4. Specification
Measuring function : Earth resistance, AC current (Load & leakage)
A/D conversion : Dual slope integration mode
Safety standard
: IEC 61010-1,IEC61010-2-032
Installation CAT
Ⅱ
600V or CAT
Ⅲ
300V
Sampling
: Approx. 2 times/second for AC current
Measuring time
: Approx. 30 second for earth resistance
Display : LCD16 letters/characters x 2 line with contrast
adjuster
Over range indication
: “OVER” on LCD
Low battery indication
: “B” mark on LCD
Data hold indication
: “DH” mark on LCD for AC current measurement
Detection method : Synchronous detection
Accuracy (23°C ± 5ºC, 80% RH or less) :
Earth resistance (Earth current: Less than 1A)
Range Resolution Accuracy
Less than 10
Ω 0.1Ω
±
0.5
Ω
10 ~ 50Ω 0.1Ω
±
2.0
Ω
50 ~ 150Ω 0.1Ω
±
5.0
Ω
150 ~ 200Ω 0.1Ω
±
20
Ω
Note
: Accuracy is specified by standard resistance with following test configuration.
- 6 -
Induction CT
Measuring CT