background image

MECHANICAL INSTALLATION GUIDELINES

1. Prepare the panel cutout with proper dimensions as 
    shown above.

   

2. Fit the unit into the panel with the help of clamp given.

   

3. The equipment in its installed state must not come in 
    close proximity to any heating source, caustic vapors, oil 
    steam, or other unwanted process byproducts.
   

4. Use the specified size of crimp terminal (M3.5 screws) to 
    wire the terminal block. Tightening the screws on the 
    terminal block using the tightening torque of the range of 
    1.2 N.m.

   

5. Do not connect anything to unused terminals. 
   

INSTALLATION GUIDELINES

1. This equipment, being built-in-type, normally becomes a 
    part of main control panel and in such case the terminals
    do not remain accessible to the end user after installation 
    and internal wiring.                                                                                                                                                                                                                                                                                                                                                                                                                      

2. Do not allow pieces of metal, wire clippings, or fine 
    metallic fillings from installation to enter the product or 
    else it may lead to a safety hazard that may in turn 
    endanger life or cause electrical shock to the operator.      

3. Circuit  breaker or mains switch must be installed 
    between power source and supply terminal to facilitate
    power ‘ON’ or ‘OFF’ function. However this mains switch 
    or circuit breaker must be installed at convenient place 
    normally accessible to the operator.     

4. Use and store the instrument within the specified 
    ambient temperature and humidity ranges as mentioned 
    in this manual.     

MAINTENANCE

1. The equipment should be cleaned regularly to avoid 
    blockage of ventilating parts.         

2. Clean the equipment with a clean soft cloth. Do not use 
    isopropyl alcohol or any other cleaning agent.

3. Fusible resistor must not be replaced by operator. 

Read complete instructions prior to installation 
and operation of the unit. 

WARNING :

 Risk of electric shock.

SAFETY PRECAUTION

!

       All safety related codifications, symbols and instructions 
that appear in this operating manual or on the equipment 
must be strictly followed to ensure the safety of the operating 
personnel as well as the instrument. 

      If all the equipment is not handled in a manner specified 
by the manufacturer, it might impair the protection provided 
by the equipment.

WARNING GUIDELINES

WARNING : Risk of electric shock.

 1. To prevent the risk of electric shock, power supply to the 
     equipment must be kept OFF while doing the wiring 
     arrangement. Do not touch the terminals while power is 
     being supplied.  

 2. To reduce electro magnetic interference, use wire with 
     adequate rating and twists of the same of equal size shall 
     be made with shortest connection.            

 3. Cable used for connection to power source, must have a 
     cross section of 1mm or greater. These wires should have 
     insulations capacity made of at least 1.5kV.      

 4. When extending the thermocouple lead wires, always use
     thermocouple compensation wires for wiring for the RTD
     type, use a wiring material with a small lead resistance
     (5    max per line) and no resistance differentials among 
     three wires should be present.    
 5. A better anti-noise effect can be expected by using 
     standard power supply cable for the instrument.         

Ω

STATUS LED DESCRIPTION

KEY OPERATION

To enter in parameter setting

For start/stop PID auto tuning

Press 
6 sec

Press 3 sec

+

To go in factory setting mode

PRESS KEY

FUNCTION

OPERATOR MODE

To reset process after soak time end

PARAMETER SETTING MODE

To set parameter value and 
move to the next parameter

To increment parameter value.

To decrement parameter value.

Set parameter to be save & exit. 

4 - Auto Tuning on indication

1 - Soak Time counting indication

1
2

3

2345

2500

4

2 - Control O/P 1 

3 - Control O/P 2  

Page -2

Содержание UTC-2200G

Страница 1: ...TROL METHOD TERMINAL CONNECTION PV Process value SV Set Value Accuracy 3 ON OFF control 8 9 3 Wire RTD 2 Wire RTD Thermocouple Install jumper when using 2 Wire RTD Sensor Input 8 9 10 72 85 68 68 3 ME...

Страница 2: ...or to installation and operation of the unit WARNING Risk of electric shock SAFETY PRECAUTION All safety related codifications symbols and instructions that appear in this operating manual or on the e...

Страница 3: ...e Out Band Alarm Heating Mode Low Alarm Cooling Mode Outband Alarm Alarming Mode OFF Mode Yes No Save Set 2 Individual to Set 1 Set 2 Reletive to Set 1 Second Hour Minute Factory Setting ALM2 S2MD R1D...

Страница 4: ...t power on NO In case of power supply failure soak time counting will be restarted at next power on Soak time memory MEMO END SAVE NO In case of soak time end if user apply SAVE in configuration then...

Страница 5: ...alarm alarm BASIC CONFIGURATION Password is 73 If CTR1 PID CONTROL PARAMETER SETTING Press key to Save Exit If CTR 2 BL TP If CTR1 TP Password is 37 Press key to Save Exit R2MD OFF S2MD INDI 0 to 999...

Страница 6: ...TP Selected If ON OFF Selected If LOW HIGH Ab L Select If PID TP Selected If ON OFF Selected Heat Heat Case 2 If PID TP Selected Heat Cool Case 3 If IN B AB O OT B Select If ON OFF Selected If ON OFF...

Страница 7: ...If LOW HIGH Ab L Select If IN B AB O OT B Select If LOW HIGH Ab L Select If IN B AB O OT B Select If PID TP Selected If ON OFF Selected Heat Alarm Case 4 Cool Cool Case 5 Cool Alarm Case 6 Page 7...

Страница 8: ...Auto tuning function automatically computes and sets the Proportional band Pb Integral time It Derivative time dt and cycle time as per process characteristics Tuning LED will turn ON during Auto Tuni...

Отзывы: