
ACTION : Click On Pulse
Width Button.
COMMENTS : Pulse Width
Selection box is displayed.
ACTION : Enter value
between 20msec and
200msec.
COMMENTS : Pulse widths
are in steps of 20msec. If
60msec enter 60 and click on
OK.
2.15.3 Selecting Relay Divisor
This allows the user to set the relay to pulse every 1, 10 ,
100 or 1000 counts. i.e. If the divisor is set to 1 every time
M560 registers and stores 1 count relay the pulses once. If
set to 100, the relay only pulses once after M560 has
registered and stored 100 counts. The M560 always
registers and stores the number of counts regardless of what
the relay divisor is set to. i.e. If the kilowatt consumption
was 500 kW per hour and relay divisor was set to 100 you
would get 5 pulses an hour.
ACTION : Click On Relay
Divisor Button.
COMMENTS : Divisor
selection box is displayed.