Equivalent circuit
Test result = RE+(R
1
//R
2
//R
3
// - - -)
Resistance of parallel connection (R
1
//R
2
//R
3
// - - -)
<
RE
Test result
≒
RE
The greater the number of parallel paths, the closer the measured value will be
to the actual earth resistance.
8-4. Earth resistance measurements for the earthing electrode
RE1 to RE4…..Individual earth resistances of tested earthing system
Test result = RE4+(RE3//RE2//RE1)
Resistance of parallel connection (RE3//RE2//RE3//)
<
RE4
Test result
≒
RE4